Report of Concrete Compressive Strength Test
Report No.: 297201
Project No.: 0612510
Date of Service: 08/27/2007
Report Date: 09/06/2007
Project: Lesley Infrastructure
Services: Test Compressive Strength samples delivered to laboratory.
PROJECT DATA
Contractor:
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): 5" - 7"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
--^SlM~:>i38~
ASTM C-39
Mix Design 1.0.: 7751
Placement Date: 08/27/2007
Weather Conditions: Sunny
Time Sampled: 10:30am
Temperature - Air:
Truck No: NA
Air Content: NA
Overall Placement Location:
Curb inlet throat
Measured
Slump
(inches)
Batch time:
Concrete:
Ticket No: NA
Unit Weight (pet): NA
Sample Location:---- ._~
Station 3+50, lateral A-2, Station 0+61.96, lateral A-1, Station 0+06.12, lateral C-5,
Station 30+06.12, lateral C, Station 12+83.36, line A, Station 0+66.40, lateral A-3
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
110,630
Cylinder
Marked Date
Set No. Tested
1 1 09/03/2007
1 2 09/24/2007
1 3 09/24/2007
4 10/22/2007
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Area
(in')
28.27
Compressive
Strength
(psi)
3,910
Fracture
Type
Unbonded Cap
Remarks: All information other than concrete compressive strength test results was provided by the contractor and
assumed to be correct.
Technician: Undefined
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX)
Attn: Mr. Alex Bennett PE (1-ec copy)
1-ec Lacy Construction Attn: Mr. Kevin Briles
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Attn: Mr. Larry Davis
Rone Engineering
P-~~
K. Scott Watson, AET
Project Manager