Duke Lesley 2A-LR071016
Rone En~==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630.9745
Report of Concrete Compressive Strength Test
Report No.: 301473
Project No.: 0712932
Date of Service: 10/09/2007
Report Date: 10/16/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 9349 PW
Placement Date: 10/09/2007
Weather Conditions: Partly cloudy
Time Sampled: 03:45am Batch time: 03:34am
Temperature - Air: 740F Concrete: 810F
Truck No: 135 Ticket No: 14576
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Slab on building, grid lines C-E/21-30
Measured
Slump
(inches)
4.5
Sample Location:
Grid lines C.2/21.8
REPORT OF TESTS
Cylinder
Marked Date
Set No. Tested
1 1 10/16/2007
1 2 11/06/2007
1 3 11/06/2007
1 4 12/04/2007
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
128,480
Compressive
Strength
(psi)
4,540
Fracture
Type
Shear
Area
(in2)
28.27
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd.
(TM/KW) Page 1 of 9
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301473
Project No.: 0712932
Date of Service: 10/09/2007
Report Date: 10/16/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349 PW
Placement Date: 10/09/2007
Weather Conditions: Partly cloudy
Time Sampled: 04:45am Batch time: 04:31am
Temperature - Air: 750F Concrete: 810F
Truck No: 137 Ticket No: 14586
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Slab on building, grid lines C-E/21-30
Measured
Slump
(inches)
5.0
Sample Location:
Grid lines C.2/23
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
118,880
Cylinder
Marked Date
Set No. Tested
2 1 10/16/2007
2 2 11/06/2007
2 3 11/06/2007
2 4 12/04/2007
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Compressive
Strength
(psi)
4,200
Fracture
Type
Cone/Split
Area
(in')
28.27
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/KW) Page 2 of 9
Rone En2==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301473
Project No.: 0712932
Date of Service: 10/09/2007
Report Date: 10/16/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349 PW
Placement Date: 10/09/2007
Weather Conditions: Partly cloudy
Time Sampled: 05:40am Batch time: 05:23am
Temperature - Air: 750F Concrete: 810F
Truck No: 125 Ticket No: 14596
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Slab on building, grid lines C-E/21-30
Measured
Slump
(inches)
4.0
Sample Location:
Grid lines D/23.8
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
122,220
Cylinder
Marked Date
Set No. Tested
3 1 10/16/2007
3 2 11/06/2007
3 3 11/06/2007
3 4 12/04/2007
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Compressive
Strength
(psi)
4,320
Fracture
Type
Cone/Split
Area
(in2)
28.27
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, ltd.
(TM/KW) Page 3 of 9
Rone En~~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301473
Project No.: 0712932
Date of Service: 10/09/2007
Report Date: 10/16/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349 PW
Placement Date: 10/09/2007
Weather Conditions: Partly cloudy
Time Sampled: 06:30am Batch time: 06:20am
Temperature - Air: 740F Concrete: 800F
Truck No: 135 Ticket No: 14606
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Slab on building, grid lines C-E/21-30
Sample Location:
Grid lines D.2/25.1
REPORT OF TESTS
Measured
Slump
(inches)
4.25
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
115,610
Cylinder
Marked Date
Set No. Tested
4 1 10/16/2007
4 2 11/06/2007
4 3 11/06/2007
4 4 12/04/2007
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Compressive
Strength
(psi)
4,090
Area
(in')
28.27
Fracture
Type
Shear
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TMlKW) Page 4 of 9
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301473
Project No.: 0712932
Date of Service: 10/09/2007
Report Date: 10/16/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349 PW
Placement Date: 10/09/2007
Weather Conditions: Partly cloudy
Time Sampled: 08:05am Batch time: 07:51am
Temperature - Air: 760F Concrete: 810F
Truck No: 144 Ticket No: 14616
Air Content: NA Unit Weight (pet): NA
Overall Placement Location:
Slab on building, grid lines C-E/21-30
