Duke Lesley 3C-LR070831 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Reinforcing Steel Inspection Report No.: 297359 Project No.: 0711530 Date of Service: 08/29/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Reinforcing Steel Inspection Report of Inspection Locations and Items Inspected: Paving, east side, (4) steel, (6) #6 pier cages for light standards, 12' long cages Item sins pected: Conforming Non Items Inspected' Conforming Non Item s Ins peeled: Co nfo rming Non Co nfo rm ing Co nlo rm ing Co nlo rm ing Placing Drawings Bar Length Column Ties Properly Approved x and Shape x Tied and Spaced x 8 ar Size x P ra per Bar P lacem ent x Stirrup Spacing NA BarGrade x Properly Tied x Stirrup Type NA 8 ars Clean x Dowel Bars in Place NA Lapped Splices NA Form Clean NA P roper Bar Suppa rts NA Co mer Bars NA Num ber of Bars x ProperCover NA Mechanical Splices NA Discrepancies I Comments: No apparent discrepancies were noted at the locations listed above. Technician: Denny Harris Rone Engineering See Report 297225 for technician time~~ Report Distribution: .. Orl9' ?,~~ ~;y~l,"ct;'" LP (0,,,,,, TXI Att"' Me, Pool Byrne . .. ., '. " ,~~ " , 1-cc City of Coppell Attn: Mr. Lee Stone K. Scott Watson AET 1-cc City of Coppell Attn: Mr. Larry Davis Project Manager ~ LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/LB) Page 1 of 1 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Drilled Pier Inspection Report No.: 296251 Project No.: 0711530 Date of Service: 08/21/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Straight Shaft Pier Inspection Report of Inspection Driller: c Inney fI Ing Pier Identification P 18 P 18.5 P 19 M 19 K/9 PierDiameter(in) 2 4/F 1 2 4/F 1 2 4/F 1 2 4/F 1 2 4/F 1 Depth of Pier From Surface (ft) 46.00 44.00 48.00 45.80 43.10 Depth of Bearing Stratum From Surface (ft) 36.00 32.00 36.00 35.00 32.80 Required Penetration (ft) 10.00 10.00 10.00 10.00 10.00 Actual Penetration (ft)" 10.00 12.00 12.00 10.80 10.30 Condition of Bottom (wet/drv) Dry Dry D rv Dry Dry Plum b Within Tolerance (ves I no) Yes Yes Yes Yes Yes C asina D iam eter (in) I Casing Length (ft) 2 6 13 6 26/32 .1 2 6/3 6 26/36 26/3 2 .1 N urn ber of Bars I Reinfo rci~B ar Size 6 1#6 6 1#6 6 1#6 6 1#6 h.61#6 - "="====c.=~,,=-~ -""'-=-." . ".". .. . " ..-- n -~-- Length of Relnforcing-::; lee! (ft) 44.00 41.80 42.80 43.80 41.10 Time Drilling was Completed (am Ipm) 8 :4 5 AM 9:30 AM 1 0 :2 0 AM 1 1 :03 AM 11:50AM Time Concrete was Placed (am Ipm) 10:19 AM 10:52AM 1 1 :32 AM 1 1 :57 AM 1 2 :20 P M Depth of Pier From Top of Concrete (ft) 44.42 42.42 46.42 44.22 41.52 E Ie va tio n: S urfa ce (ft)** 99.58 99.58 99.58 99.58 99.58 Elevation: Top of Pier (ft)** 98.00 98.00 98.00 98.00 98.00 Elevation: Bottom ofPier(ft)** 53.58 55.58 51.58 53.78 56.48 Elevation: Top of Bearing Stratum (ft.)** 63.58 67.58 63.58 64.58 66.78 Bearina Stratum (description) G r a v s h a Ie M K' D '11' Note: See report# 296252 forCompressive Strength TestSpecimens. * Additional Penetration not requested unless noted. **Elevation by others LIMITATIONS: The test results presented herein were prepared based upon the speCific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/JB) Page 1 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630.9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Drilled Pier Inspection Report No.: 296251 Project No.: 0711530 Date of Service: 08/21/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Straight Shaft Pier Inspection D rille