Northlake College-LR071213
KLEINFELDER
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
LIME DEPTH CHECKS
TO: Dallas County Community College Dist.
1505 South Lamar, Suite 1015
Dallas, Texas 75215
PROJECT: North Lake College, N Campus
W Sandy Lake Road @ SH 121
PROJECT NO: 87015
REPORT DATE: 12/13/2007
REPORT NO.: 127363
T est Performed By: J. Mayo
Date of Test: 12/4/2007
Results:
Location
Lime
Depth
North Parking Area
E entrance fire lane at Royal
60' Sand 70' W from SE corner of Area A (firelane)
45' E and 95' N from the SE corner of Area A (firelane)
8.5"
7.75"
8.125"
8.5"
Requirements
6"
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu) KLEINFELDER
DCCCD Bond Office; AUn: James Williams Uames.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu)
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis Joel Peters, P. E.
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, TX 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
IN-PLACE MOISTURE DENSITY TEST RESULTS
To: Dallas County Community College Dist. Test Date: 11/17/2007
1505 South Lamar, Suite 1015 Project No: 87015
Dallas, Texas 75215 Report Date: 12/13/2007
Report No: 117430
Project: North Lake College, N Campus Definitions of Terms
Location: W Sandy Lake Road @ SH 121 RQP- Rt Qtr Point CL - Centerline
Field Rep: J. Mayo LQP - Lt Qtr Point Sta - Station
Test Test Location Depth 0 Wet Field Dry Proctor Percent
No. Lift 0 Density Moisture Density No. Proctor
(%) (pet) Density
South Parking Lot Area
1 SE quadrant 6" 112.7 36.6* 82.5 001559 97.3
2 SW quadrant 6" 122.4 39.7* 87.6 001559 103.3*
3 NW quadrant 6" 108.3 35.7 79.8 001559 94.1*
4 NE quadrant 6" 114.3 27.3* 89.8 001559 105.9*
5 NE quadrant 6" 112.7 26.3* 89.2 001559 105.2*
Proctor No: Description Opt. Moisture Max. Density
001559 Brown Clay with Lime 32.2 84.8
Specs. Gauge No: 26077 Test Methods: ASTM D 2922
Dens. (%) 95 to 100 Std. Density Count: 2413 ASTM D 3017
Moist. (%) Opt. +3 Std. Moist Count: 669 ASTM D 698
Trans. Depth (in.): 6
Remarks: * - Outside specified limits
Reports to:
Starling Richardson Canst.; Attn: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Canst.; Attn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu) a7ELDER
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) ~
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com) -, Joel Peters, P.E.
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently Identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, TX 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
IN-PLACE MOISTURE DENSITY TEST RESUL TS
To: Dallas County Community College Dist. Test Date: 11/29/2007
1505 South Lamar, Suite 1015 Project No: 87015
Dallas, Texas 75215 Report Date: 12/13/2007
Report No: 117507
Project: North Lake ColleQe, N Campus Definitions of Terms
Location: W Sandy Lake Road @ SH 121 RQP- Rt Qtr Point CL - Centerline
Field Rep: J. Mayo LQP - Lt Qtr Point Sta - Station
Test T est Location Depth 0 Wet Field Dry Proctor Percent
No. Lift 0 Density Moisture Density No. Proctor
