Duke Lesley 2A-LR071031
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300525
Project No.: 0712932
Date of Service: 10/01/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): NA
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7751 PW
Placement Date: 10/01/2007
Weather Conditions: Clear
Time Sampled: 11 :OOam
Temperature - Air: 890F
Truck No: 104
Air Content: NA
Overall Placement Location:
Building piers U8.2-6.2; 3.2; 2.5; 1.4; 0.9
Batch time: 10:39am
Concrete: 940F
Ticket No: 14205
Unit Weight (pcf): NA
Measured
Slump
(inches)
6.5
Sample Location:
Pier U7.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/08/2007 7 6.00 28.27 98,060 3,470 Cone/Shear
1 2 10/08/2007 7 6.00 28.27 81,710 2,890 Cone/Split
Average 3,180
1 3 10/29/2007 28 6.00 28.27 124,740 4,410 Cone/Split
1 4 10/29/2007 28 6.00 28.27 131,860 4,660 Shear
Average 4,540
5 11/26/2007 56
Technician: Chris Harbour Rone Engineering
See Report 300524 for technician time~ ~
Report Distribution: ~ ~
Orig: Duke Construction. LP (Dallas, TX) Alln: Mr. Paul Byrne .' ~
(1-ec copy)
1-cc Potter Concrete Alln: Mr. Ryan Skelly K. Scott Watson, AET
1-cc City of Coppell Alln: Mr. Lee Stone Project Manager
1-cc City of Coppell Alln: Mr. Larry Davis
LIMITATIONS: The test results presented herein were prepared based upon the specifiC samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 1 of 1
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300431
Project No.: 0712932
Date of Service: 09/29/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): NA
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7751 PW
Placement Date: 09/29/2007
Weather Conditions: Clear
Time Sampled: 11 :OOam
Temperature - Air: 780F
Truck No: 137
Air Content: NA
Overall Placement Location:
Building piers U10.2-8.8, 16.8
Batch time: 09:55am
Concrete: 860F
Ticket No: 14123
Unit Weight (pcf): NA
Measured
Slump
(inches)
7.0
Sample Location:
Building pier U10.2
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/06/2007 7 6.00 28.27 90,050 3,180 Shear
1 2 10/06/2007 7 6.00 28.27 85,130 3,010 Cone/Split
Average 3,100
3 10/27/2007 28 6.00 28.27 121,100 4,280 Cone/Shear
4 10/27/2007 28 6.00 28.27 113,800 4,020 Cone/Split
Average 4,150
1 5 11/24/2007 56
Technician: Chris Harbour
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Alln: Mr. Paul Byrne
(1-ec copy)
1-cc Poller Concrete Alln: Mr. Ryan Skelly
1-cc City of Coppell Alln: Mr. Lee Stone
1-cc City of Coppell Alln: Mr. Larry Davis
Rone Engineering
p~ ;:::>
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation In quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 1 of 1
Rone En2==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300245
Project No.: 0712932
Date of Service: 09/28/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): NA
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 77551 PW
Placement Date: 09/28/2007
Weather Conditions: Clear
Time Sampled: 10:25am
Temperature - Air: 850F
Truck No: 101
Air Content: NA
Overall Placement Location:
Building piers U14.2-13.2, U12.2-10.8
Batch time: 09:38am
Concrete: 890F
Ticket No: 14083
Unit Weight (pcf): NA
Measured
Slump
(inches)
6.5
Sample Location:
Building pier U13.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/05/2007 7 6.00 28.27 92,840 3,280 Shear
1 2 10/26/2007 28 6.00 28.27 122,710 4,340 Cone/Split
1 3 10/26/2007 28 6.00 28.27 110,250 3,900 Cone/Split
Average 4,120
4 11/23/2007 56
5 11/23/2007 56
Technician: Chris Harbour Rone Engineering
See Report 300244 for technician time~~
~~~: . .. ~
Orig: Duke Construction, LP (Dallas, TX) Altn: Mr. Paul Byrne .. ~
(1-ec copy) -
1-cc Polter Concrete Altn: Mr. Ryan Skelly K. Scott Watson AET
1-cc City of Coppell Altn: Mr. Lee Stone p . t M '
1-cc City of Coppell Attn: Mr. Larry Davis rOJec anager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 1 of 1