r: M cK innev D rillina Pier Identification H.9/9.9 H/9.9 H 11 1 H 112 H 11 3 PierDiameter(in) 2 4 IF 1 2 4 IF 4 2 4/F 2 2 4 IF 2 2 4/F 2 De p th 0 f Pie r Fro m Surface(ft) 46.70 51.60 52.20 55.60 53.30 Depth of Bear in a Stratum Fro m Surface(ft) 32.20 36.80 35.90 39.60 36.50 Required Penetration (ft) 10.00 14.00 16.00 16.00 16.00 A ctua I P e ne tra tio n (ft)* 14.50 14.80 16.30 16.00 16.80 Condition of Bottom (wet I d rv) D rv Dry D rv D rv D rv Plumb Within Tolerance (ves Ino) Yes Yes Yes Yes Yes Casing D iam eter (in) I C asina Length (ft) 2 6 13 2 .1 2 6 13 6 2 6/3 6 2 6 13 6 2 6/3 2 .1 NumberofBars IReinforcinQ BarSize 6 1#6 9 1#6 6 1#6 6 1#6 6 1#6 Length of Reinforcina Steel (ft) 43.70 50.70 51.80 54.80 52.30 Time DrillinQ was Completed (am Ipm) 1 :00 PM 2:10 PM 3 :41 PM 4:12 PM 5:16 PM l':!m~Cc.ncre1E'< was Placed (aw-711m):: .- ""--1--:tHt P M 2:46 PM 4 :tHt:f" Mh_- ~ 5-:tHrP M.. D e p th 0 f P ie r Fro m Top 0 f Con c re te (ft) 44.12 51 .02 51.62 55.02 52.72 Elevation: Surface (ft)** 99.58 99.58 99.58 99.58 99.58 Elevation:Top of Pier (ft).. 97.00 99.00 99.00 99.00 99.00 Elevation: Bottom of Pier (ft)** 52.88 47.98 47.38 43.98 46.28 E Ie va tio n: Top of Bearina Stratum (fl.)** 67.38 62.78 63.68 59.98 63.08 Bearing Stratum (descriotion) Gravshale Note: See report # 296252 for Com pressive Strength Test S pecim ens. . Additional Penetration not requested unless nole d. uE levation by others Technician: Gary Kamrath Started: 06:15am Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne (1-ec copy) 1-cc City of Coppell Attn: Mr. Lee Stone 1-cc City of Coppell Attn: Mr. Larry Davis Finished: 06:45pm Rone Engineering p~ ~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/JB) Page 2 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Drilled Pier Inspection Report No.: 296552 Project No.: 0711530 Date of Service: 08/23/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Straight Shaft Pier Inspectian Report of Inspection D rille r: M cK inney Drilling Pie r Id e n ti fi c a ti a n F 114 F 115 F 116 F 117 F .4/1 0 Pier D iam eter (in) 2 4 IF 2 2 4 IF 2 2 4 IF 2 24 IF 2 2 4/F 6 De p th a f P ie r Fro. m S u rfa c e (ft) 47.80 48.00 48.50 46.00 48.70 Depth afBearing Stratum Fro. m S urfa ce (ft) 31.80 30.70 31.00 29.00 35.00 R e qui re d P e netra tia n (ft) 16.00 16.00 16.00 16.00 12.00 Actual Penetratian (ft)* 16.00 17.30 17.50 17.00 13.70 Canditian afBattam (wet I dry) Dry Dry Dry Dry Dry Plumb Within Talerance (yes Ina) Yes Yes Yes Yes Yes Casing Diameter(in)/Casina Lenath(ft) 2 6/3 2 26/30 2 6/3 2 .1 26 13 0 2 6 13 6 ~~ ~ be raf !3.il!S I R,~!!1 fOL~ ng~~ Bar Size 6 1#6 6 1#6 .6,1#6-,_ =6 ~if--:6;- ,. 6 1#6 . - .-.- ~ ,~ ~ Length at Relnfa(cina Steel (ft) 46.00 47.00 47.50 45'.50 - 48.70 Time Drillina was Campleted (a m I pm) 8:40AM 9:22 AM 10:12 AM 10:45 AM 12:56 PM Time Cancrete was Placed (am I pm) 9:00 AM 10:00AM 1 0 :40 A M 1 1 :20 AM 1 :55 PM Depth af Pier Fram Tap afCancrete (ft) 47.22 47.42 47.92 45.42 48.12 Elevatian: Surface (ft) .. 99.58 99.58 99.58 99.58 99.58 Elevatian: Tap afPier (ft).. 99.00 99.00 99.00 99.00 99.00 Elevatian: Battam afPier(ft)" 51.78 51 .58 51 .08 53.58 50.88 Elevatian: Tap afBearina Stratum ( ft.) .. 