Gateway BP(3.1)-LR070906
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 297075
Project No.: 0712786
Date of Service: 08/28/2007
Report Date: 09/06/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 3% - 5%
Test Method: ASTM C-172
..~ UIi Cp3i (except 12.1.2)
ASTM C-143
ASTM C-231
ASTM C-1 064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1524
Placement Date: 08/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 03:02am Batch time: 02:23am
Temperature - Air: 700F Concrete: 830F
Truck No: 1187 Ticket No: 13695404
Air Content: 5.3% Unit Weight (pcf): NA
Overall Placement Location:
I-'Clving, I'l-lUU':i2!.2I..: I to i:.:L~~h_, .Lc;: 0, P9 _' ;. _ i
Measured
Slump
(inches)
5.0
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
1 1 09/04/2007 7 6.00 28.27 116,490 4,120 Cone/Shear
2 09/25/2007 28
3 09/25/2007 28
4 10/23/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM!LS) Page 1 of 5
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 297075
Project No.: 0712786
Date of Service: 08/28/2007
Report Date: 09/06/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Measured
Slump
(inches)
5.0
Mix Design I.D.: 1524
Placement Date: 08/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 04:30am Batch time: 03:28am
Temperature - Air: 710F Concrete: 860F
Truck No: 136 Ticket No: 13695414
Air Content: 5.0% Unit Weight (pet): NA
Overall Placement Location:
lu. r.~-F!,l'jmg-;i'r"f1.J1J:.JLr2/ [I to E"'I~S4.!/ h7&, pg (: i.Ji
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTr..,1 C3"1 (elffiBpt
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
-
2 1 09/04/2007 7 6.00 28.27 115,270 4,080 Cone/Split
2 2 09/25/2007 28
2 3 09/25/2007 28
2 4 10/23/2007 56
Remarks: Water added at site: 10 gallons
LIMITATIONS The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TMlLB) Page 2 of 5
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Concrete Compressive Strength Test
Report No.: 297075
Project No.: 0712786
Date of Service: 08/28/2007
Report Date: 09/06/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Constructors & Associates Mix Design 1.0.: 1524
Concrete Supplier: Redi-Mix Placement Date: 08/28/2007
Plant: 136 Weather Conditions: Cloudy, calm
Specification Requirements Time Sampled: 04:53am Batch time: 04:31am
Strength: 3,600 psi @ 28 days Temperature - Air: 730F Concrete: 900F
Slump (in.): 4" - 6" Truck No: 1032 Ticket No: 13695425
Air (%): 3% - 5% Air Content: 4.9% Unit Weight (pct): NA
Test Method: ASTM C-172 Overall Placement Location:
ASTM C'31 (ex1:'.3j_L~6..T..2"'r--FaViITg:-W;;Y1Ai~ou.9060 (ot:=2"99563 1017, pg C"1.01
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Measured
Slump
(inches)
5.5
Sample Location:
Same as above
REPORT OF TESTS
Cylinder
Marked Date
Set No. Tested
3 1 09/04/2007
3 2 09/25/2007
3 3 09/25/2007
3 4 10/23/2007
Age
(days)
7
Diameter
(in)
6.00
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
113,850
Area
(in2)
28.27
Compressive
Strength
(psi)
4,030
Fracture
Type
Cone/Split
28
28
56
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, LId.
