Loading...
Duke Lesley-LR070824 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Rone Engineering . Report of Concrete Compressive Strength Test Report No.: 295538 Project No.: 0612510 Date of Service: 08/14/2007 Report Date: 08/24/2007 Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Client: Project: Lesley Infrastructure Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Measured Slump (inches) 4.75 Mix Design I.D.: 1701 Placement Date: 08/14/2007 Weather Conditions: Clear Time Sampled: 02:45pm Temperature - Air: 1030F Truck No: 3033 Air Content: NA Overall Placement Location: Structural concrete poured for wall Station 0+44.89, line B, type A, TXDOT headwall Contractor: Concrete Supplier: LMC Plant: 6 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 6" maximum Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Batch time: 01 :49pm Concrete: 790F Ticket No: 6310044 Unit Weight (pcf): NA Sample Location: See above REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 92,300 Compressive Strength (psi) 3,260 Cylinder Marked Set No. - - 1 1 Fracture Type Unbonded Cap Area (in2) 28.27 Diameter (in) 6.00 Date Tested 08/21/2007 Age (days) 7 28 28 09/11/2007 09/11/2007 2 3 56 10/09/2007 4 Started: 01 :15pm Finished: 03:30pm Rone Engineering ~~..~ Technician: Ryan Rawlinson Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Alex Bennett PE (1-ec copy) 1-cc City of Coppell Attn: Mr. Lee Stone 1-cc City of Coppell Attn: Mr. Larry Davis K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd. (CHILB) Page 1 of 1 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 296073 Project No.: 0612510 Date of Service: 08/18/2007 Report Date: 08/24/2007 Project: Lesley Infrastructure Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Concrete Supplier: Lacy Plant: On site Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 6" maximum Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design I.D.: 5194 Placement Date: 08/18/2007 Weather Conditions: Cloudy Time Sampled: 07:20am Temperature - Air: 7JDF Truck No: NA Air Content: 5.7% Overall Placement Location: Paving, eastbound and westbound Dividend St., Station 34+70 to 34+00, below) Measured Slump (inches) 5.75 Batch time: 07:15am Concrete: 710F Ticket No: NA Unit Weight (pcf): NA (cont. Sample Location: Dividend, eastbound lane, Station 34+20 REPORT OF TESTS Cylinder Marked Date Set No. Tested 1 1 08/21/2007 1 2 08/25/2007 3 09/15/2007 4 10/13/2007 Age (days) 3 Diameter (in) 6.00 7 28 56 Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 79,770 Compressive Strength (psi) 2,820 Fracture Type Unbonded Cap Area (in') 28.27 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LBfLB) Page 1 of 6 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Concrete Compressive Strength Test Report No.: 296073 Project No.: 0612510 Date of Service: 08/18/2007 Report Date: 08/24/2007 Project: Lesley Infrastructure Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Remarks: Cont: eastbound turn lane, Station 22+50 to 19+85, 25+75 to 28+25, 32+25 to 34+00, 35+75 to 37+28, 39+00 to 4+05 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 2 of 6 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 296073 Project No.: 0612510 Date of Service: 08/18/2007 Report Date: 08/24/2007 Project: Lesley Infrastructure Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Concrete Supplier: Lacy Plant: On site Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 6" maximum Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design I.D.: 5194 Placement Date: 08/18/2007 Weather Conditions: Clear Time Sampled: 08:45am Temperature - Air: 790F Truck No: NA Air Content: 4.6% Overall Placement Location: Paving, eastbound and westbound Dividend St., Station 34+70 to 34+00, below) Measured Slump (inches) 2.75 Batch time: 08:40am Concrete: 760F Ticket No: NA Unit Weight (pct): NA (cont. Sample Location: Station 23+00 REPORT OF TESTS Cylinder Marked Date Set No. Tested 2 1 08/21/2007 2 2 08/25/2007 2 3 09/15/2007 2 4 10/13/2007 Age (days) 3 Diameter (in) 6.00 7 28 56 Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 88,290 Compressive Strength (psi) 3,120 Fracture Type Unbonded Cap Area (in2) 28.27 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 3 of 6 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Concrete Compressive Strength Test Report No.: 296073 Project No.: 0612510 Date of Service: 08/18/2007 Report Date: 08/24/2007 Project: Lesley Infrastructure Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Remarks: Cont: eastbound turn lane, Station 22+50 to 19+85, 25+75 to 28+25,32+25 to 34+00,35+75 to 37+28,39+00 to 4+05 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 4 of 6 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 296073 Project No.: 0612510 Date of Service: 08/18/2007 Report Date: 08/24/2007 Project: Lesley Infrastructure Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Concrete Supplier: Lacy Plant: On site Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 6" maximum Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design 1.0.: 5194 Placement Date: 08/18/2007 Weather Conditions: Cloudy Time Sampled: 10:55am Temperature - Air: 840F Truck No: NA Air Content: 4.1 % Overall Placement Location: Paving, eastbound and westbound Dividend St., Station 34+70 to 34+00, below) Measured Slump (inches) 1.75 Batch time: 10:50am Concrete: 780F Ticket No: NA Unit Weight (pcf): NA (cont. Sample Location: Station 36+00 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 98,630 Cylinder Marked Date Set No. Tested 3 1 08/21/2007 3 2 08/25/2007 3 3 09/15/2007 3 4 10/13/2007 OrA . .) Diameter . ys)./ (in) .' 3 .' 6.00 / 7 28 56 Area (in2) 28.27 Compressive Strength. .-11 (pst)" , /" ; 3,490 / /' // / /" -~ Fracture Type Unbonded Cap LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LBfLB) Page 5 of 6 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Concrete Compressive Strength Test Report No.: 296073 Project No.: 0612510 Date of Service: 08/18/2007 Report Date: 08/24/2007 Project: Lesley Infrastructure Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Remarks: Cont: eastbound turn lane, Station 22+50 to 19+85, 25+75 to 28+25,32+25 to 34+00,35+75 to 37+28,39+00 to 4+05 Technician: Ryan Rawlinson Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Alex Bennett PE (1-ec copy) 1-cc City of Coppell Attn: Mr. Lee Stone 1-cc City of Coppell Attn: Mr. Larry Davis Started: 06:15am Finished: 11 :30am Rone Engineering ~~.~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibilitY for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LBILB) Page 6 of 6