Duke Lesley-LR070702 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 290014 Project No.: 0612510 Date of Service: 06/13/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing PROJECT DATA Contractor: Test Method: ASTM D-2922 ASTM D-3017 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: DT Standard Counts Moisture Density Current: 742 Current: 2514 Previous: 741 Previous: 2511 MOISTURE DENSITY RELATIONS Maximum Moisture Density Project Requirements MID No. Description % (pet) Moisture Density 272998 Brown I Silty Clay wI Organics 22.5 96.5 Optimum +4 95 min FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (%max) Utility back fill Waterline ww-3, Station 13+00, 4' below grade 6" 272998 25.1 118.8 95.0 98 Utility back fill 2 Waterline ww-3, Station 13+00, 2' below grade 6" 272998 25.0 118.4 94.7 98 Utility back fill 3 Waterline ww-3, Station 13+00, final 6" 272998 24.3 118.2 95.1 99 Utility back fill 4 Waterline ww-3, Station 15+00, 4' below grade 6" 272998 25.7 120.3 95.7 99 Utility back fill 5 Waterline ww-3, Station 15+00, 2' below grade 6" 272998 25.8 116.2 92.4 96 Utility back fill 6 Waterline ww-3, Station 15+00, final 6" 272998 23.4 117.8 95.5 99 Utility back fill 7 Gas/Electric, Station 48+50, final 6" 272998 22.6 117.7 96.0 100 Utility back fill 8 Gas/Electric, Station 43+50, final 6" 272998 23.0 117.0 95.1 99 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 1 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Re-Testing Report No.: 290240 Project No.: 0612510 Date of Service: 06/14/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Test in accordance with ASTM Standards. PROJECT DATA Contractor: Test Method: ASTM 0-2922 ASTM 0-3017 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: DT Standard Counts Moisture Density Current: 744 Current: 2506 Previous: 741 Previous: 2511 MOISTURE DENSITY RELATIONS MID No. 272998 Description Brown I Silty Clay wI Organics Moisture % Maximum Density (pet) 96.5 Project Requirements Moisture Density Optimum +4 95 min 22.5 FIELD DENSITY TESTS 3 Probe MID Moisture Wet Density Dry Density Density Test Location Depth No. % (pet) (pet) (%max) Utility back fill Retest #1 from report #290164 6" 272998 24.9 114.5 91.7 95 Utility back fill Retest #2 from report #290164 6" 272998 25.2 121.1 96.7 100 Utility back fill Retest #3 from report #290164 6" 272998 22.5 115.3 94.1 98 Utility back fill Retest #4 from report #290164 6" 272998 24.2 115.1 92.7 96 Utility back fill Retest #5 from report #290164 6" 272998 24.9 114.4 91.6 95 Test No 2 4 5 Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Alex Bennett PE (1-ec copy) Rone Engineering See Report 290239 fo, ledmk;ao time P-~ ~ K. Scott Watson, AET Project Manager Technician: Joe Jernigan LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 1 of 1 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 290239 Project No.: 0612510 Date of Service: 06/14/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing FIELD DENSITY TESTS Probe Depth MID No. Moisture Wet Density Dry Density Density % (pct) (pct) (% max) Test No Test Location 9 Utility back fill Waterline ww-5, Station 21 +00, 2' below grade Utility back fill Waterline ww-5, Station 21 +00, final 6" 272998 24.2 116.4 93.7 97 10 6" 272998 24.8 115.3 92.4 96 Technician: Joe Jernigan Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Alex Bennett PE (1-ec copy) Started: 12:00pm Finished: 04:30pm Rone Engineering ,~~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 2 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 290239 