Rone En~==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300539
Project No.: 0712932
Date of Service: 10/01/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 10/01/2007
Weather Conditions: Cloudy, calm
Time Sampled: 03:50am Batch time: 03:39am
Temperature - Air: 760F Concrete: 920F
Truck No: 143 Ticket No: 14139
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Slab - G,H,J/11-21
Measured
Slump
(inches)
5.0
Sample Location:
G,H,J/11-11.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/08/2007 7 6.00 28.27 109,820 3,880 Shear
1 2 10/29/2007 28 6.00 28.27 136,250 4,820 Shear
1 3 10/29/2007 28 6.00 28.27 145,850 5,160 Cone/Split
Average 4,990
1 4 11/26/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 1 of 10
Rone Eni=:=
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300539
Project No.: 0712932
Date of Service: 10/01/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 10/01/2007
Weather Conditions: Cloudy, calm
Time Sampled: 04:45am Batch time: 04:34am
Temperature - Air: 760F Concrete: 920F
Truck No: 143 Ticket No: 14148
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Slab - G,H,J/11-21
Measured
Slump
(inches)
6.0
Sam pie Location:
G,H,J/11.8-12.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
2 1 10/08/2007 7 6.00 28.27 107,380 3,800 Shear
2 2 10/29/2007 28 6.00 28.27 134,580 4,760 Cone/Shear
2 3 10/29/2007 28 6.00 28.27 137,920 4,880 Cone/Split
Average 4,820
2 4 11/26/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 2 of 10
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300539
Project No.: 0712932
Date of Service: 10/01/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 10/01/2007
Weather Conditions: Cloudy, calm
Time Sampled: 06:00am Batch time: 05:44am
Temperature - Air: 780F Concrete: 900F
Truck No: 143 Ticket No: 14159
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Slab - G,H,J/11-21
Measured
Slump
(inches)
6.0
Sample Location:
G,H,J/12.8-13.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
3 1 10/08/2007 7 6.00 28.27 119,800 4,240 Cone/Split
3 2 10/29/2007 28 6.00 28.27 153,590 5,430 Cone/Split
3 3 10/29/2007 28 6.00 28.27 150,540 5,320 Cone/Split
Average 5,380
3 4 11/26/2007 56
liMITATiONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 3 of 10
Rone En2==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300539
Project No.: 0712932
Date of Service: 10/01/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point We
Coppell, Texas
Services: Obtain samples of fresh concrete t the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for uring and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 10/01/2007
Weather Conditions: Cloudy, calm
Time Sampled: 06:55am Batch time: 06:41am
Temperature - Air: nOF Concrete: 920F
Truck No: 125 Ticket No: 14169
Air Content: NA Unit Weight (pct): NA
Overall Placement Location:
Slab - G,H,J/11-21
Measured
Slump
(inches)
5.0
Sample Location:
G,H,J/13.8-14.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
4 1 10/08/2007 7 6.00 28.27 116,180 4,110 Shear
4 2 10/29/2007 28 6.00 28.27 143,970 5,090 Cone/Split
4 3 10/29/2007 28 6.00 28.27 146,480 5,180 Cone/Split
Average 5,140
4 4 11/26/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 4 of 10
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Com pressive Strength Test
Report No.: 300539
Project No.: 0712932
Date of Service: 10/01/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 10/01/2007
Weather Conditions: Sunny
Time Sampled: 07:35am
Temperature - Air: 780F
Truck No: 137
Air Content: NA
Overall Placement Location:
Slab - G,H,J/11-21
Batch time: 07:29am
Concrete: 920F
Ticket No: 14176
Unit Weight (pet): NA
Measured
Slump
(inches)
6.0
Sample Location:
G,H,J/14.8-15.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
5 1 10/08/2007 7 6.00 28.27 106,610 3,770 Cone/Split
