Gateway BP(3.1)-LR070805
Rone Engineering
.
Client: Transwestem Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Tes1
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sample~
back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (Ufo): 4% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 23601524
Placement Date: 07/20/2007
Weather Conditions: Cloudy
Time Sampled: 02:30am
Temperature - Air: 770F
Truck No: 1182
Air Content: 5.5%
Overall Placement Location:
Paving for car parking on Northeast Building 1, northwest of building 2
Measured
Slump
(inches)
6.0
Batch time: 01 :39am
Concrete: 860F
Ticket No: 13691747
Unit Weight (pet): NA
Sample Location:
Building 1: gridline A-12, 240' east
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
-
1 1 07/27/2007 7 6.00 28.27 80,410 2,840 Unbonded Cap
1 2 08/03/2007 14 6.00 28.27 93,890 3,320 Unbonded Cap
1 3 08/17/2007 28
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 1 of 13
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Concrete Compressive Strength Test
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples
back to the laboratory for curing and testing in accordance with applicable standards.
REPORT OF TESTS
Cylinder
Marked
Set No.
- -
1 4
Date
Tested
08/17/2007
Age
(days)
28
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
Diameter
(in)
Area
(in')
Compressive
Strength
(psi)
Fracture
Type
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LBfLB) Page 2 of 13
Rone Engineering
......
Client: Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Tes1
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sampleE
back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 4% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 23601524
Placement Date: 07/20/2007
Weather Conditions: Cloudy
Time Sampled: 03:04am
Temperature - Air: 780F
Truck No: 1184
Air Content: 2.5%
Overall Placement Location:
Paving for car parking on Northeast Building 1, northwest of building 2
Measured
Slump
(inches)
5.0
Batch time: 01 :56am
Concrete: 850F
Ticket No: 13691751
Unit Weight (pet): NA
Sample Location:
Building 1: gridlineA-17, 170 east
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
2 1 07/27/2007 7 6.00 28.27 87,970 3,110 Unbonded Cap
2 2 08/03/2007 14 6.00 28.27 102,250 3,620 Unbonded Cap
2 3 08/17/2007 28
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 3 of 13
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
n01 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestem Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Concrete Compressive Strength Tes1
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples
back to the laboratory for curing and testing in accordance with applicable standards.
REPORT OF TESTS
Cylinder
Marked
Set No.
- -
2 4
Date
Tested
08/17/2007
Age
(days)
28
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
Diameter
(in)
Area
(in')
Compressive
Strength
(psi)
Fracture
Type
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 4 of 13
Rone Engineering
.
Client: Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Tes1
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sample~
back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 136
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 4% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 23601524
Placement Date: 07/20/2007
Weather Conditions: Cloudy
Time Sampled: 04:32am
Temperature - Air: 790F
Truck No: 1039
Air Content: 2.8%
Overall Placement Location:
Paving for car parking on Northeast Building 1, northwest of building 2
Measured
Slump
(inches)
5.0
Batch time: 03:51am
Concrete: 840F
Ticket No: 13691771
Unit Weight (pet): NA
Sample Location:
Building 1: gridline A-16, 170' east
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
3 1 07/27/2007 7 6.00 28.27 79,460 2,810 Unbonded Cap
3 2 08/03/2007 14 6.00 28.27 95,120 3,360 Unbonded Cap
3 3 08/17/2007 28
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, ltd.
(lB/lB) Page 5 of 13
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
n01 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Concrete Compressive Strength Tes1
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sampleE
back to the laboratory for curing and testing in accordance with applicable standards.
REPORT OF TESTS
Cylinder
Marked
Set No.
- -
3 4
Date
Tested
08/17/2007
Age
(days)
28
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
Diameter
(in)
Area
(in')
Compressive
Strength
(psi)
Fracture
Type
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 6 of 13
Rone Engineering
.