67.78 68.88 68.58 70.58 64.58 Bearing Stratum (descriptian) G ra y s h a Ie Nate:See repart# 296553 farCampressive StrengthTestSpecimens. * Additianal Penetratian nat requested unless nated. "Elevatian by athers LIMITATIONS: The test results presented herein were prepared based upon the specific samples pravided for testing. We assume no. responsibility far variatian in quality (composition, appearance, etc.) ar any ather feature of similar subject matter pravided by persans ar conditions over which we have no. control. Our letters and reparts are for the exclusive use af the clients to. wham they are addressed and shall nat be reproduced except in full withaut the written approval af Rone Engineering Services, ltd. (CH/LB) Page 1 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little Yor1t, SOO 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Drilled Pier Inspection Report No.: 296552 Project No.: 0711530 Date of Service: 08/23/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Straight Shaft Pier Inspection D rille r: M cKinnev D rillina Pie r Id e ntifica tio n F.4/10.3 F .7/1 0 F.7/10.3 F.9/10.3 F .8/1 0 Pie r D i a mete r (i n) 2 4/F 6 2 4/F 6 2 4 /F 6 2 4/F 6 2 4/F 6 D e p th 0 f P ie r Fro m S urfa ce (ft) 50.00 47.40 48.40 47.00 49.00 D e p th 0 f B e a ri n aStra tu m Fro m S urfa ce (ft) 36.00 34.50 36.00 34.00 35.50 Required Penetration (ft) 12.00 12.00 12.00 12.00 12.00 Actual Penetration (ft)" 14.00 12.90 12.40 13.00 13.50 Condition of Bottom (wet/drv) D rv D rv D rv D rv D rv Plumb Within Tolerance (ves /no) Ves ves Ves Ves Ves Casina Diameter(in)/Casino Lenoth (ft) 2 6/3 6 26 /3 0 2 6/36 2 6/3 0 2 6 /3 2 NumberofBars /Reinforcino BarSize 6 / #6 6 / #6 6 / #6 6 / # 6 6 / #6 LenQth of Reinforcina Steel (ft) 50.00 47.40 48.40 47.00 49.00 Time Drillino \Vas Comoleted (am tom) 1 :4 5 P M 1 :23 PM 3 :37 PM 4 :0 0 P M 3:12 PM Xime ::".;.;..(;t~ was:P:aced (am /UJ'lTT 2-:15 PM 2 :4 5F M-" 3.:55 PM 'M"lt: :. 0 ~t\II-.. ~ :'35'F~ Depth of Pier From Too 0 f Con c re te (ft) 45.75 43.15 42.82 42.75 44.75 Elevation: Surface (ft).. 99.58 99.58 99.58 99.58 99.58 Elevation: Too of Pier (ft).. 95.33 95.33 94.00 95.33 95.33 Elevation: Bottom of Pier (ft).. 49.58 52.18 51 .18 52.58 50.58 Elevation: Top of Bear in a Stratum 1ft.)" 63.58 65.08 63.58 65.58 64.08 Bearing Stratum (descriotion) Gravshale Note: See re port # 296553 for Compressive Strength Test Specimens. . Additional Penetration not requested unless noted. HE levation by others Technician: Denny Harris Started: 06:15am Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne (1-ec copy) 1-cc City of Coppell Attn: Mr. Lee Stone 1-cc City of Coppell Attn: Mr. Larry Davis Finished: 05:30pm Rone Engineering p~ ~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/LB) Page 2 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630.9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Drilled Pier Inspection Report No.: 296707 Project No.: 0711530 Date of Service: 08/24/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Straight Shaft Pier Inspection Depth of Pier From Surface (ft) 48.50 51.40 41.80 44.00 46.10 Depth of Bear in a Stratum From S u rfa ce (ft) 34.60 35.00 31.80 33.00 35.00 Required Penetration (ft) 12.00 12.00 10.00 10.00 10.00 Actual Penetration (ft)* 13.90 16.40 10.00 1 1 .00 1 1 .1 0 Condition of Bottom (wet/drv) Dry D rv Dry D rv Dry Plumb Within Tolerance (yes Ino) Yes Yes Yes Yes Yes Casing Diameter(in)/Casina Lenath (ft) 26/36 26/36 2 6 13 0 2 6 13 2 . 1 2 6/36 NumberofBars IReinforcing BarSize 6 1#6 6 1#6 6 1#6 6 1#6 6 1#6 Lenath of Reinforcina Steel (ft) 47.00 50.00 41.00 42.00 42.60 Time Drillina was Completed (am Ipm) 8:45AM 9:05 AM 10:05AM 1 0:20 AM 11:40AM ~. C o,ncc~tE' wa s:.::-P ia:<:e.d(a m IJ~:.m.L.__ ..