5 2 10/29/2007 28 6.00 28.27 142,820 5,050 Shear
5 3 10/29/2007 28 6.00 28.27 139,490 4,930 Cone/Split
Average 4,990
5 4 11/26/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 5 of 10
Rone En2~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300539
Project No.: 0712932
Date of Service: 10/01/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 10/01/2007
Weather Conditions: Sunny
Time Sampled: 09:20am
Temperature - Air: 800F
Truck No: 117
Air Content: NA
Overall Placement Location:
Slab - G,H,J/11-21
Batch time: 09:05am
Concrete: 920F
Ticket No: 14189
Unit Weight (pcf): NA
Measured
Slump
(inches)
3.0
Sample Location:
G,H,J/15.8-16.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
6 1 10/08/2007 7 6.00 28.27 118,670 4,200 Cone/Split
6 2 10/29/2007 28 6.00 28.27 160,550 5,680 Cone/Split
6 3 10/29/2007 28 6.00 28.27 153,330 5,420 Cone/Split
Average 5,550
6 4 11/26/2007 56
L1MITA nONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering SelVices, Ltd.
(LB/ED) Page 6 of 10
Rone En2==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300539
Project No.: 0712932
Date of Service: 10/01/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 10/01/2007
Weather Conditions: Sunny
Time Sampled: 10:30am
Temperature - Air: 820F
Truck No: 117
Air Content: NA
Overall Placement Location:
Slab - G,H,J/11-21
Batch time: 10: 15am
Concrete: 920F
Ticket No: 14201
Unit Weight (pct): NA
Measured
Slump
(inches)
4.0
Sample Location:
G,H,J/16.8-17.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
7 1 10/08/2007 7 6.00 28.27 112,570 3,980 Cone/Split
7 2 10/29/2007 28 6.00 28.27 148,530 5,250 Cone/Split
7 3 10/29/2007 28 6.00 28.27 148,940 5,270 Shear
Average 5,260
7 4 11/26/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 7 of 10
Rone En~~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300539
Project No.: 0712932
Date of Service: 10/01/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 10/01/2007
Weather Conditions: Sunny
Time Sampled: 11 :30am
Temperature - Air: 800F
Truck No: 125
Air Content: NA
Overall Placement Location:
Slab - G,H,J/11-21
Batch time: 11: 15am
Concrete: 940F
Ticket No: 14212
Unit Weight (pct): NA
Measured
Slump
(inches)
6.0
Sample Location:
G,H,J/17.8-18.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (In) (in') (Ibs) (psi) Type
8 1 10/08/2007 7 6.00 28.27 115,120 4,070 Cone/Split
8 2 10/29/2007 28 6.00 28.27 147,320 5,210 Cone/Split
8 3 10/29/2007 28 6.00 28.27 145,800 5,160 Shear
Average 5,180
8 4 11/26/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 8 of 10
Rone En~~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 15241
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 18144
Corporate Phone: (214) 630-9145
Report of Concrete Compressive Strength Test
Report No.: 300539
Project No.: 0712932
Date of Service: 10/01/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 10/01/2007
Weather Conditions: Sunny
Time Sampled: 12:15pm
Temperature - Air: 880F
Truck No: 135
Air Content: NA
Overall Placement Location:
Slab - G,H,J/11-21
Batch time: 12:09pm
Concrete: 940F
Ticket No: 14222
Unit Weight (pcf): NA
Measured
Slump
(inches)
5.0
Sample Location:
G,H,J/18.8-19.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
9 1 10/08/2007 7 6.00 28.27 113,470 4,010 Cone/Split
9 2 10/29/2007 28 6.00 28.27 144,830 5,120 Shear
9 3 10/29/2007 28 6.00 28.27 141,070 4,990 Cone/Split
Average 5,060
9 4 11/26/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 9 of 10
Rone En~==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300539
Project No.: 0712932
Date of Service: 10/01/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 10/01/2007
Weather Conditions: Sunny
Time Sampled: 01 :OOpm
Temperature - Air: 880F
Truck No: 144
Air Content: NA
Overall Placement Location:
Slab - G,H,J/11-21
Batch time: 12:39pm
