Gateway BP(3.1)-LR071003
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Report of Concrete Compressive Strength Test
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report No.: 299709
Project No.: 0712786
Date of Service: 09/24/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 136
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Measured
Slump
(inches)
7.5
Mix Design 1.0.: 1501
Placement Date: 09/24/2007
Weather Conditions: Clear, Calm
Time Sampled: 08:00am Batch time: 07:28am
Temperature - Air: 700F Concrete: 870F
Truck No: 1190 Ticket No: 13697794
Air Content: 1.7% Unit Weight (pet): NA
Overall Placement Location:
Building 2, 2nd floor slab on deck, grid line D.9 to grid line A.1 , grid line 1.1 to grid line
6
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
-
1 1 09/27/2007 3 6.00 28.27 56,260 1,990 Shear
2 10/01/2007 7 6.00 28.27 69,100 2,440 Cone/Split
3 10/22/2007 28
4 10/22/2007 28
5 11/19/2007 56
Remarks: Water added at site: 15 gallons
LIMITATIONS: The test results presented herein were prepared based upon the speCific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LBILB) Page 1 of 3
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299709
Project No.: 0712786
Date of Service: 09/24/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 136
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 1501
Placement Date: 09/24/2007
Weather Conditions: Clear, Calm
Time Sampled: 10:30am Batch time: 10:00am
Temperature - Air: 790F Concrete: 900F
Truck No: 1032 Ticket No: 13697820
Air Content: 1.0% Unit Weight (pcf): NA
Overall Placement Location:
Building 2, 2nd floor slab on deck, grid line 0.9 to grid line A.1 , grid line 1.1 to grid line
6
Measured
Slump
(inches)
5.5
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
2 1 09/27/2007 3 6.00 28.27 74,130 2,620 Shear
2 2 10/01/2007 7 6.00 28.27 91,830 3,250 Shear
2 3 10/22/2007 28
2 4 10/22/2007 28
2 5 11/19/2007 56
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 2 of 3
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 02:30am Batch time: 01 :24am
Temperature - Air: 820F Concrete: 860F
Truck No: 1378 Ticket No: 13853996
Air Content: 1.3% Unit Weight (pcf): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
4.5
Sample Location:
60' west, 20' south from northwest building corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 08/14/2007 7 6.00 28.27 71,180 2,520 Unbonded Cap
1 2 09/04/2007 28 6.00 28.27 92,120 3,260 Cone/Split
1 3 09/04/2007 28 6.00 28.27 85,250 3,020 Cone/Split
Average 3,140 *
4 10/02/2007 56 6.00 28.27 98,060 3,470 Cone/Shear
* Does not comply with specified strength
Remarks: Dowels were placed prior to concrete placement; discrepancies noted on report #294654 were corrected prior to
concrete placement.
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KWfLB) Page 1 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 03:30am Batch time: 02:23am
Temperature - Air: 810F Concrete: 850F
Truck No: 1281 Ticket No: 13554004
Air Content: 3.4% Unit Weight (pcf): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
5.0
Sample Location:
105' west, 15' south from northwest building corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
2 1 08/14/2007 7 6.00 28.27 75,000 2,650 Unbonded Cap
2 2 09/04/2007 28 6.00 28.27 95,700 3,380 Cone/Split
2 3 09/04/2007 28 6.00 28.27 98,430 3,480 Cone/Split
Average 3,430 *
2 4 10/02/2007 56 6.00 28.27 103,220 3,650 Shear
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance. etc.) or any other feature of similar SUbject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/LB) Page 2 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 04:45am Batch time: 04:11am
Temperature - Air: 830F Concrete: 850F
Truck No: 1351 Ticket No: 13554015
Air Content: 3.3% Unit Weight (pcf): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
5.0
Sample Location:
150' west, 25' south from northwest building corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
3 1 08/14/2007 7 6.00 28.27 77,680 2,750 Unbonded Cap
3 2 09/04/2007 28 6.00 28.27 94,760 3,350 Cone/Split
3 3 09/04/2007 28 6.00 28.27 99,640 3,520 Cone/Split
Average 3,440 *
3 4 10/02/2007 56 6.00 28.27 105,370 3,730 Cone/Shear
* Does not comply with specified strength
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/LB) Page 3 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 07:25am Batch time: 05:32am
Temperature - Air: 830F Concrete: 870F