Project No.: 0612510 Date of Service: 06/14/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing PROJECT DATA Contractor: Test Method: ASTM 0-2922 ASTM 0-3017 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: DT Standard Counts Moisture Density Current: 744 Current: 2506 Previous: 741 Previous: 2511 MOISTURE DENSITY RELATIONS Maximum Moisture Density Project Requirements MID No. Description % (pet) Moisture Density 272998 Brown I Silty Clay wI Organics 22.5 96.5 Optimum +4 95 min FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (% maxI Utility back fill Waterline ww-5, Station 10+00, 2' below grade 6" 272998 25.3 114.8 91.6 95 Utility back fill 2 Waterline ww-5, Station 10+00, final 6" 272998 25.2 115.4 92.2 96 Utility back fill 3 Waterline ww-5, Station 12+00, 2' below grade 6" 272998 26.0 115.2 91.4 95 Utility back fill 4 Waterline ww-5, Station 12+00, final 6" 272998 24.8 115.2 92.3 96 Utility back fill 5 Waterline ww-5, Station 15+00, 2' below grade 6" 272998 24.1 114.8 92.5 96 Utility back fill 6 Waterline ww-5, Station 15+00, final 6" 272998 24.7 115.2 92.4 96 Utility back fill 7 Waterline ww-5, Station 18+00, 2' below grade 6" 272998 22.8 115.7 94.2 98 Utility back fill 8 Waterline ww-5, Station 18+00, final 6" 272998 25.5 115.8 92.3 96 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 1 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 290164 Project No.: 0612510 Date of Service: 06/14/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing Test No Test Location FIELD DENSITY TESTS Probe MID Depth No. Moisture Wet Density Dry Density Density % (pet) (pet) (% max) 20 Utility back fill Sanitary sewer line SS-5, Station 6+00, 2' 6" 272998 24.9 116.8 below grade Utility back fill Sanitary sewer line SS-5, Station 6+00, final 6" 272998 23.0 116.5 An asterisk (*) appears next to results which do NOT meet the project specifications. 93.5 97 21 94.7 98 Technician: Joe Jernigan Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Alex Bennett PE (1-ec copy) Started: 07:15am Finished: 11 :15am Rone Engineering p~~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 3 of 3 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 290164 Project No.: 0612510 Date of Service: 06/14/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (%max) Utility back fill 9 Waterline WW-5, Station 8+00, final 6" 272998 22.9 116.4 94.7 98 Utility back fill 10 Sanitary sewer line SS-5, Station 6+50, 4' 6" 272998 23.0 117.5 95.5 99 below grade Utility back fill 11 Sanitary sewer line SS-5, Station 6+50, 2' 6" 272998 23.1 117.1 95.1 99 below grade Utility back fill 12 Sanitary sewer line SS-5, Station 6+50, final 6" 272998 23.7 116.8 94.4 98 Utility back fill 13 Sanitary sewer line SS-5, Station 2+50, 4' 6" 272998 23.7 116.3 94.0 97 below grade Utility back fill 14 Sanitary sewer line SS-5, Station 2+50, 2' 6" 272998 23.9 116.6 94.1 98 below grade Utility back fill 15 Sanitary sewer line SS-5, Station 2+50, final 6" 272998 24.9 116.8 93.5 97 Utility back fill 16 Sanitary sewer line SS-5, Station 4+50, 4' 6" 272998 24.2 117.1 94.3 98 below grade Utility back fill 17 Sanitary sewer line SS-5, Station 4+50, 2' 6" 272998 24.1 117.0 94.3 98 below grade Utility back fill 18 Sanitary sewer line SS-5, Station 4+50, final 6" 272998 23.9 117.0 94.4 98 Utility back fill 19 Sanitary sewer line SS-5, Station 6+00, 4' 6" 272998 23.3 117.3 95.1 99 below grade LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 2 of 3 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Project: Lesley Infrastructure Services: Perform In-Place Density Testing 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of In-Place Density Testing Report No.: 290164 Project No.: 0612510 Date of Service: 06/14/2007 Report Date: 07/02/2007 PROJECT DATA Contractor: Test Method: ASTM 0-2922 ASTM 0-3017 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: DT Standard Counts Moisture Density Current: 744 Current: 2506 Previous: 7 41 Previous: 2511 MOISTURE DENSITY RELATIONS MID No. 272998 Description Brown I Silty Clay wI Organics Moisture % 22.5 FIELD DENSITY TESTS Maximum Density (pet) 96.5 Project Requirements Moisture Density Optimum +4 95 min Test No Test Location Probe Depth MID No. Moisture Wet Density Dry Density Density % (pet) (pef) (% maxI 19.8* 119.8 100.0 104 2 Utility back fill Waterline WW-5, Station 4+00, 4' below grade Utility back fill Waterline WW-5, Station 4+00,2' below grade Utility back fill Waterline WW-5, Station 4+00, final Utility back fill Waterline WW-5, Station 6+00, 4' below grade Utility back fill Waterline WVV-5, Station 6+00,2' below grade Utility back fill Waterline WW-5, Station 6+00, final Utility back fill Waterline WW-5, Station 8+00, 4' below grade Utility back fill Waterline WW-5, Station 8+00,2' below grade 6" 272998 21.4 * 119.8 98.7 102 3 4 5 6 7 8 6" 272998 20.7* 119.9 99.3 103 6" 272998 22.2* 121.8 99.7 103 6" 272998 29.7* 117.1 90.3 94* 6" 272998 22.6 116.6 95.1 99 6" 272998 24.1 116.4 93.8 97 6" 272998 23.7 116.3 94.0 97 6" 272998 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 1 of 3 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 290092 Project No.: 0612510 Date of Service: 06/13/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pct) (pet) (% max) Utility back fill 7 Sanitary 5ewer line 55-5, Station 6+00, 8' below 6" 272998 23.7 116.8 94.4 98 grade Utility back fill 8 Sanitary 5ewer line 55-5, Station 6+00, 6' below 6" 272998 23.7 116.3 94.0 97 grade Technician: Joe Jernigan Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Alex Bennett PE (1-ec copy) Started: 10:45am Finished: 05:30pm Rone Engineering P-&~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (SSILB) Page 2 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 290092 Project No.: 0612510 Date of Service: 06/13/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing PROJECT DATA Contractor: Test Method: ASTM 0-2922 ASTM 0-3017 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: DT Standard Counts Moisture Density Current: 742 Current: 2514 Previous: 741 Previous: 2511 MOISTURE DENSITY RELATIONS MID No. 272998 Description Brown I Silty Clay wI Organics Moisture % Maximum Density (pet) 96.5 Project Requirements Moisture Density Optimum +4 95 min 22.5 FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (%max) Utility back fill Sanitary sewer line ss-5, Station 0+50, 8' below 6" 272998 22.6 116.6 95.1 99 grade Utility back fill 2 Sanitary sewer line ss-5, Station 0+50, 6' below 6" 272998 24.1 116.4 93.8 97 grade Utility back fill 3 Sanitary sewer line ss-5, Station 2+50, 8' below 6" 272998 23.7 116.3 94.0 97 grade Utility back fill 4 Sanitary sewer line 55-5, Station 2+50, 6' below 6" 272998 22.9 116.4 94.7 98 grade Utility back fill 5 Sanitary sewer line ss-5, Station 4+50, 8' below 6" 272998 23.0 117.5 95.5 99 grade Utility back fill 6 Sanitary sewer line ss-5, Station 4+50, 6' below 6" 272998 23.1 117.1 95.1 99 grade LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar SUbject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (SS/LB) Page 1 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 