(%) (pcf) Density
1 Firelane 130' E x 1 DO' N from the 6" 107.5 31.8* 81.6 001609 95.7
SE corner
2 SW quadrant N parkinQ lot 6" 105.9 35.4 78.2 001609 91.7*
3 Retest of # 2 6" 110.0 33.5 82.4 001609 96.6
4 SE quadrant N parking lot 6" 111.6 27. 1 * 87.8 001609 102.9
5 Retest of # 4 6" 109.8 33.2 82.4 001609 96.6
6 45' E x 100' N from the SE corner 6" 100.9 26.4* 79.8 001609 93.6*
of bldg
7 60' S x 40' W from SE corner 6" 101.6 32.3 76.8 001609 90.0*
8 45' E x 85' N from SE corner 6" 103.8 36.2* 76.2 001609 89.3*
9 130' E x 85' N from SE corner 6" 105.1 25.1* 84.0 001609 98.5
10 NW quadrant N parking lot 6" 115.0 32.8 86.6 001609 101.5
11 NE quadrant N parking lot 6" 106.0 39.6* 75.9 001609 89.0*
12 NE quadrant N parking lot 6" 110.7 27.5* 86.8 001609 101.8
13 Firelane E of N parking lot 6" 110.2 32.1 83.4 001609 97.8
Proctor No: Description Opt. Moisture Max. Density
001609 Lime treated brown clay 31.4 85.3
Specs. Gauge No: 29979 Test Methods: ASTM D 2922
Dens. (%) Min 95 Std. Density Count: 2432 ASTM D 3017
Moist. (%) o to +3 Std. Moist Count: 643 ASTM D 698
Trans. Depth (in.): 6
Remarks: * - Outside specified limits
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu) G;;~
DCCCD Bond Office; Alln: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu)
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com) / ,oel Peters, P.E.
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, TX 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
IN-PLACE MOISTURE DENSITY TEST RESULTS
To: Dallas County Community College Dist. Test Date: 11/21/2007
1505 South Lamar, Suite 1015 Project No: 87015
Dallas, Texas 75215 Report Date: 12/13/2007
Report No: 117494
Project: North Lake ColleQe, N Campus Definitions of Terms
Location: W Sandy Lake Road @ SH 121 RQP- Rt Qtr Point CL - Centerline
Field Rep: J. Mayo LQP - Lt Qtr Point Sta - Station
Test Test Location Depth 0 Wet Field Dry Proctor Percent
No. Lift 0 Density Moisture Density No. Proctor
(%) ( pcf) Density
1 SW quadrant retest - S parkinQ 6" 108.6 30.2* 83.4 001575 89.4*
2 SW quadrant retest - S parkinQ 6" 108.1 28.4 84.2 001575 90.3*
3 SW quadrant retest - Sparking 6" 103.2 27.3 81.1 001575 86.9*
4 Middle of S parking, retest 6" 109.3 26.1* 86.7 001575 92.9*
5 SE entrance at Royal 6" 113.1 22.5* 92.3 001575 98.9
6 E entrance at Royal 6" 112.8 26.0 89.5 001575 95.9
7 NW quadrant retest 6" 113.5 27.2 89.2 001575 95.6
8 NE quadrant 6" 115.1 25.1* 92.0 001575 98.6
Proctor No: Description Opt. Moisture Max. Density
001575 Light Brown Clay with Lime 26.5 93.3
SJJecs. Gauge No: 28714 Test Methods: ASTM D 2922
Dens. (% 95 to 100 Std. Density Count: 2306 ASTM D 3017
Moist. (% Opt. +3 Std. Moist Count: 665 ASTM D 698
Trans. Depth (in.): 6
Remarks: * - Outside specified limits
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) OdiU
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams Oames.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu)
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com) / Joel Peters, P.E.