Truck No: 1278 Ticket No: 13554024
Air Content: 3.2% Unit Weight (pcf): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
4.5
Sample Location:
240' west, 25' south from northwest building corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
4 1 08/14/2007 7 6.00 28.27 64,250 2,270 Unbonded Cap
4 2 09/04/2007 28 6.00 28.27 89,740 3,170 Cone/Split
4 3 09/04/2007 28 6.00 28.27 84,41 0 2,990 Cone/Split
Average 3,080 *
4 4 10/02/2007 56 6.00 28.27 91,800 3,250 Cone/Split
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KWfLB) Page 4 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 09:40am Batch time: 08:47am
Temperature - Air: 850F Concrete: 900F
Truck No: 1393 Ticket No: 13554043
Air Content: 3.2% Unit Weight (pcf): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
6.0
Sample Location:
220' west, 50' south from northwest building corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
5 1 08/14/2007 7 6.00 28.27 65,050 2,300 Unbonded Cap
5 2 09/04/2007 28 6.00 28.27 84,600 2,990 Shear
5 3 09/04/2007 28 6.00 28.27 81,620 2,890 Cone/Split
Average 2,940 *
5 4 10/02/2007 56 6.00 28.27 87,770 3,100 Cone/Split
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/LB) Page 5 of 8
Rone Engineering
..
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 12:20pm Batch time: 11 :11am
Temperature - Air: 890F Concrete: 920F
Truck No: 1248 Ticket No: 13554069
Air Content: 3.3% Unit Weight (pcf): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
6.0
Sample Location:
170' west, 100' south from northwest building corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
6 1 08/14/2007 7 6.00 28.27 47,980 1,700 Unbonded Cap
6 2 09/04/2007 28 6.00 28.27 64,160 2,270 Cone/Split
6 3 09/04/2007 28 6.00 28.27 69,530 2,460 Cone/Split
Average 2,360 *
6 4 10/02/2007 56 6.00 28.27 68,270 2,410 Cone/Split
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/LB) Page 6 of 8
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 294684
Project No.: 0712786
Date of Service: 08/07/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 135
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1 064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23601524
Placement Date: 08/07/2007
Weather Conditions: Clear, warm
Time Sampled: 02:25pm Batch time: 01:17pm
Temperature - Air: 910F Concrete: 930F
Truck No: 1279 Ticket No: 13554092
Air Content: 3.3% Unit Weight (pcf): NA
Overall Placement Location:
Paving on northwest corner of building 1
Measured
Slump
(inches)
6.0
Sample Location:
60' west, 35' south from northwest building corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
7 1 08/14/2007 7 6.00 28.27 77,290 2,730 Unbonded Cap
7 2 09/04/2007 28 6.00 28.27 99,600 3,520 Shear
7 3 09/04/2007 28 6.00 28.27 106,680 3,770 Cone/Split
Average 3,650
7 4 10/02/2007 56 6.00 28.27 102,730 3,630 Cone/Split
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/LB) Page 7 of 8
Rone Engineering
.
Client:
Transwestern Commercial SeNices
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 297387
Project No.: 0712786
Date of Service: 08/30/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 88
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" - 6"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 1524
Placement Date: 08/30/2007
Weather Conditions: Cloudy, calm
Time Sampled: 04:03am Batch time: 03:29am
Temperature - Air: 780F Concrete: 840F
Truck No: 1303 Ticket No: 88053750
Air Content: 4.3% Unit Weight (pet): NA
Overall Placement Location:
Station 525.70-527.10 ridge, Station 525.20-527.40 ridge, page C2.01
Measured
Slump
(inches)
5.0
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
1 1 09/06/2007 7 6.00 28.27 100,820 3,570 Cone/Split
2 09/27/2007 28 6.00 28.27 123,300 4,360 Shear
3 09/27/2007 28 6.00 28.27 123,910 4,380 Cone/Split
Average 4,370
4 10/25/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 1 of 5
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 297387
Project No.: 0712786
Date of Service: 08/30/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 88
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" - 6"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 1524
Placement Date: 08/30/2007
Weather Conditions: Cloudy, calm
Time Sampled: 04:45am Batch time: 04:03am
Temperature - Air: 760F Concrete: 880F
Truck No: 1046 Ticket No: 88053753
Air Content: 4.7% Unit Weight (pet): NA
Overall Placement location:
Station 525.70-527.10 ridge, Station 525.20-527.40 ridge, page C2.01