Concrete: 940F
Ticket No: 14228
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
G,H,J/19.8-21
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
10 1 10/08/2007 7 6.00 28.27 120,640 4,270 Shear
10 2 10/29/2007 28 6.00 28.27 154,170 5,450 Shear
10 3 10/29/2007 28 6.00 28.27 155,610 5,500 Cone/Split
Average 5,480
10 4 11/26/2007 56
Started: 02:30am Finished: 02:00pm
Technician: Denny Harris
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne
(1-ec copy)
1-cc Potter Concrete Attn: Mr. Ryan Skelly
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Attn: Mr. Larry Davis
Rone Engineering
P-~
~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 10 of 10
Rone En~~
Client: Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300265
Project No.: 0712932
Date of Service: 09/28/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 03:35am Batch time: 03:24am
Temperature - Air: 720F Concrete: 900F
Truck No: 112 Ticket No: 14023
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Building pad slab on grade A-C/21-29.9
Measured
Slump
(inches)
5.0
Sample Location:
Grid line C/21-21.4
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/05/2007 7 6.00 28.27 123,790 4,380 Cone/Split
1 2 10/26/2007 28 6.00 28.27 150,930 5,340 Cone/Split
1 3 10/26/2007 28 6.00 28.27 151,310 5,350 Shear
Average 5,340
4 11/23/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 1 of9
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, 8te 600, Houston, TX 77040
4421 Freidrich, 8te 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300265
Project No.: 0712932
Date of Service: 09/28/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 09/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 04:10am Batch time: 03:51am
Temperature - Air: 720F Concrete: 900F
Truck No: 112 Ticket No: 14029
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Building pad slab on grade A-C/21-29.9
Measured
Slump
(inches)
5.0
Sample Location:
Grid line 8/22.5
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
2 1 10/05/2007 7 6.00 28.27 116,000 4,100 Cone/Split
2 2 10/26/2007 28 6.00 28.27 151,720 5,370 Shear
2 3 10/26/2007 28 6.00 28.27 152,230 5,380 Cone/Split
Average 5,380
2 4 11/23/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 2 of9
Rone Eni~
Client: Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300265
Project No.: 0712932
Date of Service: 09/28/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 04:45am Batch time: 04:20am
Temperature - Air: 690F Concrete: 900F
Truck No: 112 Ticket No: 14035
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Building pad slab on grade A-C/21-29.9
Measured
Slump
(inches)
5.5
Sample Location:
Grid line A/23-23.2
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
3 1 10/05/2007 7 6.00 28.27 116,070 4,110 Cone/Split
3 2 10/26/2007 28 6.00 28.27 145,500 5,150 Cone/Split
3 3 10/26/2007 28 6,00 28,27 147,020 5,200 Cone/Shear
Average 5,170
3 4 11/23/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 3 of 9
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300265
Project No.: 0712932
Date of Service: 09/28/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the pia ement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing an esting in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 06:12am Batch time:
Temperature - Air: 690F Concrete: 900F
Truck No: 142 Ticket No: 14050
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Building pad slab on grade A-C/21-29.9
Measured
Slump
(inches)
6.0
Sample Location:
Grid line 24-24.7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
4 1 10/05/2007 7 6.00 28.27 118,680 4,200 Cone/Split
4 2 10/26/2007 28 6.00 28.27 147,100 5,200 Cone/Split
4 3 10/26/2007 28 6.00 28.27 149,120 5,270 Shear
Average 5,240
4 4 11/23/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd.
