Gateway BP(3.1)-LR070725
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Reinforcing Steel Inspection
Report No.: 292788
Project No.: 0712786
Date of Service: 07/19/2007
Report Date: 07/25/2007
Project: Gateway Business Center
Coppell, Texas
Services: Reinforcing Steel Inspection
Report of Inspection
Locations and Items Inspected:
Northeast section of paving
~em s Ins peeled: Co nfo rm ing Non ~ems Ins peeled: Co nfo rm ing Non ~em s Inspected: Conform ing Non
Conform ing Conform ing Conform ing
P lacing Drawings Bar Lengt h Co lum n Ties Properly
Approved x and Shape x Tied and Spaced NA
Bar Size x Pro per B ar P iacern ent x Stirrup Spac ing NA
Bar Grade x Pro perly Tied x Stirrup Type NA
Bars Clean x Dowel Bars in Place x Lapped Splices x
Form Clean x Proper B ar Supports x Co mer Bars NA
Numberof Bars x ProperCover NA Mechanical Splices NA
Discrepancies / Comments: 1. Paving reinforcement covered with soil on north side of paving.
2. Missing ties on east side of placement.
3. Not chaired, all placement.
Discrepancies 1 and 2 were corrected prior to concrete placement.
Discrepancy 3 required re-inspection.
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our lelters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/JB) Page 1 of 2
Rone Engineering
.....
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of In-Place Density Testing
Report No.: 292440
Project No.: 0712786
Date of Service: 07/17/2007
Report Date: 07/25/2007
Project: Gateway Business Center
Coppell, Texas
Services: Perform In-Place Density Testing
FIELD DENSITY TESTS
Test Probe MID Moisture Wet Density Dry Density Density
No Test Location Depth No. % (pet) (pet) (% max)
Paving subgrade
6 Northeast paving, 225' south, 120' west from 6" 277811 25.7 118.2 94.0 100
northeast corner, grade
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(JB/JB) Page 2 of 3
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of In-Place Density Testing
Report No.: 292440
Project No.: 0712786
Date of Service: 07/17/2007
Report Date: 07/25/2007
Project: Gateway Business Center
Coppell, Texas
Services: Perform In-Place Density Testing
PROJECT DATA
Contractor: Constructors & Associates
Test Method: ASTM D-2922
ASTM D-3017
Gauge: Troxler 3430
Gauge Serial No: 35558
Test Mode: DT
Standard Counts
Moisture Density
Current: 604 Current: 2430
Previous: 609 Previous: 2475
MOISTURE DENSITY RELATIONS
MID No.
277809
277811
Description
Moisture
%
Maximum
Density
(pet)
89.0
94.0
Project Requirements
Moisture Density
Optimum +4 95 min
Optimum +4 95 min
Dark Brown I Clay
Tannish Brown & Dark Brown I Silty Clay
27.0
24.0
FIELD DENSITY TESTS
Test Probe MID Moisture Wet Density Dry Density Density
No Test Location Depth No. % (pet) (pet) (% max)
Paving subgrade
Northeast paving, 30' south, 50' west from 6" 277809 27.4 112.7 88.5 99
northeast corner, grade
Paving subgrade
2 Northeast paving, 150' south, 50' west from 6" 277809 27.2 111.9 88.0 99
northeast corner, grade
Paving subgrade
3 Northeast paving, 200' south, 50' west from 6" 277811 26.3 116.8 92.5 98
northeast corner, grade
Paving subgrade
4 Northeast paving, 50' south, 150' west from 6" 277811 25.7 114.4 91.0 97
northeast corner, grade
Paving subgrade
5 Northeast paving, 150' south, 120' west from 6" 277811 26.6 118.6 93.7 100
northeast corner, grade
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(JB/JB) Page 1 of 3
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of In-Place Density Testing
Report No.: 291988
Project No.: 0712786
Date of Service: 07/12/2007
Report Date: 07/25/2007
Project: Gateway Business Center
Coppell, Texas
Services: Perform In-Place Density Testing
PROJECT DATA
Contractor: Constructors & Associates
Test Method: ASTM 0-2922
ASTM 0-3017
Gauge: Troxler 3430
Gauge Serial No: 35558
Test Mode: OT
Standard Counts
Moisture Density
Current: NA Current: NA
Previous: NA Previous: NA
MOISTURE DENSITY RELATIONS
MID No.
277811
Description
Tannish Brown & Dark Brown I Silty Clay
Moisture
%
Maximum
Density
(pet)
94.0
Project Requirements
Moisture Density
Optimum +4 95 min
24.0
FIELD DENSITY TESTS
Test Probe MID Moisture Wet Density Dry Density Density
No Test Location Depth No. % (pet) (pet) (%max)
Paving subgrade
50' south, 100' east from northwest corner of 6" 277811 28.0 119.4 93.3 99
paving
Paving subgrade
2 120' south, 50' east from northwest corner of 6" 277811 27.8 118.6 92.8 99
paving
Paving subgrade
3 200' south, 75' east from northwest corner of 6" 277811 27.3 119.3 93.7 100
paving
Paving subgrade
4 200' south, 150' east from northwest corner of 6" 277811 27.7 118.5 92.8 99
paving
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(JB/JB) Page 1 of 2
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Reinforcing Steel Inspection
Report No.: 292052
Project No.: 0712786
Date of Service: 07/12/2007
Report Date: 07/25/2007
Project: Gateway Business Center
Coppell, Texas
Services: Reinforcing Steel Inspection
Report of Inspection
Locations and Items Inspected:
East parking lot, north side of south fire lane, east side of building
~em s Ins peeled: Conform ing Non ~em s Inspected: Co nfo rm ing Non nem s Ins peeled: Co nform ing Non
Canto rm ing Co nfo rm ing Conforming
p lacing Drawings Bar Length Co lum n Ties Properly
Approved x and Shape x Tied and Spaced NA
Bar Size x Pro per B ar P lacem enl x Stirrup Spacing NA
Bar Grade x Properly Tied x Stirrup Type NA
Bars Clean x Dowel Bars in Place x Lapped Splices x
Form Clean x Proper B ar Suppo rls x Corner 8 ars NA
N umber of Bars x P fa per C o'v'er x Mechanical Splices NA
Discrepancies / Comments: 1. Dowel bars not in place. 2. Missing chairs at all placement. 3. Need to correct
lap splices at several locations.
Items 1 and 3 were corrected prior to concrete placement.
Item 2 required re-inspection.
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/JB) Page 1 of 2