Duke Lesley 2A-LR071103 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 302451 Project No.: 0712932 Date of Service: 10/19/2007 Report Date: 11/03/2007 Project: Hemisphere's at Point West Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On Site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4.0" - 6.0" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design I.D.: 9349PW Placement Date: 10/19/2007 Weather Conditions: Clear Time Sampled: 04:17am Temperature - Air: 560F Truck No: 140 Air Content: 1.2% Overall Placement Location: Tilt wall panels: P89-P97, P99-P106, P115-P119, P121-P123 Measured Slump (inches) 6.5 Batch time: Concrete: 690F Ticket No: NA Unit Weight (pet): NA Sample Location: P90, Middle section REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 1 1 10/26/2007 7 6.00 28.27 115,620 4,090 Shear 1 2 11/02/2007 14 6.00 28.27 128,050 4,530 Shear 1 3 11/16/2007 28 1 4 11/16/2007 28 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LBfLB) Page 1 of 6 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 302451 Project No.: 0712932 Date of Service: 10/19/2007 Report Date: 11/03/2007 Project: Hemisphere's at Point West Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On Site Specification Requirements Strength: 4,000 psi @28 days Slump (in.): 4.0" - 6.0" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design I.D.: 9349PW Placement Date: 10/19/2007 Weather Conditions: Clear Time Sampled: 05:37am Temperature - Air: 510F Truck No: 138 Air Content: 1.1 % Overall Placement Location: Tilt wall panels: P89-P97, P99-P106, P115-P119, P121-P123 Measured Slump (inches) 5.0 Batch time: Concrete: 750F Ticket No: NA Unit Weight (pet): NA Sample Location: P96, Top section REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 2 1 10/26/2007 7 6.00 28.27 123,260 4,360 Shear 2 2 11/02/2007 14 6.00 28.27 139,450 4,930 Cone/Split 2 3 11/16/2007 28 2 4 11/16/2007 28 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 2 of 6 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 302451 Project No.: 0712932 Date of Service: 10/19/2007 Report Date: 11/03/2007 Project: Hemisphere's at Point West Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On Site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4.0" - 6.0" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design I.D.: 9349PW Placement Date: 10/19/2007 Weather Conditions: Clear / Windy Time Sampled: 07:45am Batch time: Temperature.. Air: 520F Concrete: 740F Truck No: 109 Ticket No: NA Air Content: 1.3% Unit Weight (pet): NA Overall Placement Location: Tilt wall panels: PS9-P97, P99-P106, P115-P119, P121-P123 Measured Slump (inches) 4.75 Sample Location: P104, Bottom section REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Marked Date Age Diameter Area Load Fracture Set No. Tested (days) (in) (in') (Ibs) Type 3 1 10/26/2007 7 6.00 28.27 102,460 Cone/Split 3 2 11/02/2007 14 6.00 28.27 113,960 Cone/Split 3 3 11/16/2007 28 3 4 11/16/2007 28 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 3 of 6 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 302451 Project No.: 0712932 Date of Service: 10/19/2007 Report Date: 11/03/2007 Project: Hemisphere's at Point West Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On Site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4.0" - 6.0" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design 1.0.: 9349PW Placement Date: 10/19/2007 Weather Conditions: Clear / Windy Time Sampled: 09:25am Batch time: Temperature - Air: 630F Concrete: 750F Truck No: 132 Ticket No: NA Air Content: 1.2% Unit Weight (pet): NA Overall Placement Location: Tilt wall panels: P89-P97, P99-P106, P115-P119, P121-P123 Measured Slump (inches) 4.5 Sample location: P116, Middle section REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 4 1 10/26/2007 7 6.00 28.27 114,020 4,030 Cone/Split 4 2 11/02/2007 14 6.00 28.27 129,730 4,590 Cone/Split 4 3 11/16/2007 28 4 4 11/16/2007 28 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LBILB) Page 4 of 6 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 302451 Project No.: 0712932 Date of Service: 10/19/2007 Report Date: 11/03/2007 Project: Hemisphere's at Point West Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On Site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4.0" - 6.0" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design 1.0.: 9349PW Placement Date: 10/19/2007 Weather Conditions: Clear Time Sampled: 11 :03am Temperature - Air: 730F Truck No: 107 Air Content: 1.1% Overall Placement Location: Tilt wall panels: P89-P97, P99-P106, P115-P119, P121-P123 Measured Slump (inches) 5.0 Batch time: Concrete: 750F Ticket No: NA Unit Weight (pcf): NA Sample Location: P121, Top section REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in2) (Ibs) (psi) Type 5 1 10/26/2007 7 6.00 28.27 110,710 3,920 Shear 5 2 11/02/2007 14 6.00 28.27 127,530 4,510 Cone/Split 5 3 11/16/2007 28 5 4 11/16/2007 28 L1MrrA TIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LBILB) Page 5 of 6 Rone Engineering .- Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 302451 Project No.: 0712932 Date of Service: 10/19/2007 Report Date: 11/03/2007 Project: Hemisphere's at Point West Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On Site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4.0" - 6.0" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design 1.0.: 9349PW Placement Date: 10/19/2007 Weather Conditions: Clear Time Sampled: 02:15am Temperature - Air: 750F Truck No: 140 Air Content: 1.2% Overall Placement Location: Tilt wall panels: P89-P97, P99-P106, P115-P119, P121-P123 Measured Slump (inches) 4.75 Batch time: Concrete: 750F Ticket No: NA Unit Weight (pet): NA Sample Location: P123, Top section REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 6 1 10/26/2007 7 6.00 28.27 93,650 3,310 Shear 6 2 11/02/2007 14 6.00 28.27 111,950 3,960 Cone/Split 6 3 11/16/2007 28 6 4 11/16/2007 28 Started: 03:15am Finished: 02:15pm Technician: Javier Martinez Report Distribution: Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne (1-ec copy) 1-cc Potter Concrete Attn: Mr. Ryan Skelly 1-cc City of Coppell Attn: Mr. Lee Stone 1-cc City of Coppell Attn: Mr. Larry Davis Rone Engineering p~ ;;; K. Scott Watson, AET Project Manager LIMITATIONS: The test results presented herein were prepared based upon the specifiC samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (LB/LB) Page 6 of 6