Loading...
Duke Lesley 1A-LR071103 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 770~ W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 302436 Project No.: 0713408 Date of Service: 10/19/2007 Report Date: 11/03/2007 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: 10 Specification Requirements Strength: 3,000 psi @ 28 days Slump (in.): 5.0" - 7.0" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design I.D.: 9341 Placement Date: 10/19/2007 Weather Conditions: Clear Time Sampled: 09:20am Temperature - Air: 720F Truck No: 139 Air Content: NA Overall Placement Location: See report #302435 Ba~h time: 08:54am Concrete: 840F Ticket No: 8004 Unit Weight (pct): NA Measured Slump (inches) 6.0 Sample Location: Pier D/3 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 135,620 Cylinder Marked Date Set No. Tested 1 1 10/26/2007 1 2 11/16/2007 1 3 11/16/2007 1 4 12/14/2007 Age (days) 7 Diameter (in) 6.00 28 28 56 Remarks: Water Added at Site: 5 gallons Technician: Jimmy Hall Compressive Strength (psi) 4,800 Fracture Type Cone/Split Area (in') 28.27 Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Emmit Coots (1-ec copy) 1-cc Potter Concrete Attn: Mr. Ryan Skelly 1-cc Pacheco Koch Consulting Engineers Attn: Mr. Jack Evans 1-cc City of Coppell Attn: Mr. Larry Davis 1-cc City of Coppell Attn: Mr. Lee Stone Rone Engineering See Report 302435'" leoh";;" tim'~ K. Scott Watson, AET Project Manager ~ LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume 1110 responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LBfLB) Page 1 of 1 Rone Eng== . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In-Place Density Testing Report No.: 303163 Project No.: 0713408 Date of Service: 10/26/2007 Report Date: 11/03/2007 Project: Point West VI Coppell, Texas Services: Perform In-Place Density Testing PROJECT DATA Contractor: Duke Construction, LP Test Method: ASTM D-6938 Gauge: Troxler 3430 Gauge Serial No: 35518 Test Mode: DT Standard Counts Moisture Density Current: 741 Current: 2566 Previous: 742 Previous: 2473 MOISTURE DENSITY RELATIONS Maximum Moisture Density Project Requirements MID No. Description 0/0 (pef) Moisture Density 299552 Lime Treated Brown & Tan I Sandy Clay 30.3 85.7 Optimum +4 95min 272998 Brown I Silty Clay wI Organics 22.5 96.5 Optimum +4 95min FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. 0/0 (pef) (pef) (0/0 max) Utility backfill 1 Sanitary sewer line 2, 60' from north end, 4' 6" 272998 22.6 116.6 95.1 99 below grade Utility backfill 2 Sanitary sewer line 2,60' from north end, 3' 6" 272998 22.9 116.4 94.7 98 below grade Utility backfill 3 Sanitary sewer line 2, 60' from north end, 2' 6" 272998 23.0 117.5 95.5 99 below grade Utility backfill 4 Sanitary sewer line 2, 60' from north end, l' 6" 272998 23.1 117.1 95.1 99 below grade Utility backfill 5 Sanitary sewer line 2,60' from north end, final 6" 272998 23.7 116.8 94.4 98 Utility backfill 6 Storm drain, line B, Station 1+00, final 6" 272998 23.7 116.3 94.0 97 Utility backfill 7 Storm drain, line C, Station 1+00, final 6" 272998 23.9 116.6 94.1 98 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have 1110 control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (ED/ED) Page 1 of 2 Rone Eni== , 8908 Ambassador Row, Dallas, TX 75247 77b1 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 Report of In..Place Density Testing Report No.: 303163 Project No.: 0713408 Date of Service: 10/26/2007 Report Date: 11/03/2007 Project: Point West VI Coppell, Texas Services: Perform In-Place Density Testing FIELD DENSITY TESTS Test Probe MID Moisture Wet Density Dry Density Density No Test Location Depth No. % (pet) (pet) (% max) Utility backfill 8 Storm drain, line D, Station 1 +50, final 6" 272998 24.9 116.8 93.5 97 Utility backfill 9 Retest #1 from report #302109 6" 299552 30.1 * 109.7 84.3 98 Utility backfill 10 Retest #2 from report #302109 6" 299552 32.7* 109.6 82.6 96 Utility backfill 11 Retest #3 from report #302109 6" 299552 32.4 * 110.0 83.1 97 Utility backfill 12 Retest #4 from report #3021 09 6" 299552 31.1 * 110.1 84.0 98 Uti lity backfill 13 Retest #5 from report #302109 6" 299552 31.8* 109.8 83.3 97 An asterisk (*) appears next to results which do NOT meet the project specifications. Technician: Joe Jernigan Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Emmit Coots (1-ec copy) 1-cc Pacheco Koch Consulting Engineers Attn: Mr. Jack Evans 1-cc City of Coppell Attn: Mr. Larry Davis 1-cc City of Coppell Attn: Mr. Lee Stone Started: 10:30am Finished: 12:30pm Rone Engineering p~.~ K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (ED/ED) Page 2 of 2