Duke Lesley 2A-LR071026
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300103
Project No.: 0712932
Date of Service: 09/27/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placementlocalions, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): NA
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7751 PW
Placement Date: 09/27/2007
Weather Conditions: Clear
Time Sampled: 09:40am
Temperature - Air: 740F
Truck No: 132
Air Content: NA
Overall Placement Location:
Building piers U19.8 - 17.2, U16.2-14.8
Batch time: 08:53am
Concrete: 860F
Ticket No: 13970
Unit Weight (pet): NA
Measured
Slump
(inches)
7.0
Sample Location:
Building pier U9.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/04/2007 7 6.00 28.27 82,160 2,910 Cone/Split
1 2 10/04/2007 7 6.00 28.27 81,720 2,890 Cone/Split
Average 2,900
1 3 10/25/2007 28 6.00 28.27 103,200 3,650 Cone/Split
1 4 10/25/2007 28 6.00 28.27 108,700 3,840 Cone/Split
Average 3,750
1 5 11/22/2007 56
Technician: Chris Harbour Rone Engineering
See Report 300102 for technician lime~~
~~~: ~
Ori9: Duke Construction. LP (Dallas, TX) Attn: Mr. Paul Byrne ... ~
(1-ec copy) -
1-cc P~tler Concrete Alln: Mr. Ryan Skelly K. Scott Watson, AET
1-cc City of Coppell Alln: Mr. Lee Stone. Project Manager
1-cc City of Coppell Attn: Mr. Larry DaVIS
LIMIT A nONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd.
(CH/ED) Page 1 of 1
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300123
Project No.: 0712932
Date of Service: 09/27/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1 064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/27/2007
Weather Conditions: Cloudy, calm
Time Sampled: 03:30am Batch time: 03:19am
Temperature - Air: 710F Concrete: 840F
Truck No: 131 Ticket No: 13911
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Building pad, slab on grade J-U21-30
Measured
Slump
(inches)
6.0
Sample Location:
U21-21.B
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/04/2007 7 6.00 28.27 112,100 3,960 Cone/Split
1 2 10/25/2007 28 6.00 28.27 152,520 5,390 Cone/Split
1 3 10/25/2007 28 6.00 28.27 150,170 5,310 Shear
Average 5,350
1 4 11/22/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 1 of 10
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300123
Project No.: 0712932
Date of Service: 09/27/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 09/27/2007
Weather Conditions: Cloudy, calm
Time Sampled: 04:20am Batch time: 04:05am
Temperature - Air: 710F Concrete: 860F
Truck No: 141 Ticket No: 13919
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Building pad, slab on grade J-U21-30
Measured
Slump
(inches)
5.5
Sample Location:
K/22-22.3
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
2 1 10/04/2007 7 6.00 28.27 112,600 3,980 Cone/Split
2 2 10/25/2007 28 6.00 28.27 136,880 4,840 Cone/Shear
2 3 10/25/2007 28 6.00 28.27 135,270 4,780 Cone/Split
Average 4,810
2 4 11/22/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 2 of 10
Rone En2==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300123
Project No.: 0712932
Date of Service: 09/27/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 09/27/2007
Weather Conditions: Cloudy, calm
Time Sampled: 05:10am Batch time: 04:54am
Temperature - Air: 700F Concrete: 830F
Truck No: 141 Ticket No: 13929
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Building pad, slab on grade J-U21-30
Measured
Slump
(inches)
5.0
Sample Location:
1<123-23.7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
3 1 10/04/2007 7 6.00 28.27 116,950 4,140 Cone/Split
3 2 10/25/2007 28 6.00 28.27 147,280 5,210 Cone/Split
3 3 10/25/2007 28 6.00 28.27 151,200 5,350 Cone/Shear
Average 5,280
3 4 11/22/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 3 of 10
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300123
Project No.: 0712932
Date of Service: 09/27/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (0/0): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 09/27/2007
Weather Conditions: Cloudy, calm
Time Sampled: 05:50am Batch time: 05:31am
Temperature - Air: 700F Concrete: 860F
Truck No: 131 Ticket No: 13937
Air Content: NA Unit Weight (pct): NA
Overall Placement Location:
Building pad, slab on grade J-U21-30
Measured
Slump
(inches)
