Gateway BP(3.1)-LR071022
Rone Engineering
Client: Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 296560
Project No.: 0712786
Date of Service: 08/23/2007
Report Date: 10/22/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 88
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 1524
Placement Date: 08/23/2007
Weather Conditions: Clear, warm
Time Sampled: 03:50pm Batch time: 03:03pm
Temperature - Air: 760F Concrete: 860F
Truck No: 1219 Ticket No: 88053502
Air Content: 4.6% Unit Weight (pet): NA
Overall Placement Location:
Paving, parking lot, elevation 525.70,526.50,527.30,527.70
Measured
Slump
(inches)
5.5
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 08/30/2007 7 6.00 28.27 83,230 2,940 Unbonded Cap
1 2 09/20/2007 28 6.00 28.27 97,230 3,440 Shear
1 3 09/20/2007 28 6.00 28.27 99,600 3,520 Cone/Split
Average 3,480 *
1 4 10/18/2007 56 6.00 28.27 107,180 3,790 Cone/Shear
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/JC) Page 1 of 5
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 296560
Project No.: 0712786
Date of Service: 08/23/2007
Report Date: 10/22/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 88
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1524
Placement Date: 08/23/2007
Weather Conditions: Clear, warm
Time Sampled: 05:11am Batch time: 04:29am
Temperature - Air: 740F Concrete: 810F
Truck No: 1219 Ticket No: 88053515
Air Content: 4.7% Unit Weight (pet): NA
Overall Placement Location:
Paving, parking lot, elevation 525.70, 526.50, 527.30, 527.70
Measured
Slump
(inches)
5.0
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
2 1 08/30/2007 7 6.00 28.27 79,400 2,810 Unbonded Cap
2 2 09/20/2007 28 6.00 28.27 100,590 3,560 Shear
2 3 09/20/2007 28 6.00 28.27 97,450 3,450 Cone/Split
Average 3,500 *
2 4 10/18/2007 56 6.00 28.27 107,590 3,810 Cone/Shear
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/JC) Page 2 of 5
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 296560
Project No.: 0712786
Date of Service: 08/23/2007
Report Date: 10/22/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 88
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1524
Placement Date: 08/23/2007
Weather Conditions: Clear, warm
Time Sampled: 06:30am Batch time: 05:40am
Temperature - Air: 750F Concrete: 880F
Truck No: 1198 Ticket No: 88053523
Air Content: 5.3% Unit Weight (pcf): NA
Overall Placement Location:
Paving, parking lot, elevation 525.70, 526.50, 527.30, 527.70
Measured
Slump
(inches)
5.0
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
3 1 08/30/2007 7 6.00 28.27 90,320 3,190 Unbonded Cap
3 2 09/20/2007 28 6.00 28.27 119,550 4,230 Cone/Split
3 3 09/20/2007 28 6.00 28.27 108,680 3,840 Cone/Split
Average 4,040
3 4 10/18/2007 56 6.00 28.27 120,250 4,250 Cone/Split
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/JC) Page 3 of 5
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
n01 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 296560
Project No.: 0712786
Date of Service: 08/23/2007
Report Date: 10/22/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 88
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1524
Placement Date: 08/23/2007
Weather Conditions: Clear, warm
Time Sampled: 08:10am Batch time: 07:07am
Temperature - Air: 760F Concrete: 840F
Truck No: 1046 Ticket No: 88053533
Air Content: 5.7% Unit Weight (pet): NA
Overall Placement Location:
Paving, parking lot, elevation 525.70, 526.50, 527.30, 527.70
Measured
Slump
(inches)
5.5
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
4 1 08/30/2007 7 6.00 28.27 96,910 3,430 Unbonded Cap
4 2 09/20/2007 28 6.00 28.27 116,210 4,110 Shear
4 3 09/20/2007 28 6.00 28.27 113,180 4,000 Shear
Average 4,060
4 4 10/18/2007 56 6.00 28.27 118,930 4,210 Cone/Shear
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Lid.