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, TX 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
IN-PLACE MOISTURE DENSITY TEST RESULTS
To: Dallas County Community College Dist. Test Date: 11/20/2007
1505 South Lamar, Suite 1015 Project No: 87015
Dallas, Texas 75215 Report Date: 12/13/2007
Report No: 117427
Project: North Lake College, N Campus Definitions of Terms
Location: W Sandy Lake Road @ SH 121 RQP- Rt Qtr Point CL - Centerline
Field Rep: J. Mayo LQP - Lt Qtr Point Sta - Station
Test T est Location Depth [] Wet Field Dry Proctor Percent
No. Lift D Density Moisture Density No. Proctor
(%) (pcf) Densitv
South Parking Lot Area
1 SW quadrant 6" 114.4 34.6 85.0 001559 100.2*
2 NW quadrant 6" 114.4 32.0 86.7 001559 102.2*
3 NE quadrant 6" 112.5 24.6* 90.3 001559 106.5*
4 NE quadrant 6" 114.1 30.0* 87.8 001559 103.5*
5 SE quadrant 6" 107.7 26.9* 84.9 001559 100.1 *
Proctor No: Description Opt. Moisture Max. Density
001559 Brown Clay with Lime 32.2 84.8
Specs. Gauge No: 29980 Test Methods: ASTM 0 2922
Dens. (%) 95 to 100 Std. Density Count: 2504 ASTM D 3017
Moist. (%) +3 Std. Moist Count: 657 ASTM D 698
Trans. Depth (in.): 6
Remarks: * - Outside specified limits
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu) (J, KLEINFELDER
DCCCD Bond Office; Alln: James Williams (james.williams@dcccd.edu) It? .OJ.
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) rb~ -
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com) j/ Joel Peters, P.E.
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusove use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the quaiities of apparently identical products. The use of our name must receive prior written approval Reports must be reproduced in their entirety.
KLEINFELDER
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
REINFORCING STEEL VISUAL OBSERVATIONS
TO: Dallas County Community College Dist.
1505 South Lamar, Suite 1015
Dallas, Texas 75215
PROJECT: North Lake College, N Campus
W Sandy Lake Road @ SH 121
PROJECT NO: 87015
REPORT DATE: 12/13/2007
REPORT NO.: 127029
Technician: J. Mayo
Observation Date: 12/5/2007
Item / Object Observed:
D Slab
DWall
o Grade Beam
D Column
o Paving
D Other
Specific Observation Location: Rebar on W side of the SW and NW quadrant firelane.
Referenced Drawing:
Results:
o Reinforcing steel placed in general accordance with the project drawings.
D Exceptions noted and referred to contractor for correction.
D Exceptions noted and referred to structural engineer.
o Exceptions corrected prior to placement of concrete.
Remarks:
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams Games.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu)
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected They are not intended to be
Indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Repcrts must be reproduced in their entirety.
KLEIN FELDER
Joel Peters, P.E.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127029 Page 1 of 6
CONCRETE FOR: Firelane on the W side of S parking area from the NW corner 15' W x 10' S
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
127029A 7 12/5/07 12/12/07 4.00 12.57 5 57,700 4,590
127029B 28 12/5/07 1/2/08
127029C 28 12/5/07 1/2/08
1270290 HOLD 12/5/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL T SPECIFIED
TRUCK NO. : 84 SLUMP: 6.0
TICKET NO. : 1153744 AIR TEMP. : 40
ACCUMULATED YDS : 40 of 300 MIX TEMP. : 74
TIME CAST: 5:01 AM AIR CONTENT: 2.6
TIME IN TRUCK: 61 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends. less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
R !':imil..r In TvnA!i hili Ann
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) G~~
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) f
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P.E.
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1. City of Coppell; Attn: Lee Stone
The results shawn on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently Identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127029 Page 2 of 6
CONCRETE FOR: Firelane on the W side of S parking area from the NW corner 15' W x 130' S
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
127030A 7 12/5/07 12/12/07 4.00 12.57 5 50,960 4,060
127030B 28 12/5/07 1/2/08
127030C 28 12/5/07 1/2/08
1270300 HOLD 12/5/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 1015 SLUMP: 7.0
TICKET NO. : 1153766 AIR TEMP. : 40
ACCUMULATED YDS : 70 of 300 MIX TEMP. : 74
TIME CAST: 5:36 AM AIR CONTENT: 1.6
TIME IN TRUCK: 81 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
fi ",,'an" ...
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted.' Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM Cl064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) c1ifdffi?
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) V
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com) " Joel Peters, P.E.