5.0
Sample Location:
J/24-24.3
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
4 1 10/04/2007 7 6.00 28.27 114,780 4,060 Cone/Split
4 2 10/25/2007 28 6.00 28.27 141,030 4,990 Cone/Split
4 3 10/25/2007 28 6.00 28.27 147,740 5,230 Cone/Split
Average 5,110
4 4 11/22/2007 56
liMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 4 of 10
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300123
Project No.: 0712932
Date of Service: 09/27/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 09/27/2007
Weather Conditions: Cloudy, calm
Time Sampled: 06:45am Batch time: 06:34am
Temperature - Air: 710F Concrete: 900F
Truck No: 117 Ticket No: 13950
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Building pad, slab on grade J-U21-30
Measured
Slump
(inches)
5.5
Sample Location:
U25-25.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
5 1 10/04/2007 7 6.00 28.27 115,470 4,080 Shear
5 2 10/25/2007 28 6.00 28.27 147,580 5,220 Cone/Split
5 3 10/25/2007 28 6.00 28.27 146,150 5,170 Cone/Shear
Average 5,190
5 4 11/22/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 5 of 10
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300123
Project No.: 0712932
Date of Service: 09/27/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/27/2007
Weather Conditions: Clear, calm
Time Sampled: 08:10am Batch time: 08:00am
Temperature - Air: 750F Concrete: 890F
Truck No: 104 Ticket No: 13959
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Building pad, slab on grade J-U21-30
Measured
Slump
(inches)
5.0
Sample Location:
K/26-26.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
6 1 10/04/2007 7 6.00 28.27 114,610 4,050 Cone/Split
6 2 10/25/2007 28 6.00 28.27 140,120 4,960 Cone/Split
6 3 10/25/2007 28 6.00 28.27 137,440 4,860 Cone/Split
Average 4,910
6 4 11/22/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 6 of 10
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300123
Project No.: 0712932
Date of Service: 09/27/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placementlocalions, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 09/27/2007
Weather Conditions: Clear, calm
Time Sampled: 09:30am Batch time: 09:12am
Temperature - Air: 770F Concrete: 900F
Truck No: 107 Ticket No: 13974
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Building pad, slab on grade J-L/21-30
Measured
Slump
(inches)
5.0
Sample Location:
L/27-27.0
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
7 1 10/04/2007 7 6.00 28.27 91,150 3,220 Shear
7 2 10/25/2007 28 6.00 28.27 141,420 5,000 Shear
7 3 10/25/2007 28 6.00 28.27 140,160 4,960 Cone/Split
Average 4,980
7 4 11/22/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 7 of 10
Rone En~==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300123
Project No.: 0712932
Date of Service: 09/27/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/27/2007
Weather Conditions: Clear, calm
Time Sampled: 10:00am Batch time: 09:46am
Temperature - Air: 730F Concrete: 880F
Truck No: 131 Ticket No: 13981
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Building pad. slab on grade J-U21-30
Measured
Slump
(inches)
5.5
Sample Location:
J/28-28.4
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
8 1 10/04/2007 7 6.00 28.27 91 ,760 3,250 Cone/Split
8 2 10/25/2007 28 6.00 28.27 123,120 4,350 Cone/Split
8 3 10/25/2007 28 6.00 28.27 119,620 4,230 Cone/Split
Average 4,290
8 4 11/22/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 8 of 10
Rone En~==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300123
Project No.: 0712932
Date of Service: 09/27/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/27/2007
Weather Conditions: Clear, calm
Time Sampled: 11:10am Batch time: 10:45am
Temperature - Air: 860F Concrete: 900F
Truck No: 104 Ticket No: 13991
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Building pad, slab on grade J-U21-30
Measured
Slump
(inches)
6.0
Sample Location:
K/29-29.5
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
9 1 10/04/2007 7 6.00 28.27 106,810 3,780 Cone/Split
9 2 10/25/2007 28 6.00 28.27 136,110 4,810 Cone/Split
9 3 10/25/2007 28 6.00 28.27 137,230 4,850 Cone/Split
Average 4,830
9 4 11/22/2007 56
LIMITATION S: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd.