(CH/ED) Page 4 of 9
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300265
Project No.: 0712932
Date of Service: 09/28/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 07:00am Batch time: 06:42am
Temperature - Air: 690F Concrete: 900F
Truck No: 139 Ticket No: 14059
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Building pad slab on grade A-C/21-29.9
Measured
Slump
(inches)
5.5
Sample Location:
Grid line B/25-25.5
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
5 1 10105/2007 7 6.00 28.27 116,940 4,140 Cone/Split
5 2 10/26/2007 28 6.00 28.27 147,920 5,230 Cone/Split
5 3 10/26/2007 28 6.00 28.27 148,650 5,260 Cone/Split
Average 5,240
5 4 11/23/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 5 of 9
Rone En2==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300265
Project No.: 0712932
Date of Service: 09/28/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West /
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 09/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 08:45am Batch time: 08:34am
Temperature - Air: 750F Concrete: 900F
Truck No: 142 Ticket No: 14071
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Building pad slab on grade A-C/21-29.9
Measured
Slump
(inches)
4.5
Sample Location:
Grid line 8/26-26.7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
6 1 10/05/2007 7 6.00 28.27 119,990 4,240 Shear
6 2 10/26/2007 28 6.00 28.27 148,100 5,240 Cone/Split
6 3 10/26/2007 28 6.00 28.27 157,210 5,560 Cone/Split
Average 5,400
6 4 11/23/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 6 of 9
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300265
Project No.: 0712932
Date of Service: 09/28/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 09:35am Batch time: 09:15am
Temperature - Air: 770F Concrete: 900F
Truck No: 103 Ticket No: 14079
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Building pad slab on grade A-C/21-29.9
Measured
Slump
(inches)
3.0
Sample Location:
Grid line B/27-27.5
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
7 1 10/05/2007 7 6.00 28.27 124,360 4,400 Cone/Split
7 2 10/26/2007 28 6.00 28.27 157,960 5,590 Cone/Split
7 3 10/26/2007 28 6.00 28.27 151,870 5,370 Cone/Split
Average 5,480
7 4 11/23/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 7 of 9
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300265
Project No.: 0712932
Date of Service: 09/28/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT OAT A
Mix Design 1.0.: 9349
Placement Date: 09/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 11 :05am Batch time: 10:45am
Temperature - Air: 800F Concrete: 900F
Truck No: 126 Ticket No: 14095
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Building pad slab on grade A-C/21-29.9
Measured
Slump
(inches)
5.0
Sample Location:
Grid line C/28-28.7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
8 1 10/05/2007 7 6.00 28.27 130,180 4,600 Shear
8 2 10/26/2007 28 6.00 28.27 152,900 5,410 Shear
8 3 10/26/2007 28 6.00 28.27 158,660 5,610 Cone/Split
Average 5,510
8 4 11/23/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 8 of 9
Rone En~==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300265
Project No.: 0712932
Date of Service: 09/28/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/28/2007
Weather Conditions: Cloudy, calm
Time Sampled: 12:30pm Batch time: 12:15pm
Temperature - Air: 780F Concrete: 900F
Truck No: 101 Ticket No: 14103
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Building pad slab on grade A-C/21-29.9
Measured
Slump
(inches)
5.0
Sample Location:
Grid line C/29.9-29.3
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
9 1 10/05/2007 7 6.00 28.27 104,220 3,690 Shear
9 2 10/26/2007 28 6.00 28.27 134,830 4,770 Cone/Split
9 3 10/26/2007 28 6.00 28.27 128,640 4,550 Shear
Average 4,660
9 4 11/23/2007 56
Technician: David Best Started: 02:30am
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Altn: Mr. Paul Byrne
(1-ec copy)
1-cc Polter Concrete Altn: Mr. Ryan Skelly
1-cc City of Coppell Altn: Mr. Lee Stone
1-cc City of Coppell Altn: Mr. Larry Davis
Finished: 04:30pm Rone Engineering
p~~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 9 of 9
Rone En~~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 302575
Project No.: 0712932
Date of Service: 10/20/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: On site
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 10/20/2007
Weather Conditions: Clear, windy
Time Sampled: 04:45am Batch time:
Temperature - Air: 580F Concrete: 670F
Truck No: 110 Ticket No:
Air Content: 1.2% Unit Weight (pet): NA
Overall Placement Location:
Tilt wall panels, P124-P128, P131-P146
Measured
Slump
(inches)
5.0
Sample Location:
P128, top section
REPORT OF TESTS
Cylinder
Marked Date
Set No. Tested
1 1 10/27/2007
1 2 11/03/2007
1 3 11/17/2007
1 4 11/17/2007
Age
(days)
7
Diameter
(in)
6.00
14
28
28
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
111,910
Compressive
Strength
(psi)
3,960
Fracture
Type
Cone/Split
Area
(in2)
28.27
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reprodUCed except in full without the written approval of Rone Engineering Services, Ltd.
