Loading...
Hard 8 BBQ CS070612 MEMORANDUM FROM THE DEPARTMENT OF PUBLIC WORKS To: Garreth Campbell, Construction Inspector Engineering From: Danny Hightower, Utilities Division Public Works Date: June 12, 2007 RE: Walk-thru Hard 8 BBQ 1. Cut in street ML V & mark with blue paint on lid on Bethel Rd. Need 3' extension. 2. Need curb stop on IRR & DOM. Lower to 3' on extension & mark DOM & IRR on drive in blue. 3. DOM & IRR for drainage on vault. 4. Paint vault & meter can lids blue. 5. Vault must be dry. 6. Vaults DC and COM & IRR-test paperwork needed. 7. First fire hydrant needs extension & paint lid red on valve stack & street marker button blue. 8. Re-paint fire hyd. Red. 9. Extension on main line valve next to first fire hyd. 10. Paint fire line to building & paint valve lid red and mark on curb red. 11. Second fire hyd. Paint valve stack red and blue street marker button. Mark on curb red. 12. Replaced lock hasp on vault - Freeport. 13. Extension on Freeport ML V in street - mark curb. 14. Missing City sewer cleanout. Cannot inspect. CITY OF COPPELL PUBLIC WORKS DEPARTMENT