~.AM.. - '!'o-;"1- 0-. AM. 11..;..:l...5...A-M ,".r" n 1. n D.' -- Depth of Pier From Top of Concrete (ft) 47.92 50.82 40.22 42.72 44.52 Elevation: Surface (ft)** 99.58 99.58 99.58 99.58 99.58 Elevation:Top of Pier (ft)** 99.00 99.00 98.00 98.00 98.00 Elevation: Bottom of Pier (ft)** 51.08 48.18 57.78 55.28 53.48 Elevation: Top of Bear in a Stratum (ft.)** 64.98 64.58 67.78 66.58 64.58 BearinQ Stratum (description) Grayshale Report of Inspection Note: See re port # 29670 8 fo r Com pre s s i ve S tre n g th T est S p e c i men s . * Additional Penetration not requested unless noted. **Elevation by others LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/JB) Page 1 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Drilled Pier Inspection Report No.: 296707 Project No.: 0711530 Date of Service: 08/24/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Straight Shaft Pier Inspection D rille r: M cK innev D rillina Pie r Id e ntifica tio n L/9.9 L/1 0.5 Pie r D i a mete r (i n) 2 4/F 1 2 4/F 1 De p th 0 f Pie r Fro m Surface(ft) 46.00 44.70 Depth of Bearing Stratum Fro m S u rfa c e (ft) 35.80 34.00 Required Penetration (ft) 10.00 10.00 A ctua I P e ne tra tio n (ft)" 10.20 10.70 Condition of Bottom (wet/dry) Dry Dry Plum b Within Tolerance (yes I no) Ves Ves C asinQ D iam eter (in) I C asina Lenath (ft) 26/36 2 6 13 6 NumberofBars I Reinforcina BarSize 6 1#6 6 1#6 LenQth of Reinforcing Steel (ft) 43.70 42.70 Time Drillina was Completed (am 10m) 12:00 PM 1 2 :45 P M , '''' ~-w-a-s:-P t;rc e d (a m l-p", ) Z . S 0 r M.. --+.2SPM -- - .. -. -- .~ -:-- Depth of Pier From Too of Concrete (ft) 44.42 43.12 Elevation: Surface (ft).. 99.58 99.58 Elevation: Top of Pier (ft).. 98.00 98.00 Elevation: Bottom of Pier (ft).. 53.58 54.88 E Ie va ti 0 n: Top of Bearina Stratum (ft.)"" 63.78 65.58 BearinQ Stratum (description) G ra y s h a Ie Note: See report # 296708 for Compressive Strength Test Specimens. . Additional Penetration not requested unless noted. "Elevation by others Technician: Denny Harris Started: 06:15am Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne (1-ec copy) 1-cc City of Coppell Attn: Mr. Lee Stone 1-cc City of Coppell Attn: Mr. Larry Davis Finished: 02:00pm Rone Engineering p~ ~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written appnoval of Rone Engineering Services, Ltd. (CH/JB) Page 2 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 15241 1101 W Little York, Ste 600, Houston, TX 11040 4421 Freidrich, Ste 195, Austin, TX 18144 Corporate Phone: (214) 630-9145 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Drilled Pier Inspection Report No.: 296907 Project No.: 0711530 Date of Service: 08/27/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Straight Shaft Pier Inspection Report of Inspection D rille r: c Inney rlllnQ Pier Identification L/1 1 L/1 1.5 L/12 L/1 2 .5 L/13 PierDiameter(in) 2 4/F 1 2 4/F 1 2 4/F 1 2 4/F 1 2 4/F 1 D e p th 0 f Pie r F ro m Surface (ft) 46.00 42.60 40.50 46.50 47.20 Depth ofBearinQ Stratum Fro m Surface(ft) 35.70 32.30 30.50 36.40 37.00 R e qui re d P e ne tra tio n (ft) 10.00 10.00 10.00 10.00 10.00 A ctua I P e ne tra tio n (ft). 1 0.30 10.30 10.00 10.10 10.20 Condition of Bottom (wet 1 dry) Dry D rv D rv D rv Dry Plum b Within Tolerance (yes / no) Yes Yes Ves Ves Ves C asinQ Diameter (in) 1 Casing Lenath (ft) 2 6 13 6 26/32.1 2 6 13 0 2 6 13 6 2 6/32 . 1 N u.~~ e r 0 f B a_~s_-' R e info rcin.!L~ a r Size 6 1 #6 6 / #6 6 1 #6 6 1 #6 6 1 #6 F'" _. _. . . ~ .~..=.~... .. H _.- _. ~. ..