(TMILB) Page 3 of 5
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 297075
Project No.: 0712786
Date of Service: 08/28/2007
Report Date: 09/06/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 3% - 5%
Test Method: ASTM C-172
i\STM C-3 t texcepl'rO-:-i .2) -~-
ASTM C-143
ASTM C-231
ASTM C-1 064
ASTM C-138
ASTM C-39
Mix Design I.D.: 1524
Placement Date: 08/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 07:03am Batch time: 06:16am
Temperature - Air: 730F Concrete: 880F
Truck No: 1187 Ticket No: 13695443
Air Content: 4.5% Unit Weight (pcf): NA
Overall Placement Location:
-Favlng, N-' UUi:rdU.-auoU fQE-2!:J!:J5tiJ. 101 j, pg (; i .01
Measured
Slump
(inches)
5.0
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
85,270
Cylinder
Marked Date Age
Set No. Tested (days)
4 1 09/04/2007 7
4 2 09/25/2007 28
4 3 09/25/2007 28
4 4 1 0/23/2007 56
Diameter
(in)
6.00
Remarks: Water added at site: 10 gallons
Area
(in')
28.27
Compressive
Strength
(psi)
3,020
Fracture
Type
Cone/Split
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TMfLB) Page 4 of 5
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 09/06/2007
Project: ateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Maximum Compressive
Age Diameter Area Load Strength Fracture
(days) (in) (in') (Ibs) (psi) Type
7 6.00 28.27 71,180 2,520 Unbonded Cap
28 6.00 28.27 92,120 Cone/Split
28 6.00 28.27 85,250 Cone/Split
Average
56
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTr.~ C-231
ASTM C-1 064
ASTM C-138
ASTM C-39
Cylinder
Marked
Set No.
- -
1 1
Date
Tested
08/14/2007
1
1
2
3
09/04/2007
09/04/2007
4 10/02/2007
Mix Design I.D.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 02:30am Batch time: 01 :24am
Temperature - Air: 820F Concrete: 860F
Truck No: 1378 Ticket No: 13853996
Air Content: 1.3% Unit Weight (pet): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
4.5
Sample Location:
60' west, 20' south from northwest building corner
(\{~
* Does not comply with specified strength
Remarks: Dowels were placed prior to con
concrete placement.
placement; discrepancies noted on report #294654 were corrected prior to
1J''1/~7
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar SUbject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/LB) Page 1 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 09/06/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Maximum Compressive
Diameter Area Load Strength Fracture
(in) (in') (Ibs) (psi) Type
6.00 28.27 75,000 2,650 Unbonded Cap
6.00 28.27 95,700 3,380 Cone/Split
6.00 28.27 98,430 3,480 Cone/Split
Average 3,430 *
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-731
ASTM C-1064
ASTM C-138
ASTM C-39
Cylinder
Marked Date
Set No. Tested
2 1 08/14/2007
2 2 09/04/2007
2 3 09/04/2007
2 4 10/02/2007
Age
(days)
7
28
28
56
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 03:30am Batch time: 02:23am
Temperature - Air: 810F Concrete: 850F
Truck No: 1281 Ticket No: 13554004
Air Content: 3.4% Unit Weight (pcf): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
5.0
Sample Location:
105' west, 15' south from northwest building corner
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/LB) Page 2 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 09/06/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 04:45am Batch time: 04: 11 am
Temperature - Air: 830F Concrete: 850F
Truck No: 1351 Ticket No: 13554015
Air Content: 3.3% Unit Weight (pet): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
5.0
Sample Location:
150' west, 25' south from northwest building corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
3 1 08/14/2007 7 6.00 28.27 77,680 2,750 Unbonded Cap
3 2 09/04/2007 28 6.00 28.27 94,760 3,350 Cone/Split
3 3 09/04/2007 28 6.00 28.27 99,640 3,520 Cone/Split
Average 3,440 *
3 4 10/02/2007 56
* Does not comply with specified strength
Remarks: Water added at site: 10 gallons
LIMITATIONS The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KWfLB) Page 3 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste GOO, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 09106/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Maximum Compressive
Age Diameter Area Load Strength Fracture
(days) (in) (in') (Ibs) (psi) Type
7 6.00 28.27 64,250 2,270 Unbonded Cap
28 6.00 28.27 89,740 3,170 Cone/Split
28 6.00 28.27 84,4 1 0 2,990 Cone/Split
Average 3,080 *
56
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Cylinder
Marked Date
Set No. Tested
4 1 08/14/2007
4 2 09/04/2007
4 3 09/04/2007
4 4 10/02/2007
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 07:25am Batch time: 05:32am
Temperature - Air: 830F Concrete: 870F
Truck No: 1278 Ticket No: 13554024
Air Content: 3.2% Unit Weight (pet): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
4.5
Sample Location:
240' west, 25' south from northwest building corner
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, LId
(KW/LB) Page 4 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 09/06/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Maximum Compressive
Age Diameter Area Load Strength Fracture
(days) (in) (in') (Ibs) (psi) Type
7 6.00 28.27 65,050 2,300 Unbonded Cap
28 6.00 28.27 84,600 2,990 Shear
28 6.00 28.27 81,620 2,890 Cone/Split
Average 2,940 *
56
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Cylinder
Marked Date
Set No. Tested
5 1 08/14/2007
5 2 09/04/2007
5 3 09/04/2007
5 4 10/02/2007
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 09:40am Batch time: 08:47am
Temperature - Air: 850F Concrete: 900F
Truck No: 1393 Ticket No: 13554043
Air Content: 3.2% Unit Weight (pcf): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
6.0
Sample Location:
220' west, 50' south from northwest building corner
* Does not comply with specified strength
LIMITATIONS The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our ietters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in fuli without the written approval of Rone Engineering Services, Ltd.