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approvaL Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127029 Page 3 of 6
CONCRETE FOR: Firelane on the W side of S parking area from the NW corner 15' W x 230' S
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
127031A 7 12/5/07 12/12/07 4.00 12.57 3 55,880 4,450
127031B 28 12/5/07 1/2/08
127031C 28 12/5/07 1 /2/08
1270310 HOLD 12/5/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
I ACTUAL SPECIFIED
TRUCK NO. : 39 SLUMP: 4.5
TICKET NO. : 1153799 AIR TEMP. : 40
ACCUMULATED YDS: 130 of 300 MIX TEMP. : 75
TIME CAST: 7:06 AM AIR CONTENT: 1.8
TIME IN TRUCK: 66 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: NfA
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 Similar tn T,,~" h", on<< nf cvlinder is Dointed
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utili2ed in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C 173 I C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) Cb/~
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) f/
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P.E.
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
Indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
KLEINFELDER
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist.
1505 South Lamar, Suite 1015
Dallas, Texas 75215
PROJECT: North Lake College, N Campus
W Sandy Lake Road @ SH 121
PROJECT NO: 87015
TECHNICIAN: J. Mayo
REPORT DATE: 12/13/2007
REPORT NO: 127029 Page 4 of 6
CONCRETE FOR: Pavement from the SE entrance at Royal, 340' W x 3D' N
CYLINDER AGE
MARK DAYS
127032A 7
127032B 28
127032C 28
1270320 HOLD
DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
CAST TESTED DIAMETER, IN. AREA, (N.2 TYPE LOAD,LBS STRENGTH, PSI
12/5/07 12/12/07 4.00 12.57 5 49,640 3,950
12/5/07 1/2/08
12/5/07 1/2/08
12/5/07 HOLD
SUPPLIER: Southern Star
MIX DESIGN: D00000007725
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
AVERAGE 28 DAY STRENGTH:
28 DAY STRENGTH REQUIREMENT: 4,000
TRUCK NO. :
TICKET NO. :
ACCUMULATED YDS :
TIME CAST:
TIME IN TRUCK:
WEATHER:
905
1153884
200 of 300
7:46AM
49 min
Clear
r
SLUMP:
AIR TEMP.:
MIX TEMP.:
AIR CONTENT:
WATER ADDED (gal) :
UNIT WEIGHT:
ACTUAL
5.75
45
71
2.1
o
N/A
SPECIFIED
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1
5 Side fractures at top or bottom (occur commonly with un bonded caps).
6 ." ,t on'" nf r.vlind"r i" oointed
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231: Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams Uames.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu)
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
( ~LEIN~;L
7 Joel Peters, P.E.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127029 Page 5 of 6
CONCRETE FOR: Pavement from the SE entrance at Royal, 240' W x 10' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
127033A 7 12/5/07 12/12/07 4.00 12.57 5 45,980 3,660
127033B 28 12/5/07 1/2/08
127033C 28 12/5/07 1/2/08
1270330 HOLD 12/5/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: DOOOOOO07725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED I
TRUCK NO. : 28 SLUMP: 5.5
TICKET NO. : 1154002 AIR TEMP.: 45
ACCUMULATED YDS : 240 of 300 MIX TEMP.: 74
TIME CAST: 8:43 AM AIR CONTENT: 2.0
TIME IN TRUCK: 62min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end. vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 Simi ~. ~ inder is nnin"'rl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Un bonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM Cl72 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C 138; Air Content ASTM C 173 / C231; Temperature ASTM C 1 064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) fh/~
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Uames.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) f/ .-
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P.E.