- r.~' . ".,- --~- Length of Relnforcina Steel (ff)" . -- 44.50 . 40:00' 38.70 44.50 - 44.5U Tim e DrillinQ was Completed (am 1 pm) 9 :2 8 AM 9 :4 0 AM 10:10 AM 1 0 :3 0 AM 1 0 :47 A M Tim e Con c re te was P la c e d (am 1 pm) 9 :5 0 AM 10:15 AM 1 0 :4 0 AM 1 1 :05 AM 1 1 :45 A M De p th 0 f P ie r Fro m Top of Concrete (ft) 44.42 41.02 38.92 44.92 45.62 Elevation: Surface (fO" 9 9.58 99.58 99.58 99.58 99.58 Elevation:Top of Pier (ft).. 98.00 98.00 98.00 98.00 98.00 Elevation: Bottom of Pier (fO" 5 3 .58 56.98 59.08 53.08 52.38 Elevation: Top of Bearina Stratum (ft.).. 63.88 67.28 69.08 63.18 62.58 Bearing Stratum (description) G ra v s h a Ie M K' D . r Note: See re port # 296908 fo r Com pre s s i ve S tre n g th T est S p e c i men s . . Additional Penetration not requested unless noted. "Elevation by others LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/JB) Page 1 of 3 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Drilled Pier Inspection Report No.: 296907 Project No.: 0711530 Date of Service: 08/27/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Straight Shaft Pier Inspection D rille r: M cK inney Drilling Pie rid e ntifica tio n L/1 3.5 L/14 L/1 4 .5 M 115 M 11 5.5 PierDiameter(in) 2 4/F 1 2 4/F 1 2 4/F 1 2 4/F 1 2 4/F 1 De p th 0 f Pie r Fro m Surface(ft) 45.00 41.50 45.00 42.00 42.50 Depth of Bearing Stratum Fro m S u rfa c e (ft) 33.30 30.50 34.60 30.40 31.00 Required Penetration (ft) 10.00 10.00 10.00 10.00 10.00 A ctua I P e ne tra tio n (ft)' 11 .70 11 .00 10.40 1 1 .60 11 .50 Condition of Bottom (wet I dry) Dry D rv D rv D rv Dry Plumb Within Tolerance (yes Ino) Yes Yes Yes Yes Yes Casino Diameter(in)/Casino Lenoth (ft) 2 6 13 2 .1 2 6/3 0 26/32.1 2 6 13 0 26/32.1 NumberofBars IReinforcing BarSize 6 1#6 6 1#6 6 1#6 6 1#6 6 1#6 Length of Reinforcing Steel (ft) 42.80 39.20 43.20 40.50 40.20 Time Drilling was Completed (am Ipm) 12:02 PM 12:30 PM 1 :26 PM 2:20 PM 3 :4 5 P M 'T'm.e Concrete wZl~'P!ace.d (am !-pm) 1 :.1.0 PM 1:30PM 2~4 5'P M -; .1_, 0 F' 1v\-- 1-_;l~2-'f> tvt- D e p th 0 f Pie r Fro m Top 0 f Con c re te (ft) 43.42 39.92 43.42 40.42 40.92 Elevation: Surface (ft).. 99.58 99.58 99.58 99.58 99.58 Elevation:Top of Pier (ft).. 98.00 98.00 98.00 98.00 98.00 E Ie va tio n: Botto m of Pier (ft).. 54.58 58.08 54.58 57.58 57.08 Elevation: Top of Bearing Stratum (ft.).. 66.28 69.08 64.98 69.1 8 68.58 B e a ri noS tra tu m (description) G ra v s h a Ie Note: See report # 296908 for Compressive Strength Test Specimens. .. Additional Penetration not requested unless noted. HE levation by others LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/JB) Page 2 of 3 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Drilled Pier Inspection Report No.: 296907 Project No.: 0711530 Date of Service: 08/27/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Straight Shaft Pier Inspection D rille r: M cKinnev D rillinQ Pie r Identifica tio n M 11 6 PierDiameter(in) 2 4/F 1 DepthofPierFrom Surface (ft) 42.60 Depth of Bearing Stratum Fro m S urfa ce (ft) 31 .40 Required Penetration (ft) 10.00 A ctua I P e ne tra tio n (ft)' 1 1 .20 Condition of Bottom (wet I d rv) Dry Plum b Within Tolerance (ves I no) Yes Casino Diameter(in)/Casing Lenoth (ft) 2 6 13 0 NumberofBars IReinforcing BarSize 6 1#6 Length of Reinforcing Steel (ft) 40.50 Time Drilling was Completed (am Ipm) 4 :07 PM ~-e-c-r:1:"rc:te w;rs-?laC"ed (a-m {pm). - - 4-:-4-5 P-M- -=--.-- ----- -::-- ---- ----~ Depth of Pier From Too of Concrete (ft) 41.02 Elevation: Surface (ft)" 99.58 Elevation: Top of Pier (ft).. 