Loading...
Gateway BP(3.1)-LR071022 (2) Rone Engineering Client: Transwestern Commercial Services 5001 Spring Valley Dallas, TX 75244 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 301782 Project No.: 0712786 Date of Service: 10/11/2007 Report Date: 10/22/2007 Project: Gateway Business Center Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Constructors & Associates Concrete Supplier: Redi Mix Plant: 136 Specification Requirements Strength: 3,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Measured Slump (inches) 5.0 Mix Design I.D.: 330J1501 Placement Date: 10/11/2007 Weather Conditions: Sunny, calm Time Sampled: 12:01pm Batch time: Temperature - Air: 780F Concrete: 880F Truck No: 1186 Ticket No: 13699324 Air Content: 1.7% Unit Weight (pet): NA Overall Placement Location: Building #1, slab leave-outs, grid line A to A.1-8.7 to 9 and 0.8 to E-8 to 10 Sample Location: Grid line A, l' south 8.8 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in2) (Ibs) (psi) Type 1 1 10/18/2007 7 6.00 28.27 83,750 2,960 Shear 1 2 11/08/2007 28 1 3 11/08/2007 28 1 4 12/06/2007 56 Remarks: Notified on site crew leader of test results LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/KW) Page 1 of 2 Client: Transwestern Commercial Services 5001 Spring Valley Dallas, TX 75244 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 301781 Project No.: 0712786 Date of Service: 10/11/2007 Report Date: 10/22/2007 Project: Gateway Business Center Coppell' Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Constructors & Associates Concrete Supplier: Redi Mix Plant: 136 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Measured Slump (inches) 6.0 Mix Design 1.0.: 23601524 Placement Date: 10/11/2007 Weather Conditions: Clear, calm Time Sampled: 03:36am Batch time: 02:34am Temperature - Air: 600F Concrete: nOF Truck No: 1035 Ticket No: 13699228 Air Content: 4.0% Unit Weight (pet): NA Overall Placement Location: Paving - building 1 on south side and west side - parking spaces and driveway Sample Location: Grid line Building 1, A 1 50' west, 50' north REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in2) (Ibs) (psi) Type 1 1 10/18/2007 7 6.00 28.27 100,280 3,550 Shear 1 2 11/08/2007 28 1 3 11/08/2007 28 1 4 12/06/2007 56 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/KW) Page 1 of 5 Client: Transwestern Commercial Services 5001 Spring Valley Dallas, TX 75244 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 301781 Project No.: 0712786 Date of Service: 10/11/2007 Report Date: 10/22/2007 Project: Gateway Business Center Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Constructors & Associates Concrete Supplier: Redi Mix Plant: 136 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Batch time: 04:11am Concrete: 800F Ticket No: 13699241 Unit Weight (pet): NA Measured Slump (inches) 5.0 Mix Design 1.0.: 23601524 Placement Date: 10/11/2007 Weather Conditions: Clear Time Sampled: 05:10am Temperature - Air: 600F Truck No: 1032 Air Content: 3.5% Overall Placement Location: Paving - building 1 on south side and west side - parking spaces and driveway Sample Location: Grid line Building 1, E3, 50' south REPORT OF TESTS Cylinder Marked Date Set No. Tested 2 1 10/18/2007 2 2 11/08/2007 2 3 11/08/2007 2 4 12/06/2007 Age (days) 7 Diameter (in) 6.00 28 28 56 Remarks: Water added at site: 10 gallons Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 89,100 Compressive Strength (psi) 3,150 Fracture Type Shear Area (in') 28.27 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, ltd. (LBfKW) Page 2 of 5 Client: Transwestern Commercial Services 5001 Spring Valley Dallas, TX 75244 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 301781 Project No.: 0712786 Date of Service: 10/11/2007 Report Date: 10/22/2007 Project: Gateway Business Center Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Constructors & Associates Concrete Supplier: Redi Mix Plant: 136 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Batch time: 05:37am Concrete: 800F Ticket No: 13699254 Unit Weight (pcf): NA Measured Slump (inches) 4.0 Mix Design I.D.: 23601524 Placement Date: 10/11/2007 Weather Conditions: Sunny Time Sampled: 07:25am Temperature - Air: 600F Truck No: 1185 Air Content: 4.0% Overall Placement Location: Paving - building 1 on south side and west side - parking spaces and driveway Sample Location: Grid line Building 1, E1, 15' south, 50' west REPORT OF TESTS Cylinder Marked Date Set No. Tested 3 1 10/18/2007 3 2 11/08/2007 3 3 11/08/2007 3 4 12/06/2007 Age (days) 7 Diameter (in) 6.00 28 28 56 Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 104,810 Compressive Strength (psi) 3,710 Fracture Type Cone/Split Area (in') 28.27 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LBIKW) Page 3 of 5 Client: Transwestern Commercial Services 5001 Spring Valley Dallas, TX 75244 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 301781 Project No.: 0712786 Date of Service: 10/11/2007 Report Date: 10/22/2007 Project: Gateway Business Center Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Constructors & Associates Concrete Supplier: Redi Mix Plant: 136 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1 064 ASTM C-138 ASTM C-39 Batch time: Concrete: 790F Ticket No: 13699281 Unit Weight (pcf): NA Measured Slump (inches) 4.75 Mix Design I.D.: 23601524 Placement Date: 10/11/2007 Weather Conditions: Sunny Time Sampled: 09:00am Temperature - Air: 690F Truck No: 1033 Air Content: 5.0% Overall Placement Location: Paving - building 1 on south side and west side - parking spaces and driveway Sample Location: Grid line Building 1, E6, 30' south REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 4 1 10/18/2007 7 6.00 28.27 87,700 3,100 Cone/Split 4 2 11/08/2007 28 4 3 11/08/2007 28 4 4 12/06/2007 56 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/KW) Page 4 of 5