Gateway BP(3.1)-LR070822 Rone Engineering . Client: Transwestern Commercial Services 5001 Spring Valley Dallas, TX 75244 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Tes1 Report No.: 293118 Project No.: 0712786 Date of Service: 07/23/2007 Report Date: 08/22/2007 Project: Gateway Business Center Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring sample~ back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Constructors & Associates Concrete Supplier: Redi Mix Plant: 136 Specification Requirements Strength: 3,000 psi @ 28 days Slump (in.): 7" maximum Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Batch time: 12:27pm Concrete: 860F Ticket No: 13691988 Unit Weight (pet): NA Measured Slump (inches) 4.5 Mix Design 1.0.: 34550 Placement Date: 07/23/2007 Weather Conditions: Cloudy Time Sampled: 01 :30pm Temperature - Air: 870F Truck No: 1193 Air Content: 1.2% Overall Placement Location: Building 1 poured all 4 corners grade beam, building 2 poured northeast building corner grade beam Sample Location: Building 1 at southwest corner, grade beam REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type - 1 1 07/30/2007 7 6.00 28.27 86,170 3,050 Unbonded Cap 1 2 08/20/2007 28 6.00 28.27 116,830 4,130 Unbonded Cap 1 3 08/20/2007 28 6.00 28.27 119,180 4,220 Unbonded Cap Average 4,170 1 4 09/17/2007 56 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/KW) Page 1 of 2