Loading...
Northlake College-LR070920 K L E I N F E L D E R 2211 Century Center Blvd., Suite 101, Irving, TX 75062 972-870-0808 Metro 972-953-0398 Fax 972-870-0802 IN-PLACE MOISTURE DENSITY TEST RESULTS To: Dallas County Community College Dist. Test Date: 9/18/2007 1505 South Lamar, Suite 1015 Project No: 87015 Dallas, Texas 75215 Report Date: 9/20/2007 Report No: 097387 Project: North Lake College, N Campus Definitions of Terms Location: W Sandy Lake Road @ SH 121 ROP- Rt Otr Point CL - Centerline Field Rep: J. Schuler LQP - Lt Qtr Point Sta - Station Test Test Location Depth D Wet Field Dry Proctor Percent No. Lift 0 Density Moisture Density No. Proctor (%) (pet) Density Blda Pad Subgrade / 1 15' E and 120' N of SW corner 1 st 126.4 21.2* 104.3 001354 107.4 2 75' E and 80' N of SW corner 1 st 125.6 21.2* 103.6 001354 I 106.7 3 100' Wand 110' N of SE corner 1 st 122.5 22.3* 100.2 001354 , 103.2 4 20' Wand 30' N of SE corner 1 st 126.0 21.2* 104.0 001354 107.1 "--- Proctor No: Description Opt. Moisture Max. Density 001354 Gray fat clay 22.6 97.1 Specs. Gauge No: 28714 Test Methods: ASTM D 2922 Dens. (%) Min 95 Std. Density Count: 2297 ASTM D 3017 Moist. (%) +1 to +5 Std. Moist Count: 658 ASTM D 698 Trans. Depth (in.): 6 ~ Remarks: d I J , (j) 1~ . I Reports to: i Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) ,/.. ~ Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) ( ( KLEI FEL'~. A / ~Jil fIJ DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu) , DCCCD Bond Office; Attn: James Williams Uames.williams@dcccdedu) 1M~ '7YDlj r DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com) I Joel Peters, PEl I I ~ Jacobs: Attn: Jennifer Blount (Jennifer.blount@jacobs.com) 1- City of Coppell; Attn: Larry Davis 1- City of Coppell; Attn: Lee Stone The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be Indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety. K L E I N F E L D E R 2211 Century Center Blvd., Suite 101, Irving, TX 75062 972-870-0808 Metro 972-953-0398 Fax 972-870-0802 IN-PLACE MOISTURE DENSITY TEST RESUL TS To: Dallas County Community College Dist. Test Date: 9/18/2007 1505 South Lamar, Suite 1015 Project No: 87015 Dallas, Texas 75215 Report Date: 9/20/2007 Report No: 097391 Project: North Lake College, N Campus Definitions of Terms Location: W Sandy Lake Road @ SH 121 RQP- Rt Qtr Point CL - Centerline Field Reo: J. Schuler LOP - Lt Otr Point Sta - Station Test Test Location Depth D Wet Field Dry Proctor Percent No. Lift 0 Density Moisture Density No. Proctor (%) (pet) Density Retests 1 # 1 from 9/18 1 st 120.5 23.8 97.3 001354 100.2 2 # 2 from 9/18 1st 120.2 24.2 96.8 001354 99.7 3 # 3 from 9/18 1 st 119.2 24.0 96.1 001354 99.0 4 # 4 from 9/18 1 st 120.2 23.9 97.0 001354 99.9 Proctor No: Description Opt. Moisture Max. Density 001354 Gray fat clay 22.6 97.1 Specs. Gauge No: 28714 Test Methods: ASTM D 2922 Dens. (%) Min 95 Std. Density Count: ASTM D 3017 Moist. (%) +1 to +5 Std. Moist Count: ASTM D 698 Trans. Depth (in.): 6 Remarks: Reports to: Starling Richardson Const.; Atln: Eric Stanaland (eps@starlingrichardson.com) Starling Richardson Const.; Atln: Andy Munoz (amunoz@starlingrichardson.com) DCCCD Bond Office; Atln: Brenda Spinelli (brenda.spinelli@dcccd.edu) (yjZ DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu) DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) '//~ Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com) /Joel Peters, P.E. Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com) 1- City of Coppell; Attn: Larry Davis 1- City of Coppell; Atln: Lee Stone The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.