Report of Concrete Compressive Strength Test
Report No.: 295589
Project No.: 0712786
Date of Service: 08/14/2007
Report Date: 09/13/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: LMC
Plant: 3
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1551
Placement Date: 08/14/2007
Weather Conditions: Sunny
Time Sampled: 02: 15pm
Temperature - Air: 1050F
Truck No: 1096
Air Content: 3.4%
Overall Placement Location:
Inlets
Batch time: 01 :29pm
Concrete: 920F
Ticket No: 3235136
Unit Weight (pet): NA
Measured
Slump
(inches)
3.0
Sample Location:
Inlets, front parking lot in front of building 2
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 08/21/2007 7 6.00 28.27 90,430 3,200 Unbonded Cap
2 09/11/2007 28 6.00 28.27 116,060 4,100 Cone/Split
3 09/11/2007 28 6.00 28.27 124,710 4,410 Cone/Split
Average 4,260
4 10/09/2007 56
Remarks: Water added at site: 10 gallons
LIMITATIONS The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 1 of 2
Rone Engineering
..
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Report of Concrete Compressive Strength Test
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report No.: 295527
Project No.: 0712786
Date of Service: 08/14/2007
Report Date: 09/13/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1 064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/14/2007
Weather Conditions: Sunny
Time Sampled: 03:05am
Temperature - Air: 780F
Truck No: 1032
Air Content: 4.1 %
Overall Placement Location:
Paving
Batch time: 02:44am
Concrete: 900F
Ticket No: 13693938
Unit Weight (pcf): NA
Measured
Slump
(inches)
4.75
Sample Location:
Block B, lot 1, south section
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
-
1 1 08/21/2007 7 6.00 28.27 77,420 2,740 Unbonded Cap
2 09/11/2007 28 6.00 28.27 99,820 3,530 Cone/Split
3 09/11/2007 28 6.00 28.27 103,600 3,660 Shear
Average 3,600
4 10/09/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 1 of 5
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 295527
Project No.: 0712786
Date ot Service: 08/14/2007
Report Date: 09/13/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/14/2007
Weather Conditions: Sunny
Time Sampled: 04:16am
Temperature - Air: 780F
Truck No: 1036
Air Content: 5.1 %
Overall Placement Location:
Paving
Batch time: 03:29am
Concrete: 920F
Ticket No: 13693943
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
Block B, lot 1, center section
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
2 1 08/21/2007 7 6.00 28.27 85,240 3,010 Unbonded Cap
2 2 09/11/2007 28 6.00 28.27 108,320 3,830 Cone/Shear
2 3 09/11/2007 28 6.00 28.27 106,430 3,760 Cone/Shear
Average 3,800
2 4 10/09/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 2 of 5
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 295527
Project No.: 0712786
Date of Service: 08/14/2007
Report Date: 09/13/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/14/2007
Weather Conditions: Sunny
Time Sampled: 05:21am
Temperature - Air: 800F
Truck No: 1036
Air Content: 5.3%
Overall Placement Location:
Paving
Batch time: 04:46am
Concrete: 950F
Ticket No: 13693958
Unit Weight (pcf): NA
Measured
Slump
(inches)
6.0
Sample Location:
Block B, lot 1, north section
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
3 1 08/21/2007 7 6.00 28.27 76,780 2,720 Un bonded Cap
3 2 09/11/2007 28 6.00 28.27 103,670 3,670 Cone/Shear
3 3 09/11/2007 28 6.00 28.27 113,070 4,000 Shear
Average 3,830
3 4 10/09/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 3 of 5
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 295527
Project No.: 0712786
Date of Service: 08/14/2007
Report Date: 09/13/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 136
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1 064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 23601524
Placement Date: 08/14/2007
Weather Conditions: Sunny
Time Sampled: 06:50am
Temperature - Air: 800F
Truck No: 1017
Air Content: 4.9%
Overall Placement Location:
Paving
Batch time: 06: 1 Dam
Concrete: 950F
Ticket No: 13693969
Unit Weight (pet): NA
Measured
Slump
(inches)
5.25
Sample Location:
Block B, lot 1, east section
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
4 1 08/21/2007 7 6.00 28.27 85,930 3,040 Unbonded Cap
4 2 09/11/2007 28 6.00 28.27 109,090 3,860 Cone/Shear
4 3 09/11/2007 28 6.00 28.27 117,780 4,170 Cone/Split
Average 4,010
4 4 10/09/2007 56