(KWILB) Page 5 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 09/06/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
T est Method: ASTM C-1 72
ASTM C-31 (except 10.1.2)
ASTM C-143
ASn,1 C-2~1
ASTM C-1 064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 12:20pm Batch time: 11 :11am
Temperature - Air: 890F Concrete: 920F
Truck No: 1248 Ticket No: 13554069
Air Content: 3.3% Unit Weight (pcf): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
6.0
Sample Location:
170' west, 100' south from northwest building corner
REPORT OF TESTS
Cylinder
Marked
Set No.
- -
6 1
Date
Tested
08/14/2007
Age
-TJP-
28
28
Diameter
(in)
6.00
6 2
6 3
09/04/2007
09/04/2007
6
4
10/02/2007
56
(>
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
47,980
Area
(in2)
28.27
6.00
6.00
28.27
28.27
64,160
69,530
Average
* Does not comply with specified strength
Compressive
Strength
~
Fracture
Type
Unbonded Cap
Cone/Split
Cone/Split
(/
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KWILB) Page 6 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 09/06/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
.~. ,?T~:' r=:-'231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 02:25pm Batch time: 01: 17pm
Temperature - Air: 910F Concrete: 930F
Truck No: 1279 Ticket No: 13554092
Air Content: 3.3% Unit Weight (pcf): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
6.0
Sample Location:
60' west, 35' south from northwest building corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
7 1 08/14/2007 7 6.00 28.27 77,290 2,730 Unbonded Cap
7 2 09/04/2007 28 6.00 28.27 99,600 3,520 Shear
7 3 09/04/2007 28 6.00 28.27 106,680 3,770 Cone/Split
Average 3,650
7 4 10/02/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/LB) Page 7 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 296989
Project No.: 0712786
Date of Service: 08/27/2007
Report Date: 09/06/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perfomn required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Constructors & Associates
Concrete Supplier: LMC
Plant: 3
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
...^,~.T~\{~ (' .'/'11
ASTM C-1064
ASTM C-138
ASTM C-39
Measured
Slump
(inches)
4.0
Mix Design I.D.: 1551
Placement Date: 08/27/2007
Weather Conditions: Partly cloudy, calm
Time Sampled: 02:35pm Batch time: 01 :24pm
Temperature - Air: 930F Concrete: 910F
Truck No: 5023 Ticket No: 3235884
Air Content: 4.3% Unit Weight (pcf): NA
Overall Placement Location:
Inlet top, northwest corner of west parking lot, leave out area around storm drain, 100'
north, 80' of (cont)
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
1 1 09/03/2007 7 6.00 28.27 98,500 3,480 Unbonded Cap
2 09/24/2007 28
3 09/24/2007 28
4 10/22/2007 56
Remarks: Cont: southeast corner of west parking lot
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports a~e
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TMlLB) Page 1 of 2