290014 Project No.: 0612510 Date of Service: 06/13/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (%max) Utility back fill 9 Waterline ww-5, Station 2+00, 4' below grade 6" 272998 25.1 118.8 95.0 98 Utility back fill 10 Waterline ww-5, Station 2+00, 2' below grade 6" 272998 25.0 118.4 94.7 98 Utility back fill 11 Waterline ww-5, Station 2+00, final 6" 272998 24.3 118.2 95.1 99 Technician: Joe Jernigan Report Distribution: Orig: Duke Construction, LP (Dallas, TX) AUn: Mr. Alex Bennett PE (1-ec copy) Started: 08:30am Finished: 1 0:45am Rone Engineering p~~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd. (LB/LB) Page 2 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, 5te 600, Houston, TX 77040 4421 Freidrieh, 5te 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 289724 Project No.: 0612510 Date of Service: 06/11/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing PROJECT DATA Contractor: Test Method: ASTM D-2922 ASTM D-3017 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: DT Standard Counts Moisture Density Current: 741 Current: 2611 Previous: 745 Previous: 2629 MOISTURE DENSITY RELATIONS MID No. 272998 Description Brown I Silty Clay wI Organics Moisture % Maximum Density (pet) 96.5 Project Requirements Moisture Density Optimum +4 95 min 22.5 FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (%max) Utility back fill Storm drain, Line A, Station 13+00, final 6" 272998 24.8 114.9 92.1 95 Utility back fill 2 Storm drain, Line C, Station 8+50, 2' below 6" 272998 24.1 116.4 93.8 97 grade Utility back fill 3 Storm drain, Line C, Station 8+50, final 6" 272998 22.6 116.1 94.7 98 Utility back fill 4 Storm drain, Lateral A-1, Station 0+30, final 6" 272998 25.8 116.2 92.4 96 Utility back fill 5 12" Sanitary sewer line 55-3, Station 0+50, 8' 6" 272998 23.1 116.3 94.5 98 below grade Utility back fill 6 12" Sanitary sewer line 55-3, Station 0+50, 6' 6" 272998 24.5 116.8 93.8 97 below grade Utility back fill 7 12" Sanitary sewer line 55-3, Station 0+50, 4' 6" 272998 24.7 116.0 93.0 96 below grade LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LBfLB) Page 1 of 4 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 289724 Project No.: 0612510 Date of Service: 06/11/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pef) (pet) (% max) Utility back fill 8 12" Sanitary sewer line 55-3, Station 0+50, 2' 6" 272998 24.2 115.9 93.3 97 below grade Utility back fill 9 12" Sanitary sewer line 55-3, Station 0+50, final 6" 272998 23.8 116.7 94.3 98 Utility back fill 10 12' Sanitary sewer line 55-3, Station 3+50, 8' 6" 272998 25.8 117.2 93.2 97 below grade Utility back fill 11 12" Sanitary sewer line ss-3, Station 3+50, 6' 6" 272998 23.1 116.8 94.9 98 below grade Utility back fill 12 12" Sanitary sewer line ss-3, Station 3+50, 4' 6" 272998 23.4 117.7 95.4 99 below grade Utility back fill 13 12" Sanitary sewer line ss-3, Station 3+50, 2' 6" 272998 23.8 116.0 93.7 97 below grade Utility back fill 14 12" Sanitary sewer line ss-3, Station 3+50, final 6" 272998 24.3 116.3 93.6 97 Utility back fill 15 12" Sanitary sewer line 55-3, Station 6+50,8' 6" 272998 24.5 115.9 93.1 97 below grade Utility back fill 16 12" Sanitary sewer line ss-3, Station 6+50, 6' 6" 272998 23.8 116.0 93.7 97 below grade Utility back fill 17 12" Sanitary sewer line ss-3, Station 6+50, 4' 6" 272998 23.6 120.8 97.7 101 below grade Utility back fill 18 12" Sanitary sewer line ss-3, Station 6+50, 2' 6" 272998 24.5 119.9 96.3 100 below grade LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, LId (LB/LB) Page 2 of 4 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 289724 Project No.: 0612510 Date of Service: 06/11/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (%max) Utility back fill 19 12" Sanitary sewer line 55-3, Station 6+50, final 6" 272998 24.1 119.1 96.0 100 Utility back fill 20 12" Waterline w-2, Station 10+00,2' below 6" 272998 23.5 119.9 97.1 101 grade Utility back fill 21 12" Waterline w-2, Station 10+00, final 6" 272998 24.6 119.4 95.8 99 Utility back fill 22 12" Waterline w-2, Station 13+00, 2' below 6" 272998 24.3 117.5 94.5 98 grade Utility back fill 23 12" Waterline w-2, Station 13+00, final 6" 272998 24.4 117.3 94.3 98 Utility back fill 24 12" Waterline w-4, Station 0+50, 3' below grade 6" 272998 24.0 116.9 94.3 98 Utility back fill 25 12" Waterline w-4, Station 0+50, l' below grade 6" 272998 24.2 117.1 94.3 98 Utility back fill 26 12" Waterline w-4, Station 0+50, final 6" 272998 24.8 116.9 93.7 97 Utility back fill 27 12" Waterline w-4, Station 3+50, 3' below grade 6" 272998 23.4 117.8 95.5 99 Utility back fill 28 12" Waterline w-4, Station 3+50, l' below grade 6" 272998 24.1 117.3 94.5 98 Utility back fill 29 12" Waterline w-4, Station 3+50, final 6" 272998 23.6 116.9 94.6 98 Utility back fill 30 12" Waterlone w-4, Station 6+50, 3' below 6" 272998 24.7 116.8 93.7 97 grade Utility back fill 31 12" Waterline w-4, Station 6+50, l' below grade 6" 272998 24.5 116.2 93.3 97 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 3 of 4 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 289724 Project No.: 0612510 Date of Service: 06/11/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (%max) Utility back fill 32 12" Waterline w-4, Station 6+50, final 6" 272998 22.8 116.9 95.2 99 Utility back fill 33 12" Waterline w-4, Station 9+50,3' below grade 6" 272998 24.1 117.5 94.7 98 Utility back fill 34 12" Waterline w-4, Station 9+50, l' below grade 6" 272998 22.7 117.4 95.7 99 Utility back fill 35 12" Waterline w-4, Station 9+50, final 6" 272998 24.2 117.1 94.3 98 Technician: Joe Jernigan Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Alex Bennett PE (1-ec copy) Started: 12:15pm Finished: 03:15pm Rone Engineering p~~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LBfLB) Page 4 of 4 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 289854 Project No.: 0612510 Date of Service: 06/12/2007 Report Date: 07/02/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing PROJECT DATA Contractor: Test Method: ASTM 0-2922 ASTM 0-3017 Gauge: Troxler 3430 Gauge Serial No: 35318 Test Mode: DT Standard Counts Moisture Density Current: 738 Current: 2507 Previous: 7 41 Previous: 2511 MOISTURE DENSITY RELATIONS MID No. 272998 Description Brown I Silty Clay wI Organics Moisture % Maximum Density (pet) 96.5 Project Requirements Moisture Density Optimum +4 95 min 22.5 Test No Test Location FIELD DENSITY TESTS Probe MID Depth No. Moisture Wet Density Dry Density Density % (pcf) (pet) (% max) Utility back fill Waterline ww-3, Station 9+15, 2' below grade 6" 272998 24.7 119.0 95.4 99 Utility back fill 2 Waterline ww-3, Station 9+15, final 6" 272998 24.7 119.0 95.4 99 Utility back fill 3 Waterline ww-3, Station 11 +00, 2' below grade 6" 272998 23.1 119.3 96.9 100 Utility back fill 4 Waterline ww-3, Station 11 +00, final 6" 272998 23.0 116.7 94.9 98 Technician: Joe Jernigan Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Alex Bennett PE (1-ec copy) Started: 10:00am Finished: 05:30pm Rone Engineering p~~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (SS/LB) Page 1 of 1