(LB/ED) Page 9 of 10
Rone En2==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 300123
Project No.: 0712932
Date of Service: 09/27/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 1
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/27/2007
Weather Conditions: Clear, calm
Time Sampled: 12:00pm Batch time: 11:45am
Temperature - Air: 860F Concrete: 870F
Truck No: 107 Ticket No: 14002
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Building pad, slab on grade J-U21-30
Measured
Slump
(inches)
5.5
Sample Location:
K/30-30.5
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
10 1 10/04/2007 7 6.00 28.27 107,240 3,790 Cone/Split
10 2 10/25/2007 28 6.00 28.27 135.750 4,800 Cone/Split
10 3 10/25/2007 28 6.00 28.27 138,660 4,900 Cone/Split
Average 4,850
10 4 11/22/2007 56
Technician: David Best
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Alln: Mr. Paul Byrne
(1-ec copy)
1-cc Potter Concrete Alln: Mr. Ryan Skelly
1-cc City of Coppell Alln: Mr. Lee Stone
1-cc City of Coppell Alln: Mr. Larry Davis
Started: 02:30am Finished: 04:30pm
Rone Engineering
p~
~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 10 of 10
Rone En2=:=
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299967
Project No.: 0712932
Date of Service: 09/26/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/26/2007
Weather Conditions: Cloudy, calm
Time Sampled: 03:30am Batch time: 03:18am
Temperature - Air: 700F Concrete: 820F
Truck No: 129 Ticket No: 7771
Air Content: 0.5% Unit Weight (pcf): NA
Overall Placement Location:
Slab on grade, grid lines E-G/11-21 (west)
Measured
Slump
(inches)
5.0
Sample Location:
Grid line E/11.5
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/03/2007 7 6.00 28.27 85,160 3,010 Cone/Split
1 2 10/24/2007 28 6.00 28.27 117,770 4,170 Cone/Shear
1 3 10/24/2007 28 6.00 28.27 124,390 4,400 Cone/Split
Average 4,280
1 4 11/21/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 1 of 9
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299967
Project No.: 0712932
Date of Service: 09/26/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 09/26/2007
Weather Conditions: Cloudy, calm
Time Sampled: 04:15am Batch time: 03:59am
Temperature - Air: 710F Concrete: 800F
Truck No: 107 Ticket No: 7779
Air Content: 0.4% Unit Weight (pet): NA
Overall Placement Location:
Slab on grade, grid lines E-G/11-21 (west)
Measured
Slump
(inches)
5.0
Sample Location:
Grid line E.8/12.2
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
2 1 10/03/2007 7 6.00 28.27 71,650 2,530 Cone/Shear
2 2 10/24/2007 28 6.00 28.27 96,510 3,410 Shear
2 3 10/24/2007 28 6.00 28.27 91,330 3,230 Shear
Average 3,320 *
2 4 11/21/2007 56
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 2 of 9
Rone En2~
Client: Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299967
Project No.: 0712932
Date of Service: 09/26/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 09/26/2007
Weather Conditions: Cloudy, calm
Time Sampled: 04:40am Batch time: 04:36am
Temperature - Air: 740F Concrete: 820F
Truck No: 107 Ticket No: 7786
Air Content: 0.6% Unit Weight (pcf): NA
Overall Placement Location:
Slab on grade, grid lines E-G/11-21 (west)
Measured
Slump
(inches)
5.5
Sample Location:
Grid line F.2/13.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
3 1 10/03/2007 7 6.00 28.27 94,740 3,350 Cone/Split
3 2 10/24/2007 28 6.00 28.27 121,630 4,300 Shear
3 3 10/24/2007 28 6.00 28.27 126,850 4,490 Cone/Split
Average 4,390
3 4 11/21/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 3 of 9
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299967
Project No.: 0712932
Date of Service: 09/26/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Req u irements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/26/2007
Weather Conditions: Cloudy, calm
Time Sampled: 06:00am Batch time: 05:33am
Temperature - Air: 750F Concrete: 890F
Truck No: 141 Ticket No: 7798
Air Content: 0.6% Unit Weight (pcf): NA
Overall Placement Location:
Slab on grade, grid lines E-G/11-21 (west)
Measured
Slump
(inches)
5.0
Sample Location:
Grid line E.2/14.5
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
4 1 10/03/2007 7 6.00 28.27 94,460 3,340 Cone/Shear
4 2 10/24/2007 28 6.00 28.27 127,900 4,520 Cone/Shear
4 3 10/24/2007 28 6.00 28.27 122,670 4,340 Cone/Split
Average 4,430
4 4 11/21/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, ltd.
(LB/ED) Page 4 of 9
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299967
Project No.: 0712932
Date of Service: 09/26/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349
Placement Date: 09/26/2007
Weather Conditions: Cloudy, calm
Time Sampled: 07:30am Batch time: 06:54am
Temperature - Air: 710F Concrete: 800F
Truck No: 129 Ticket No: 7806
Air Content: 0.3% Unit Weight (pet): NA
Overall Placement Location:
Slab on grade, grid lines E-G/11-21 (west)
Measured
Slump
(inches)
5.5
Sample Location:
Grid line G/15.2
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
5 1 10/03/2007 7 6.00 28.27 105,500 3,730 Cone/Split
5 2 10/24/2007 28 6.00 28.27 143,610 5,080 Shear
5 3 10/24/2007 28 6.00 28.27 141,040 4,990 Cone/Split
Average 5,030
5 4 11/21/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd.