98.00 Elevation: Bottom of Pier (ft).. 56.98 E Ie va tio n: Top of Bearing Stratum (fty' 68.18 Bearina Stratum (description) G ra v s h a Ie Note: See report # 296908 for Com pressive Strength Test Specim ens. .,. Additional Penetration not requested unless noted. **E levation by others Technician: Denny Harris Started: 06:15am Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Altn: Mr. Paul Byrne (1-ec copy) 1-cc City of Coppell Altn: Mr. Lee Stone 1-cc City of Coppell Altn: Mr. Larry Davis Finished: 05:45pm Rone Engineering pad- ~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition. appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/JB) Page 3 of 3 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 296950 Project No.: 0711530 Date of Service: 08/27/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Perform In-Place Density Testing PROJECT DATA Contractor: Duke Construction, LP Test Method: ASTM D-6938 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: DT Standard Counts Moisture Density Current: 729 Current: 2516 Previous: 731 Previous: 2509 MOISTURE DENSITY RELATIONS Maximum Moisture Density Project Requirements MID No. Description % (pet) Moisture Density 272995 Brown I Silty Clay wI Organics 23.5 96.0 Minimum +4 92-96 272998 Brown I Silty Clay wI Organics 22.5 96.5 Optimum +4 95 min ..- ~-~.- FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (% max) Utility backfill Sanitary sewer line, section A, 50' from south 6" 272995 31.1 116.0 88.5 92 end, l' below grade Utility backfill 2 Sanitary sewer line, section A, 50' from south 6" 272995 29.9 116.3 89.5 93 end, final Utility backfill 3 Sanitary sewer line, section A, 200' from south 6" 272995 31.5 116.1 88.3 92 end, 3' below grade Utility backfill 4 Sanitary sewer line, section A, 200' from south 6" 272995 29.5 116.3 89.8 94 end,~ below grade Utility backfill 5 Sanitary sewer line, section A, 200' from south 6" 272995 29.2 115.1 89.1 93 end, l' below grade Utility backfill 6 Sanitary sewer line, section A, 200' from south 6" 272995 28.3 114.2 89.0 93 end, final Utility backfill 7 Fire lane, center, l' below grade 6" 272998 22.8 116.9 95.2 99 LIMITATIONS: The test results presented herein were prepared based upon the specifiC samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 1 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 296950 Project No.: 0711530 Date of Service: 08/27/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Perform In-Place Density Testing FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pct) (pct) (% max) Utility backfill 8 Fine lane, center, final 6" 272998 24.5 116.2 93.3 97 Technician: Joe Jernigan Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne (1-ec copy) 1-cc City of Coppel! Attn: Mr. Lee Stone 1-cc City of Coppel! Attn: Mr. Larry Davis Started: 09:00am Finished: 11 :30am Rone Engineering P-~~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 2 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of Reinforcing Steel Inspection Report No.: 297359 Project No.: 0711530 Date of Service: 08/29/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Reinforcing Steel Inspection Report of Inspection Locations and Items Inspected: Paving, east side, (4) steel, (6) #6 pier cages for light standards, 12' long cages ~em s Inspected: Co nfo rm ing Non Items Inspected: Co nfo rm ing Non Item s Ins peeled: Conforming Non Co nfo rm ing Conforming Co nform ing P lac ing 0 rawings Bar Length Column Ties Properly Approved x and Shape x Tied and Spaced x Bar Size x Pro per Bar P lacem ent x Stirrup Spacing NA Cal GraJu .