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127029 Page 6 of 6
CONCRETE FOR: Pavement from the SE entrance at Royal, 130' W x 5' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
127034A 7 12/5/07 12/12/07 4.00 12.57 3 51,770 4,120
127034B 28 12/5/07 1/2/08
127034C 28 12/5/07 1/2/08
1270340 HOLD 12/5/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED 1
TRUCK NO. : 39 SLUMP: 5.0
TICKET NO. : 1154165 AIR TEMP. : 50
ACCUMULATED YDS: 290 of 300 MIX TEMP. : 77
TIME CAST: 9:25 AM AIR CONTENT: 2.2
TIME IN TRUCK: 38 min WATER ADDED (gal): 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
A h,,'..nrl . i~ nnint..rl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C13e; Air ContentASTM C173/ C231; Temperature ASTM Cl064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) ;1LEINFELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu) W~
DCCCD Bond Office; Alln: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) YJOel Peters, P.E.
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 117049 Page 1 of 2
CONCRETE FOR: Pier caps C-15, E-6, F-2 and S-14
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
117049A 7 11/9/07 11/16/07 4.00 12.57 2 42,490 3,380
117049B 28 11/9/07 12/7/07 4.00 12.57 5 52,740 , 4,200
117049C , 28 11/9/07 12/7/07 4.00 12.57 3 54,910 4,370
1170490 HOLD 11/9/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 4,285
MIX DESIGN: DOOOOOO09351 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL T SPECIFIED
TRUCK NO. : 948 SLUMP: 5.875
TICKET NO. : 1135191 AIR TEMP.: 85
ACCUMULATED YDS : 10 of 60 MIX TEMP. : 87
TIME CAST: 1 :41 PM AIR CONTENT: N/A
TIME IN TRUCK: 41 min WATER ADDED (gal) : 10
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
n Simil"r tn TvnA 5 hilt And
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Un bonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C 172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173 / C231: Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Altn; Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Altn: Andy Munoz (amunoz@starlingrichardson.com) (};(}jl~
DCCCD Bond Office; Altn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Altn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) ~oel Peters, P.E.
Jacobs; Altn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Altn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Altn: Larry Davis
1- City of Coppell; Altn: Lee Stone
The results shown on this report are tor the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 117049 Page 2 of 2
I CONCRETE FOR: Grade beam L-2 to L5.5 I
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
117050A 7 11/9/07 11/16/07 4.00 12.57 5 42,120 3,350
117050B 28 11/9/07 12/7/07 4.00 12.57 5 56,510 4,500
117050C 28 11/9/07 12/7/07 4.00 12.57 3 54,650 4,350
1170500 HOLD 11/9/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 4,425
MIX DESIGN: 000000009351 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED
TRUCK NO. : 84 SLUMP: 8.0
TICKET NO. : 1135285 AIR TEMP. : 80
ACCUMULATED YDS : 50 of 60 MIX TEMP.: 89
TIME CAST: 2:46 PM AIR CONTENT: N/A
TIME IN TRUCK: 56min WATER ADDED (gal) : 10
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends. less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end. vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 ~. . ~. ~ but end of . ,oointed
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
o Portions of the information contained in this report have been furnished by others. 0 Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. 0 Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
o Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C13B; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Altn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; Altn: Andy Munoz (amunoz@starlingrichardson.com) OuJl~~
DCCCD Bond Office; Altn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Altn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Altn: Mike Daniels (mike.daniels@dcccd.edu) Jl'JOel Peters, P.E.
Jacobs; Altn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Altn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Altn: Larry Davis
1- City of Coppell; Altn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127035 Page 1 of 8
CONCRETE FOR: Pavement SW quadrant from the SW corner 5' N x 15' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD,LBS STRENGTH, PSI
127035A t:8 12/6/07 12/13/07 4.00 12.57 3 56,840 , 4,520
127035B 12/6/07 1/3/08
127035C 28 12/6/07 1/3/08
1270350 HOLD 12/6/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 26 SLUMP: 5.5
TICKET NO. : 1154923 AIR TEMP.: 40
ACCUMULATED YDS: 30 of 600 MIX TEMP.: 75
TIME CAST: 2:44 AM AIR CONTENT: 2.9
TIME IN TRUCK: 41 min WATER ADDED (gal) : 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
R .';imi ,<; h"t"nrl r
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) (); KLEIN FELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com)
OCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu) ~~~~
OCCCD Bond Office; AUn: James Williams (james.williams@dcccd.edu)
OCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) I
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P,E.
