Report of Concrete Compressive Strength Tes1
Report No.: 289430
Project No.: 0712786
Date of Service: 06/07/2007
Report Date: 07/09/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sample~
back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: LMC
Plant: 7
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 3.0' - 5.0'
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1551
Placement Date: 06/07/2007
Weather Conditions: Clear
Time Sampled: 03:45pm
Temperature - Air: 850F
Truck No: 1045
Air Content: 3.8%
Overall Placement Location:
Inlet bottoms at Gateway Business Center.
Measured
Slump
(inches)
5.0
Batch time: 02:59pm
Concrete: 900F
Ticket No: 7178838
Unit Weight (pct): NA
Sample Location:
Station 1+42.7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
- -
1 1 06/14/2007 7 6.00 28.27 79,820 2,820 Unbonded Cap
1 2 07/05/2007 28 6.00 28.27 116,070 4,110 Unbonded Cap
1 3 07/05/2007 28 6.00 28.27 108,970 3,850 Unbonded Cap
Average 3,980
1 4 08/02/2007 56