(TMIED) Page 1 of"
Rone Engineering
..
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 302575
Project No.: 0712932
Date of Service: 10/20/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: On site
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 10/20/2007
Weather Conditions: Clear, windy
Time Sampled: 07:15am Batch time:
Temperature - Air: 570F Concrete: 700F
Truck No: 131 Ticket No:
Air Content: 1.3% Unit Weight (pet): NA
Overall Placement Location:
Tilt wall panels, P124-P128, P131-P146
Measured
Slump
(inches)
6.0
Sample Location:
P131, middle section
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
2 1 10/27/2007 7 6.00 28.27 99,830 3,530 Shear
2 2 11/03/2007 14
2 3 11/17/2007 28
2 4 11/17/2007 28
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TMIED) Page 2 of 4
Rone En~==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 302575
Project No.: 0712932
Date of Service: 10/20/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: On site
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 10/20/2007
Weather Conditions: Clear, windy
Time Sampled: 09: 15am Batch time:
Temperature - Air: 680F Concrete: 700F
Truck No: 110 Ticket No:
Air Content: 1.3% Unit Weight (pet): NA
Overall Placement Location:
Tilt wall panels, P124-P128, P131-P146
Measured
Slump
(inches)
5.5
Sample Location:
P145
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
3 1 10/27/2007 7 6.00 28.27 102,730 3,630 Shear
3 2 11/03/2007 14
3 3 11/17/2007 28
3 4 11/17/2007 28
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TMIED) Page 3 of 4
Rone En~~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 302575
Project No.: 0712932
Date of Service: 10/20/2007
Report Date: 10/31/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: On site
Specification Requirements
Strength: 4,000 psi @28 days
Slump (in.): 4" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 10/20/2007
Weather Conditions: Clear, windy
Time Sampled: 10:15am Batch time:
Temperature - Air: 710F Concrete: 750F
Truck No: 110 Ticket No:
Air Content: 1.1 % Unit Weight (pet): NA
Overall Placement Location:
Tilt wall panels, P124-P128, P131-P146
Measured
Slump
(inches)
6.0
Sample Location:
P143, top section
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
104,250
Cylinder
Marked Date
Set No. Tested
4 1 10/27/2007
4 2 11/03/2007
4 3 11/17/2007
4 4 11/17/2007
Age
(days)
7
Diameter
(in)
6.00
14
28
28
Area
(in2)
28.27
Compressive
Strength
(psi)
3,690
Fracture
Type
Cone/Split
Started: 04:00am Finished: 11:15am
Technician: Javier Martinez
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne
(1-ec copy)
1-cc Potter Concrete Attn: Mr. Ryan Skelly
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Attn: Mr. Larry Davis
Rone Engineering
p~
~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TMIED) Page 4 of ..