Gateway BP(3.1)-LR071018 (2)
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Reinforcing Steel Inspection
Report No.: 301372
Project No.: 0712786
Date of Service: 10/08/2007
Report Date: 10/18/2007
Project: Gateway Business Center
Coppell, Texas
Services: Reinforcing Sleellnspection
Report of Inspection
Locations and Items Inspected:
Paving, northwest side of building, fire lane and paving, even
with northwest corner of building moving northeast towards the north corner
of the build ing
Item s Inspected: Co nfo rming Non Items Inspected: Co nfo rm ing Non Item s Inspected: Conforming Non
Conforming Conforming Confo rm ing
Placing Drawings Bar Length Column Ties Properly
Approved x and Shape x Tied and Spaced NA
Bar Size x Pro per B ar Placement x Stirrup Spacing NA
Bar Grade x Pro perly Tied x Stirrup Type NA
Bars Clean x Dowel Bars in Place x Lapped Splices NA
Form Clean x Proper B ar Suppo rts x Corner Bars NA
Numberof Bars x P fO per Cover x Mechanical Splices NA
Discrepancies I Comments:
1. Chairs to be placed during concrete placement.
No apparent discrepancies were noted at the locations listed above.
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no conlnel. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/KW) Page 1 of 2
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of In-Place Density Testing
Report No.: 301687
Project No.: 0712786
Date of Service: 10/10/2007
Report Date: 10/18/2007
Project: Gateway Business Center
Coppell, Texas
Services: Perform In-Place Density Testing
PROJECT DATA
Contractor: Constructors & Associates
Test Method: ASTM D-6938
Gauge: Troxler 3430
Gauge Serial No: 35518
Test Mode: DT
Standard Counts
Moisture Density
Current: 739 Current: 2508
Previous: 737 Previous: 2504
MOISTURE DENSITY RELATIONS
MID No.
277809
Description
Moisture
%
Maximum
Density
(pet)
89.0
Project Requirements
Moisture Density
Optimum +4 95 min
Dark Brown / Clay
27.0
2
Test Location
Paving subgrade
50' south from northwest corner, south side
Paving subgrade
100' south from northwest corner, south side
Paving subgrade
200' south from northwest corner, south side
FIELD DENSITY TESTS
Probe MID
Depth No.
Moisture Wet Density Dry Density Density
% (pet) (pet) (% maxI
Test
No
6" 277809
30.8
116.9
89.4
100
6" 277809
30.9
116.4
88.9
100
3
6" 277809
29.2
115.1
89.1
100
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be repnoduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 1 of 2
Rone Engineering
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301474
Project No.: 0712786
Date of Service: 10/09/2007
Report Date: 10/18/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 259
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 2% - 4%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 23501501
Placement Date: 10/09/2007
Weather Conditions: Clear
Time Sampled: 03:10am
Temperature - Air: 710F
Truck No: 1350
Air Content: 2.0%
Overall Placement Location:
Paving - north of building parking lot
Batch time: 02:28am
Concrete: 870F
Ticket No: 59015480
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
5' west, 10' south from northeast corner of paving
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/16/2007 7 6.00 28.27 100,580 3,560 Cone/Split
1 2 11/06/2007 28
1 3 11/06/2007 28
1 4 12/04/2007 56
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 1 of 6
Rone Engineering
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301474
Project No.: 0712786
Date of Service: 10/09/2007
Report Date: 10/18/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 259
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 2% - 4%
Test Method: AS'TM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23501501
Placement Date: 10/09/2007
Weather Conditions: Clear
Time Sampled: 05:20am
Temperature - Air: 710F
Truck No: 1347
Air Content: 2.2%
Overall Placement Location:
Paving - north of building parking lot
Batch time: 04:33am
Concrete: 880F
Ticket No: 59015494
Unit Weight (pct): NA
Measured
Slump
(inches)
5.5
Sample Location:
100' west, 15' north from southeast corner of paving
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
2 1 10/16/2007 7 6.00 28.27 91,450 3,230 Cone/Shear
2 2 11/06/2007 28
2 3 11/06/2007 28
2 4 12/04/2007 56
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 2 of 6
Rone Engineering
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301474
Project No.: 0712786
Date of Service: 10/09/2007
Report Date: 10/18/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards. .