- Lied-- - x $tir~ .. NA - .... -".--'-'--'- - .. Bars Clean x Dowel Bars in Place NA Lapped Splices NA Form Clean NA P roper Bar Suppo rts NA Comer Bars NA NumberofBars x Proper Cover NA Mechanical Splices NA Discrepancies I Comments: No apparent discrepancies were noted at the locations listed above. Technician: Denny Harris Rone Engineering See Report 297225 for technician time~ ~ Report Distribution: ". ~ Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne . . . ~- . '.' . . . (1-ec copy) 1-cc City of Coppell Attn: Mr. Lee Stone K Scott Watson AET 1-cc City of Coppell Attn: Mr. Larry Davis . Project Manager ~ LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/LB) Page 1 of 1 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 296400 Project No.: 0711530 Date of Service: 08/22/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: 01 Specification Requirements Strength: 3,000 psi @ 28 days Slump (in.): 5" - 7" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design 1.0.: 7751 PW Placement Date: 08/22/2007 Weather Conditions: Cloudy Time Sampled: 1 0:40am Temperature - Air: 900F Truck No: 137 Air Content: NA Overall Placement Location: Point West I - H/14 Batch time: 10:05am Concrete: 920F Ticket No: 13120 Unit Weight (pet): NA Measured Slump (inches) 7.0 Sample Location: Grid line H/14 REPORT OF TESTS Cylinder Marked Date Set No. Tested 1 1 08/29/2007 1 2 09/19/2007 1 3 09/19/2007 1 4 10/17/2007 Age (days) 7 Diameter (in) 6.00 28 28 56 Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 87,720 Compressive Strength (psi) 3,100 Fracture Type Unbonded Cap Area (in2) 28.27 Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Brian Pierce (1-cc copy) 1-cc City of Coppell Attn: Mr. Lee Stone 1-cc City of Coppell Attn: Mr. Larry Davis Rone Engineering s" Report 296399 10'''0"0;000 t;mep-~ ~ K. Scott Watson, AET Project Manager Technician: Denny Harris LIMITATIONS The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/LB) Page 1 of 1 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 296252 Project No.: 0711530 Date of Service: 08/21/2007 Report Date: 08/31/2007 Project: Point West Office I Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: 01 Specification Requirements Strength: 3,000 psi @ 28 days Slump (in.): 5" - 7" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design 1.0.: 7751 PW Placement Date: 08/21/2007 Weather Conditions: Partly cloudy Time Sampled: 11 :35am Batch time: 11 :04am Temperature - Air: 870F Concrete: 920F Truck No: 127 Ticket No: 13101 Air Content: NA Unit Weight (pcf): NA Overall Placement Location: See Drilled Pier inspection Measured Slump (inches) 6.5 Sample Location: Pier PIg REPORT OF TESTS Cylinder Marked Date Set No. Tested 1 1 08/28/2007 2 09/18/2007 3 09/18/2007 1 4 10/16/2007 Age (days) 7 Diameter (in) 6.00 28 28 56 Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 65,650 Compressive Strength (psi) 2,320 Fracture Type Unbonded Cap Area (in2) 28.27 Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Brian Pierce (1-cc copy) 1-cc City of Coppell Attn: Mr. Lee Stone 1-cc City of Coppell Attn: Mr. Larry Davis Rone Engineering Soo R,port 296251 foc,,,,,,,;,;>o ';m'p-~ ~ K. Scott Watson, AET Project Manager Technician: Gary Kamrath LIMITATIONS The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd. (CH/LB) Page 1 of 1