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
...
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127035 Page 2 of 8
CONCRETE FOR: Pavement SW quadrant from the SW corner 85' W x 20' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD,LBS STRENGTH, PSI
127036A 7 12/6/07 12/13/07 4.00 12.57 3 55,620 4,430
127036B 28 12/6/07 1/3/08
127036C 28 12/6/07 1/3/08
1270360 HOLD 12/6/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
I ACTUAL SPECIFIED
TRUCK NO. : 84 SLUMP: 6.5
TICKET NO. : 1154943 AIR TEMP.: 40
ACCUMULATED YDS: 90 of 600 MIX TEMP. : 69
TIME CAST: 3:12 AM AIR CONTENT: 2.8
TIME IN TRUCK: 32 min WATER ADDED (gal) : 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 . . h", 4"-1 nf "vlinrl"r i~ nnint"rl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) (};/jJ~~
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams Oameswilliams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) / Joel Peters, P. E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; AUn: Jennifer Blount (Jenniferblount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127035 Page 3 of 8
CONCRETE FOR: Pavement SW quadrant from the SW corner 70' N x 40' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
127037A 7 12/6/07 12/13/07 4.00 12.57 3 51,920 4,130
127037B 28 12/6/07 1/3/08
127037C 28 12/6/07 1/3/08
127037D HOLD 12/6/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL SPECIFIED I
TRUCK NO. : 26 SLUMP: 5.25
TICKET NO. : 1154955 AIR TEMP. : 40
ACCUMULATED YDS: 120 of 600 MIX TEMP. : 71
TIME CAST: 3:37 AM AIR CONTENT: 3.7
TIME IN TRUCK: 37 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends: tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
fl Similar to T,,~ " . n";nIDn
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Un bonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138: Air Content ASTM C173/ C231: Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com) f70~, ~
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) /
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P.E.
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply oniy to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127035 Page 4 of 8
CONCRETE FOR: Pavement SW quadrant from the SW corner 90' E x 80' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
127038A 7 12/6/07 12/13/07 4.00 12.57 3 56,120 4,470
127038B 28 12/6/07 1/3/08
127038C 28 12/6/07 1/3/08
1270380 HOLD 12/6/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 1015 SLUMP: 5.75
TICKET NO. : 1154986 AIR TEMP. : 40
ACCUMULATED YDS : 190 of 600 MIX TEMP.: 71
TIME CAST: 4:17 AM AIR CONTENT: 3.0
TIME IN TRUCK: 32 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends: tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
R . ,nnint<>rl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) rr;;~-
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams Games.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) ~oel Peters, P.E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppe"; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127035 Page 5 of 8
CONCRETE FOR: Pavement NW quadrant from NW corner 200' S x 50' E
CYLINDER AGE DATE DATE AVG.CYLlNDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD,LBS STRENGTH, PSI
127039A 7 12/6/07 12/13/07 4.00 12.57 3 43,240 3,440
127039B 28 12/6/07 1/3/08
127039C 28 12/6/07 1/3/08
127039D HOLD 12/6/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
r ACTUAL SPECIFIED
TRUCK NO. : 905 SLUMP: 5.75
TICKET NO. : 1155012 AIR TEMP. : 40
ACCUMULATED YDS: 240 of 600 MIX TEMP. : 69
TIME CAST: 5:32 AM AIR CONTENT: 2.5
TIME IN TRUCK: 65min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends. less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 ~ " nnint~rl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) crJ~
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) I
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P.E.
