Duke Lesley-LR070519 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 283734 Project No.: 0612510 Date of Service: 04/04/2007 Report Date: 05/19/2007 Project: Lesley Infrastructure Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sample~ back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Concrete Supplier: LMC Plant: 7 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 3" - 5" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Batch time: 03:06pm Concrete: 710F Ticket No: 7177218 Unit Weight (pct): NA Measured Slump (inches) 3.5 Mix Design I.D.: 1701 Placement Date: 04/04/2007 Weather Conditions: Clear Time Sampled: 03:35pm Temperature - Air: 670F Truck No: 959 Air Content: 4.7% Overall Placement Location: Manhole, 5' south from telephone pole in southeast corner of 1421 building (Power Wa\ Technologies) Sample Location: Same as above REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cyli nder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type - - 1 1 04/11/2007 7 6.00 28.27 145,940 5,160 Unbonded Cap 1 2 05/02/2007 28 6.00 28.27 180,290 6,380 Un bonded Cap 1 3 05/02/2007 28 6.00 28.27 178,470 6,310 Unbonded Cap Average 6,340 1 4 05/30/2007 56 6.00 28.27 198,250 7,010 Unbonded Cap Technician: Ryan Rawlinson Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Alex Bennett PE (1-ec copy) Started: 02:30pm Finished: 04:30pm Rone Engineering P-~~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW/KW) Page 1 of 1 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 283670 Project No.: 0612510 Date of Service: 04/04/2007 Report Date: 05/19/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing PROJECT DATA Contractor: Test Method: ASTM 0-2922 ASTM 0-3017 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: DT Standard Counts Moisture Density Current: 740 Current: 2629 Previous: 744 Previous: 2633 MOISTURE DENSITY RELATIONS Maximum Moisture Density Project Requirements MID No. Description % (pet) Moisture Density 272998 Brown I Silty Clay wi Organics 22.5 96.5 Optimum +4 95 min FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pef) (pet} (%max) Utility backfill 12" sanitary sewer, Line S-2 station 16+00, 9' 6" 272998 24.7 117.5 94.2 98 below grade Utility backfill 2 12" sanitary sewer, Line S-2 station 16+00, 8' 6" 272998 22.9 117.2 95.4 99 below grade Utility backfill 3 12" sanitary sewer, Line 5-2 station 16+00, 7' 6" 272998 24.0 116.3 93.8 97 below grade Utility backfill 4 12" sanitary sewer, Line S-2 station 16+00,6' 6" 272998 24.1 116.5 93.9 97 below grade Utility backfill 5 12" sanitary sewer, Line S-2 station 16+00, 5' 6" 272998 23.2 115.6 93.8 97 below grade Utility backfill 6 12" sanitary sewer, Line S-2 station 16+00,4' 6" 272998 25.2 115.9 92.6 96 below grade LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KWfKW) Page 1 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 283670 Project No.: 0612510 Date of Service: 04/04/2007 Report Date: 05/19/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (%max) Utility backfill 7 12" sanitary sewer, Line 8-2 station 16+00, 3' 6" 272998 26.3 117.7 93.2 97 below grade Utility backfill 8 12" sanitary sewer, Line 8-2 station 16+00,2' 6" 272998 24.9 116.9 93.6 97 below grade Utility backfill 9 12" sanitary sewer, Line 8-2 station 16+00, l' 6" 272998 23.7 117.3 94.8 98 below grade Utility backfill 10 12" sanitary sewer, Line 8-2 station 16+00, 6" 272998 23.2 116.9 94.9 98 final Technician: Joe Jernigan Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Alex Bennett PE (1-ec copy) Started: 07:15am Finished: 10:15am Rone Engineering P-~~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar SUbject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW/KW) Page 2 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testin~ Report No.: 283556 Project No.: 0612510 Date of Service: 04/03/2007 Report Date: 05/19/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing PROJECT DATA Contractor: Test Method: ASTM 0-2922 ASTM 0-3017 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: DT Standard Counts Moisture Density Current: 742 Current: 2633 Previous: 744 Previous: 2631 MOISTURE DENSITY RELATIONS Maximum Moisture Density Project Requirements MID No. Description % (pet) Moisture Density 272998 Brown I Silty Clay wI Organics 22.5 96.5 Optimum +4 95 min FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (%max) Utility backfill 12" sanitary sewer, Station 14+00, 9' below 6" 272998 24.8 114.9 92.1 95 grade Utility backfill 2 12" sanitary sewer, Station 14+00, 8' below 6" 272998 24.1 116.4 93.8 97 grade Utility backfi II 3 12" sanitary sewer, Station 14+00, 7' below 6" 272998 22.6 116.1 94.7 98 grade Utility backfill 4 12" sanitary sewer, Station 14+00,6' below 6" 272998 25.8 116.2 92.4 96 grade Utility backfill 5 12" sanitary sewer, Station 14+00, 5' below 6" 272998 23.1 116.3 94.5 98 grade Utility backfill 6 12" sanitary sewer, Station 14+00, 4' below 6" 272998 24.5 116.8 93.8 97 grade LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/KW) Page 1 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 283556 Project No.: 0612510 Date of Service: 04/03/2007 Report Date: 05/19/2007 Project: Lesley Infrastructure Services: Perform In-Place Density Testing FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pcf) (pet) (% max) Utility backfill 7 12" sanitary sewer, Station 14+00, 3' below 6" 272998 24.7 116.0 93.0 96 grade Utility backfill 8 12" sanitary sewer, Station 14+00, 2' below 6" 272998 24.2 115.9 93.3 97 grade Utility backfill 9 12" sanitary sewer, Station 14+00, l' below 6" 272998 24.5 115.9 93.1 97 grade Utility backfill 10 12" sanitary sewer, Station 14+00, final 6" 272998 23.8 116.0 93.7 97 Utility backfill 11 Storm drain, line E, Station 9+00, 4' below 6" 272998 23.8 116.0 93.7 97 grade Utility backfill 12 Storm drain, line E, Station 9+00, 3' below 6" 272998 24.3 116.3 93.6 97 grade Utility backfill 13 Storm drain, line E, Station 9+00, 2' below 6" 272998 24.2 116.4 93.7 97 grade Utility backfill 14 Storm drain, line E, Station 9+00, l' below 6" 272998 24.8 115.3 92.4 96 grade Utility backfill 15 Storm drain, line E, Station 9+00, final 6" 272998 25.3 114.8 91.6 95 Technician: Joe Jernigan Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Alex Bennett PE (1-ec copy) Started: 09:00am Finished: 11 :30am Rone Engineering ,~~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TMIKW) Page 2 of 2