Measured
Slump
(inches)
4.0
Sample Location:
Grid lines 0.3/26.1
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in") (Ibs) (psi) Type
5 1 10/16/2007 7 6.00 28.27 119,300 4,220 Shear
5 2 11/06/2007 28
5 3 11/06/2007 28
5 4 12/04/2007 56
LIMITATION S: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TMlKW) Page 5 of 9
Rone En~==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301473
Project No.: 0712932
Date of Service: 10/09/2007
Report Date: 10/16/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349 PW
Placement Date: 10/09/2007
Weather Conditions: Partly cloudy
Time Sampled: 09:10am Batch time: 08:57am
Temperature - Air: 760F Concrete: 810F
Truck No: 102 Ticket No: 14628
Air Content: NA Unit Weight (pcf): NA
Overall Placement Location:
Slab on building, grid lines C-E/21-30
Measured
Slump
(inches)
4.0
Sample Location:
Grid lines 0.8/27
REPORT OF TESTS
Cylinder
Marked Date
Set No. Tested
6 1 10/16/2007
6 2 11/06/2007
6 3 11/06/2007
6 4 12/04/2007
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
113,760
Compressive
Strength
(psi)
4,020
Fracture
Type
Shear
Area
(in')
28.27
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/KW) Page 6 of 9
Rone Eni==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301473
Project No.: 0712932
Date of Service: 10/09/2007
Report Date: 10/16/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349 PW
Placement Date: 10/09/2007
Weather Conditions: Sunny
Time Sampled: 10:15am
Temperature - Air: 760F
Truck No: 134
Air Content: NA
Overall Placement Location:
Slab on building, grid lines C-E/21-30
Batch time: 09:57am
Concrete: 810F
Ticket No: 14639
Unit Weight (pcf): NA
Measured
Slump
(inches)
4.25
Sample Location:
Grid lines C.5/28
REPORT OF TESTS
Cylinder
Marked Date
Set No. Tested
7 1 10/16/2007
7 2 11/06/2007
7 3 11/06/2007
7 4 12/04/2007
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
120,030
Compressive
Strength
(psi)
4,250
Fracture
Type
Cone/Split
Area
(in2)
28.27
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TMlKW) Page 7 of 9
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301473
Project No.: 0712932
Date of Service: 10/09/2007
Report Date: 10/16/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349 PW
Placement Date: 10/09/2007
Weather Conditions: Sunny
Time Sampled: 11:15am
Temperature - Air: 770F
Truck No: 142
Air Content: NA
Overall Placement Location:
Slab on building, grid lines C-E/21-30
Sample Location:
Grid lines 0.1/29
REPORT OF TESTS
Batch time: 11 :04am
Concrete: 820F
Ticket No: 14651
Unit Weight (pet): NA
Measured
Slump
(inches)
3.75
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
108,250
Cylinder
Marked Date
Set No. Tested
8 1 10/16/2007
8 2 11/06/2007
8 3 11/06/2007
8 4 12/04/2007
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Area
(in')
28.27
Compressive
Strength
(psi)
3,830
Fracture
Type
Shear
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TMlKW) Page 8 of 9
Rone En2==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301473
Project No.: 0712932
Date of Service: 10/09/2007
Report Date: 10/16/2007
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 01
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9349 PW
Placement Date: 10/09/2007
Weather Conditions: Sunny
Time Sampled: 12:30pm
Temperature - Air: 770F
Truck No: 142
Air Content: NA
Overall Placement Location:
Slab on building, grid lines C-E/21-30
Batch time:
Concrete: 820F
Ticket No: 14661
Unit Weight (pet): NA
Measured
Slump
(inches)
4.5
Sample Location:
Grid lines C/30
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
9 1 10/16/2007 7 6.00 28.27 101,180 3,580 Shear
9 2 11/06/2007 28
9 3 11/06/2007 28
9 4 12/04/2007 56
Started: 02:30am Finished: 02:00pm
Technician: Brad Hickman
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) AlIn: Mr. Paul Byrne
(1-ec copy)
1-cc Potter Concrete Alln: Mr. Ryan Skelly
1-cc City of Coppell Alln: Mr. Lee Stone
1-cc City of Coppell Alln: Mr. Larry Davis
Rone Engineering
p~
;:;::>
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/KW) Page 9 of 9