Measured
Slump
(inches)
5.0
Sample location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
2 1 09/06/2007 7 6.00 28.27 95,080 3,360 Shear
2 2 09/27/2007 28 6.00 28.27 119,380 4,220 Shear
2 3 09/27/2007 28 6.00 28.27 127,090 4,490 Shear
t lerage 4,360
2 4 10/25/2007 56
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 2 of 5
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 297387
Project No.: 0712786
Date of Service: 08/30/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 88
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" - 6"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1524
Placement Date: 08/30/2007
Weather Conditions: Cloudy, calm
Time Sampled: 05:30am Batch time: 05:08am
Temperature - Air: 710F Concrete: 830F
Truck No: 1303 Ticket No: 88053759
Air Content: 4.2% Unit Weight (pcf): NA
Overall Placement Location:
Station 525.70-527.10 ridge, Station 525.20-527.40 ridge, page C2.01
Measured
Slump
(inches)
5.5
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
3 1 09/06/2007 7 6.00 28.27 102,240 3,620 Cone/Split
3 2 09/27/2007 28 6.00 28.27 133,580 4,720 Cone/Split
3 3 09/27/2007 28 6.00 28.27 132,430 4,680 Cone/Shear
Average ',700
3 4 10/25/2007 56
Remarks: Water added at site: 15 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 3 of 5
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 297387
Project No.: 0712786
Date of Service: 08/30/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 88
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" - 6"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1524
Placement Date: 08/30/2007
Weather Conditions: Cloudy, calm
Time Sampled: 06:35am Batch time: 06:00am
Temperature - Air: 720F Concrete: 900F
Truck No: 1348 Ticket No: 13695739
Air Content: 3.7% Unit Weight (pet): NA
Overall Placement Location:
Station 525.70-527.10 ridge, Station 525.20-527.40 ridge, page C2.01
Measured
Slump
(inches)
5.0
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
4 1 09/06/2007 7 6.00 28.27 85,190 3,010 Cone/Split
4 2 09/27/2007 28 6.00 28.27 105,280 3,720 Cone/Split
4 3 09/27/2007 28 6.00 28.27 105,380 3,730 Cone/Split
Average ,),730
4 4 10/25/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/LB) Page 4 of 5
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Client:
Report No.: 299092
Project No.: 0712786
Date of Service: 09/18/2007
Report Date: 10/03/2007
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX ~
Project: Gatewa usiness Center
Copp , Texas
Services: Obt samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
sa pies back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: LMC
Plant: 3
Specification Req u i rements
Strength: 3,600 psi @ 28 days
Slump (in.): 2" - 4"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 1551
Placement Date: 09/18/2007
Weather Conditions: Sunny
Time Sampled: 02:15pm
Temperature - Air: 870F
Truck No: 1111
Air Content: 3.5%
Overall Placement Location:
Inlet top outer Station 7+00
Sample Location:
Same as above
REPORT OF TESTS
Batch time: 01 :39pm
Concrete: 880F
Ticket No: 37018
Unit W. t( f): NA
Measured
Slump
(inches)
3.0
~;}~
Cylinder
Marked Date
Set No. Tested
1 1 09/25/2007
2 10/16/2007
3 10/16/2007
4 11/13/2007 56
Diameter
(in)
6.00
Remarks: Water added at site: 10 gallons
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
99,460
Area
(in2)
28.27
Ig/"tflJ~"
Fracture
Type
Shear
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/LB) Page 1 of 2
Rone Engineering
.
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299208
Project No.: 0712786
Date of Service: 09/19/2007
Report Date: 10/03/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 136
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1 064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 830J1521
Placement Date: 09/19/2007
Weather Conditions: Cloudy, windy
Time Sampled: 10:02am Batch time: 09:26am
Temperature - Air: 800F Concrete: 870F
Truck No: 1185 Ticket No: 13697316
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Pier caps, canopy, building 1
Measured
Slump
(inches)
4.5
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
78,400
Cylinder
Marked Date
Set No. Tested
1 1 09/26/2007
2 10/17/2007
3 10/17/2007
1 4 11/14/2007
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Compressive
Strength
(psi)
2,770
Fracture
Type
Cone/Split
Area
(in')
28.27
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TMlLB) Page 1 of 2