(LB/ED) Page 5 of 9
Rone En~==
Client: Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299967
Project No.: 0712932
Date of Service: 09/26/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/26/2007
Weather Conditions: Cloudy, calm
Time Sampled: 08:46am Batch time: 08:19am
Temperature - Air: 800F Concrete: 880F
Truck No: 128 Ticket No: 7820
Air Content: 0.3% Unit Weight (pet): NA
Overall Placement Location:
Slab on grade, grid lines E-G/11-21 (west)
Measured
Slump
(inches)
5.0
Sample Location:
Grid line E.8/16.3
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
6 1 10/03/2007 7 6.00 28.27 103,930 3,680 Cone/Split
6 2 10/24/2007 28 6.00 28.27 130,360 4,610 Cone/Split
6 3 10/24/2007 28 6.00 28.27 133,740 4,730 Shear
Average 4,670
6 4 11/21/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 6 of 9
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299967
Project No.: 0712932
Date of Service: 09/26/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/26/2007
Weather Conditions: Cloudy, calm
Time Sampled: 10:50am Batch time: 10:24am
Temperature - Air: 780F Concrete: 900F
Truck No: 141 Ticket No: 7837
Air Content: 0.6% Unit Weight (pet): NA
Overall Placement Location:
Slab on grade, grid lines E-G/11-21 (west)
Measured
Slump
(inches)
5.5
Sample Location:
Grid line E.6/17
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
7 1 10/03/2007 7 6.00 28.27 104,180 3,680 Shear
7 2 10/24/2007 28 6.00 28.27 124,000 4,390 Shear
7 3 10/24/2007 28 6.00 28.27 132,390 4,680 Cone/Split
Average 4,530
7 4 11/21/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. ltd.
(LB/ED) Page 7 of 9
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Com pressive Strength Test
Report No.: 299967
Project No.: 0712932
Date of Service: 09/26/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/26/2007
Weather Conditions: Cloudy, calm
Time Sampled: 11 :30am Batch time: 10:55am
Temperature - Air: 850F Concrete: 900F
Truck No: 103 Ticket No: 7843
Air Content: 0.7% Unit Weight (pcf): NA
Overall Placement Location:
Slab on grade, grid lines E-G/11-21 (west)
Measured
Slump
(inches)
6.0
Sample Location:
Grid line F/1a.5
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
8 1 10/03/2007 7 6.00 28.27 97,440 3,450 Cone/Split
8 2 10/24/2007 28 6.00 28.27 128,740 4,550 Cone/Split
8 3 10/24/2007 28 6.00 28.27 124,230 4,390 Cone/Split
Average 4,470
8 4 11/21/2007 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LBIED) Page 8 of9
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299967
Project No.: 0712932
Date of Service: 09/26/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349
Placement Date: 09/26/2007
Weather Conditions: Cloudy, calm
Time Sampled: 12:00pm Batch time: 11:41am
Temperature - Air: 850F Concrete: 900F
Truck No: 128 Ticket No: 7852
Air Content: 0.4% Unit Weight (pet): NA
Overall Placement Location:
Slab on grade, grid lines E-G/11-21 (west)
Measured
Slump
(inches)
6.0
Sample Location:
Grid line E/19.5
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
9 1 10/03/2007 7 6.00 28.27 98,680 3,490 Cone/Split
9 2 10/24/2007 28 6.00 28.27 127,700 4,520 Cone/Split
9 3 10/24/2007 28 6.00 28.27 134,280 4,750 Shear
Average 4,630
9 4 11/21/2007 56
Technician: David Best Started: 02:30am
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne
(1-ec copy)
1-cc Potter Concrete Attn: Mr. Ryan Skelly
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Attn: Mr. Larry Davis
Finished: 03:00pm Rone Engineering
p~
~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(LB/ED) Page 9 of 9
Rone En~==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299952
Project No.: 0712932
Date of Service: 09/26/2007
Report Date: 10/26/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,000 psi @ 28 days
Slump (in.): NA
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7751 PW
Placement Date: 09/26/2007
Weather Conditions: Partly Cloudy
Time Sampled: 09:20am Batch time: 08:39am
Temperature - Air: 790F Concrete: 860F
Truck No: 107 Ticket No: 7823
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Building piers 24.8-20.2/L - 10 piers, 1 pier cap at B/27-27.1
Measured
Slump
(inches)
7.25
Sample Location:
Building pier U24.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/03/2007 7 6.00 28.27 57,540 2,040 Cone/Split
1 2 10/03/2007 7 6.00 28.27 59,940 2,120 Shear
Average 2,080
1 3 10/24/2007 28 6.00 28.27 76,950 2,720 Cone/Split
1 4 10/24/2007 28 6.00 28.27 86,770 3,070 Cone/Split
Average 2,900 *
1 5 11/21/2007 56
* Does not comply with specified strength
Technician: Chris Harbour Rone Engineering
See Report 299951 for technician time~~
Report Distribution: ---......
Orig: Duke Construction, LP (Dallas, TX) AUn: Mr. Paul Byrne .. ~
(1-ec copy)
1-cc Polter Concrete AUn: Mr. Ryan Skelly K. Scott Watson, AET
1-cc City of Coppell Altn: Mr. Lee Stone. ProJ'ect Manager
1-cc City of Coppell AUn: Mr. Larry DaVIS
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(lBJED) Page 1 of 1