Client:
Transwestem Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Tes1
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sample~
back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 4% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 23601524
Placement Date: 07/20/2007
Weather Conditions: Cloudy
Time Sampled: 06:34am
Temperature - Air: 780F
Truck No: 1192
Air Content: 4.8%
Overall Placement Location:
Paving for car parking on Northeast Building 1, northwest of building 2
Measured
Slump
(inches)
4.5
Batch time: 05: 19am
Concrete: 830F
Ticket No: 13691800
Unit Weight (pet): NA
Sample Location:
Parking spaces at building 2: gridline A-17, 120' Ex 60'N
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
4 1 07/27/2007 7 6.00 28.27 89,230 3,160 Unbanded Cap
4 2 08/03/2007 14 6.00 28.27 93,900 3,320 Unbonded Cap
4 3 08/17/2007 28
LIMITATIONS: The test results presented herein were prepared based upon the specifIC samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be repnoduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 7 of 13
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestem Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Concrete Compressive Strength Tes1
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sample~
back to the laboratory for curing and testing in accordance with applicable standards.
REPORT OF TESTS
Cylinder
Marked
Set No.
- -
4 4
Date
Tested
08/17/2007
Age
(days)
28
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
Compressive
Strength
(psi)
Fracture
Type
Diameter
(in)
Area
(in')
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LBfLB) Page 8 of 13
Rone Engineering
.
Client: Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich. Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Tes1
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sample~
back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 4% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 07/20/2007
Weather Conditions: Partly cloudy
Time Sampled: 07:40am Batch time: 07:09am
Temperature - Air: 800F Concrete: 910F
Truck No: 1032 Ticket No: 13691825
Air Content: 2.5% Unit Weight (pet): NA
Overall Placement Location:
Paving for car parking on Northeast Building 1, northwest of building 2
Measured
Slump
(inches)
5.25
Sample Location:
Building 2: grid line A-13.5, 120' east
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
-
5 1 07/27/2007 7 6.00 28.27 67,930 2,400 Unbonded Cap
5 2 08/03/2007 14 6.00 28.27 93,950 3,320 Unbonded Cap
5 3 08/17/2007 28
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LBfLB) Page 9 of 13
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
T ranswestem Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Concrete Compressive Strength Tes1
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sample~
back to the laboratory for curing and testing in accordance with applicable standards.
REPORT OF TESTS
Cyli nder
Marked
Set No.
- -
5 4
Date
Tested
08/17/2007
Age
(days)
28
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
Diameter
(in)
Area
(in')
Compressive
Strength
(psi)
Fracture
Type
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 10 of 13
Rone Engineering
....
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Tes1
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sample~
back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 4% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 23601524
Placement Date: 07/20/2007
Weather Conditions: Cloudy
Time Sampled: 09:14am
Temperature - Air: 870F
Truck No: 1032
Air Content: 3.8%
Overall Placement Location:
Paving for car parking on Northeast Building 1, northwest of building 2
Measured
Slump
(inches)
5.25
Batch time: 08:44am
Concrete: 900F
Ticket No: 13691845
Unit Weight (pet): NA
Sample Location:
Building 2: gridline A-11.5, 100' east
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
-
6 1 07/27/2007 7 6.00 28.27 89,620 3,170 Unbonded Cap
6 2 08/03/2007 14 6.00 28.27 107,710 3,810 Unbonded Cap
6 3 08/17/2007 28
LIMITATIONS: The test results presented herein were prepared based upon the specifiC samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 11 of 13
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestem Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Concrete Compressive Strength Tes1
Report No.: 292853
Project No.: 0712786
Date of Service: 07/20/2007
Report Date: 08/05/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sample~
back to the laboratory for curing and testing in accordance with applicable standards.
REPORT OF TESTS
Cylinder
Marked
Set No.
- -
6 4
Date
Tested
08/17/2007
Age
(days)
28
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
Diameter
(in)
Area
(in')
Compressive
Strength
(psi)
Fracture
Type
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specifiC samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 12 of 13