Gateway BP(3.1)-LR070703
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of In-Place Density Testing
Report No.: 289893
Project No.: 0712786
Date of Service: 06/12/2007
Report Date: 07/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Perform In-Place Density Testing
PROJECT DATA
Contractor: Constructors & Associates
Test Method: ASTM 0-2922
ASTM 0-3017
Gauge: Troxler 3430
Gauge Serial No: 34008
Test Mode:
Standard Counts
Moisture Density
Current: 654 Current: 2653
Previous: 649 Previous: 2608
MOISTURE DENSITY RELATIONS
MID No.
277809
Description
Moisture
%
Maximum
Density
(pet)
89.0
Project Requirements
Moisture Density
Optimum +4 95 min
Dark Brown / Clay
27.0
FIELD DENSITY TESTS
Test Probe MID Moisture Wet Density Dry Density Density
No Test Location Depth No. % (pet) (pet) (%max)
Pavement subgrade
Retest #5 from report 288564 dated 5/24/07 6" 277809 30.5 116.7 89.4 100
and 6/11/07
Pavement subgrade
2 Parking lot north from building 1, 65' north and 6" 277809 30.2 115.4 88.6 100
45' west of northeast building corner
Pavement subgrade
3 Parking lot north from building 1, 65' north and 6" 277809 30.4 115.7 88.7 100
200' west of northeast building corner
Remarks: Still stockpiles of material north of test 2 and 3
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(SS/LB) Page 1 of 2