Report of Concrete Compressive Strength Test
Report No.: 301806
Project No.: 0612510
Date of Service: 10/06/2007
Report Date: 10/18/2007
Project: Lesley Infrastructure
Services: Test compressive strength test specimens prepared by others and picked up at the jobsite.
PROJECT OAT A
Contractor:
Concrete Supplier: LMC
Plant: NA
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: NA
Placement Date: 10/05/2007
Weather Conditions: NA
Time Sampled:
Temperature - Air:
Truck No: NA
Air Content: NA
Overall Placement Location:
Headwall (Wall), Line E
Measured
Slump
(inches)
Batch time:
Concrete:
Ticket No: NA
Unit Weight (pcf): NA
Sample Location:
Line E Headwall
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
1 1 10/12/2007 7 6.00 28.27 94,960 3,360 Shear
1 2 11/02/2007 28
1 3 11/02/2007 28
4 11/30/2007 56
Remarks: All information other than concrete compressive strength test results was provided by the contractor and
assumed to be correct.
Technician: Denny Harris
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX)
Attn: Mr. Alex Bennett PE (1-ec copy)
1-ec Lacy Construction Alln: Mr. Kevin Briles
1-cc City of Coppell Alln: Mr. Lee Stone
1-cc City of Coppell Alln: Mr. Larry Davis
Rone Engineering
Soo Repo" 301161 'ocle,',,;,;.. I;me~~ _~
K. Scolt Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 1 of 1