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 259
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 2% - 4%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23501501
Placement Date: 10/09/2007
Weather Conditions: Clear
Time Sampled: 07:30am
Temperature - Air: 710F
Truck No: 1307
Air Content: 2.0%
Overall Placement Location:
Paving - north of building parking lot
Batch time: 06:01am
Concrete: 870F
Ticket No: 53015501
Unit Weight (pct): NA
Measured
Slump
(inches)
6.0
Sample Location:
200' west, 1 0' south from northeast corner of paving
Area
(in')
28.27
REPORT OF TESTS
Compressive
Strength
(psi)
3,650
Fracture
Type
Cone/Split
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
103,300
Cylinder
Marked Date
Set No. Tested
3 1 10/16/2007
3 2 11/06/2007
3 3 11/06/2007
3 4 12/04/2007
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 3 of 6
Rone Engineering
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 301474
Project No.: 0712786
Date of Service: 10/09/2007
Report Date: 10/18/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 259
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 2% - 4%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23501501
Placement Date: 10/09/2007
Weather Conditions: Clear
Time Sampled: 09:30am
Temperature - Air: 750F
Truck No: 1257
Air Content: 2.2%
Overall Placement Location:
Paving - north of building parking lot
Batch time: 08:28am
Concrete: 880F
Ticket No: 59015523
Unit Weight (pcf): NA
Measured
Slump
(inches)
5.5
Sample Location:
60' east, 10' south from northwest comer of paving
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
4 1 10/16/2007 7 6.00 28.27 103,260 3,650 Cone/Split
4 2 11/06/2007 28
4 3 11/06/2007 28
4 4 12/04/2007 56
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 4 of 6
Rone Engineering
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214)630-9745
Report of Concrete Compressive Strength Test
Report No.: 301474
Project No.: 0712786
Date of Service: 10/09/2007
Report Date: 10/18/2007
Project: Gateway Business Center
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Constructors & Associates
Concrete Supplier: Redi Mix
Plant: 259
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): 2% - 4%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 23501501
Placement Date: 10/09/2007
Weather Conditions: Clear
Time Sampled: 09:50am
Temperature - Air: 740F
Truck No: 1264
Air Content: 2.4%
Overall Placement Location:
Paving - north of building parking lot
Batch time: 09: 10am
Concrete: 880F
Ticket No: 59015535
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
30' east, S' north from southwest corner of paving
Area
(in2)
28.27
REPORT OF TESTS
Compressive
Strength
(psi)
3,370
Fracture
Type
Cone/Shear
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
95,240
Cylinder
Marked Date
Set No. Tested
5 1 10/16/2007
5 2 11/06/2007
5 3 11/06/2007
5 4 12/04/2007
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Remarks: Water added at site: 30 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar SUbject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 5 of 6
Rone Engineering
..
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Reinforcing Steel Inspection
Report No.: 300572
Project No.: 0712786
Date of Service: 10/01/2007
Report Date: 10/18/2007
Project: Gateway Business Center
Coppell, Texas
Services: Reinforcing Steel Inspection
Report of Inspection
Locations and Items Inspected:
Paving, north side of building 1, fire lane from northeast corner of building 1,
220' west
Item sins peeted" Co nfo rm ing Non Items Inspected: Conforming Non Items Inspected: Conforming Non
Conforming Conforming Conforming
Placing Drawings Bar Length Column Ties Properly
Appro ved x and Shape x Tied and Spaced NA
Bar Size x P fO per 8 ar P laeem ent x Stirrup Spacing NA
Bar Grade x Pro perty Tied x Stirrup Type NA
Bars Clean x Dowel Bars in Place x Lapped 6 plices NA
Form Clean x Pro per Bar Suppa rts x Corner Bars NA
N urn ber of Bars x Proper Cover x Mechanical Splices NA
Discrepancies I Comments:
1. Chairs to be placed during concrete placement.
No apparent discrepancies were noted at the locations listed above,
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar SUbject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(ThIIIKW) Page 1 of 2
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Transwestern Commercial Services
5001 Spring Valley
Dallas, TX 75244
Report of Reinforcing Steel Inspection
Report No.: 301688
Project No.: 0712786
Date of Service: 10/10/2007
Report Date: 10/18/2007
Project: Gateway Business Center
Coppell, Texas
Services: Reinforcing Steel Inspection
Report of Inspection
Locations and Items Inspected:
Paving, building 1, from westside of south entrance of building around
to the northwest corner of building
Items Inspected: co nlo rm ing Non Items Inspected: Conforming Non Items Inspected: Co nfo rm ing Non
Co nlo rm ing Conforming Co nlo rm ing
P lacing Drawings Bar Length Column Ties Properly
Approved x and Shape x Tied and Spaced NA
Bar Size x P ra per 8 ar Placement x Stirrup Spacing NA
Bar Grade x Pro perty Tied x Stirrup Type NA
Bars Clean x Dowel Bars in Place x Lapped Splices x
Form Clean x Pro per B ar Suppo rts x Corner 8 ars x
Num ber 01 Bars x ProperCover x Mechanical Splices NA
Discrepancies I Comments: 1. Trim reinforcement going on top of storm box drain.
2. Finish last 100' of east side.
3. Need curb reinforcement on east half.
4. Chairs to be added during concrete placement.
Discrepancies 1-3 were corrected prior to concrete placement.
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd.
(TMlKW) Page 1 of 2