(TMIJC) Page 4 of 5
Rone Engineering
..
Client: Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299092
Project No.: 0712786
Date of Service: 09/18/2007
Report Date: 10/22/2007
Project: Gateway Business Center
Coppell , Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: LMC
Plant: 3
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 2" - 4"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1551
Placement Date: 09/18/2007
Weather Conditions: Sunny
Time Sampled: 02:15pm
Temperature - Air: 870F
Truck No: 1111
Air Content: 3.5%
Overall Placement Location:
Inlet top outer Station 7+00
Batch time: 01 :39pm
Concrete: 880F
Ticket No: 3237018
Unit Weight (pet): NA
Measured
Slump
(inches)
3.0
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 09/25/2007 7 6.00 28.27 99,460 3,520 Shear
1 2 10/16/2007 28 6.00 28.27 107,830 3,810 Cone/Split
1 3 10/16/2007 28 6.00 28.27 104,090 3,680 Cone/Split
Average 3,750
1 4 11/13/2007 56
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/JC) Page 1 of 2
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299208
Project No.: 0712786
Date of Service: 09/19/2007
Report Date: 10/22/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 136
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 830J1521
Placement Date: 09/19/2007
Weather Conditions: Cloudy, windy
Time Sampled: 10:02am Batch time: 09:26am
Temperature - Air: 800F Concrete: 870F
Truck No: 1185 Ticket No: 13697316
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Pier caps, canopy, building 1
Measured
Slump
(inches)
4.5
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
1 1 09/26/2007 7 6.00 28.27 78,400 2,770 Cone/Split
1 2 10/17/2007 28 6.00 28.27 97,880 3,460 Cone/Split
1 3 10/17/2007 28 6.00 28.27 96,290 3,410 Cone/Split
Average 3,430
1 4 11/14/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/JC) Page 1 of 2
Rone Engineering
.:
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 298991
Project No.: 0712786
Date of Service: 09/18/2007
Report Date: 10/22/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 136
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1501
Placement Date: 09/18/2007
Weather Conditions: Clear, calm
Time Sampled: 03:15am Batch time: 02:54am
Temperature - Air: 690F Concrete: 840F
Truck No: 1018 Ticket No: 13697138
Air Content: 1.4% Unit Weight (pet): NA
Overall Placement Location:
Building 1, 2nd floor, slab on deck, grid line 12 to grid line 6
Measured
Slump
(inches)
5.0
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 09/21/2007 3 6.00 28.27 82,220 2,910 Cone/Split
1 2 09/25/2007 7 6.00 28.27 88,650 3,140 Cone/Split
1 3 10/16/2007 28 6.00 28.27 127,090 4,490 Shear
1 4 10/16/2007 28 6.00 28.27 129,690 4,590 Shear
Average 4,540
1 5 11/13/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/JC) Page 1 of 3
Rone Engineering
Client: Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 298991
Project No.: 0712786
Date of Service: 09/18/2007
Report Date: 10/22/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 136
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1501
Placement Date: 09/18/2007
Weather Conditions: Clear, calm
Time Sampled: 05:00am Batch time: 04:35am
Temperature - Air: 670F Concrete: 870F
Truck No: 1188 Ticket No: 13697157
Air Content: 1.4% Unit Weight (pet): NA
Overall Placement Location:
Building 1, 2nd floor, slab on deck, grid line 12 to grid line 6
Measured
Slump
(inches)
5.5
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
2 1 09/21/2007 3 6.00 28.27 74,690 2,640 Cone/Split
2 2 09/25/2007 7 6.00 28.27 110,500 3,910 Cone/Split
2 3 10/16/2007 28 6.00 28.27 138,500 4,900 Cone/Split
2 4 10/16/2007 28 6.00 28.27 134,410 4,750 Cone/Shear
Average 4,830
2 5 11/13/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.