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not ,ntended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127035 Page 6 of 8
CONCRETE FOR: Pavement NW quadrant from NW corner 200' S x 90' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
127040A 7 12/6/07 12/13/07 4.00 12.57 3 51,380 4,090
127040B 28 12/6/07 1/3/08
127040C 28 12/6/07 1/3/08
1270400 HOLD 12/6/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
I ACTUAL I SPECIFIED
TRUCK NO. : 5019 SLUMP: 4.5
TICKET NO. : 1155075 AIR TEMP. : 40
ACCUMULATED YDS: 300 of 600 MIX TEMP. : 73
TIME CAST: 6:06 AM AIR CONTENT: 3.4
TIME IN TRUCK: 29 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT : N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 ,",,,. _n'" nf " nnin".rl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173 / C231; Temperature ASTM C1064
Reports to:
Starling Richardson Cons\.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com) GrJt/~!;/
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) f Joel Peters, P,E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently Identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127035 Page 7 of 8
CONCRETE FOR: Pavement NW quadrant from NW corner 70' S x 50' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD,LBS STRENGTH, PSI
127041A 7 12/6/07 12/13/07 4.00 12.57 3 48,990 3,900
127041B 28 12/6/07 1/3/08
127041C 28 12/6/07 1/3/08
1270410 HOLD 12/6/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED
TRUCK NO. : 1015 SLUMP: 6.0
TICKET NO. : 1155108 AIR TEMP. : 40
ACCUMULATED YDS: 340 of 600 MIX TEMP. : 74
TIME CAST: 6:49 AM AIR CONTENT: 3.5
TIME IN TRUCK: 39min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
~ . nnint..n
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
o Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples laken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173 I C231, Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com) G~ ;&~
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) I Joel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l 0 E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 127035 Page 8 of 8
CONCRETE FOR: Pavement NW quadrant from NW corner 60' S x 100' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
127042A 7 12/6/07 12/13/07 4.00 12.57 3 48,970 3,900
127042B 28 12/6/07 1/3/08
127042C 28 12/6/07 1/3/08
1270420 HOLD 12/6/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL I SPECIFIED
TRUCK NO. : 905 SLUMP: 6.0
TICKET NO. : 1155206 AIR TEMP. : 45
ACCUMULATED YDS : 400 of 450 MIX TEMP. : 75
TIME CAST: 7:24 AM AIR CONTENT: 3.1
TIME IN TRUCK: 27 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT : N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps. no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
fl Similar In Tvn,,!i hilI "nd
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173 I C231; Temperature ASTM C1 064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com) (bL ~~
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams uames.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) /
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P,E.
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of OUf name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 117093 Page 1 of 2
I CONCRETE FOR: Grade beam T-6.8 to VA I
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
117093A 7 11/15/07 11/22/07 4.00 12.57 N/A 49,870 3,970
117093B f28 11/15/07 12/13/07 4.00 12.57 3 64,570 '- 5,140
117093C 28 11/15/07 12/13/07 4.00 12.57 3 64,060 5,100
1170930 HOLD 11/15/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,120
MIX DESIGN: DOOOOOO09355 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL . r SPECIFIED
TRUCK NO. : 80 SLUMP: 5.5
TICKET NO. : 1140661 AIR TEMP. : 70
ACCUMULATED YDS : 30 of 60 MIX TEMP. : 77
TIME CAST: 2:51 PM AIR CONTENT: N/A
TIME IN TRUCK: 26 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
fi Simil"r In Tvn.. fi hili ..nd nf ""linn"r .
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Un bonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C 173 I C231; Temperature ASTM C 1 064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) (h/~~
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) 7JOe' Peters, P.E.
Jacobs: Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this repon are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 12/13/2007
TECHNICIAN: J. Mayo REPORT NO: 117093 Page 2 of 2
CONCRETE FOR: Pier caps R-4 to L.9-4, L.9-6 to R-6
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD,LBS STRENGTH, PSI
117094A 7 11/15/07 11/22/07 4.00 12.57 N/A 52,220 4,160
117094B 28 11/15/07 12/13/07 4.00 12.57 3 66,210 5,270
117094C 28 11/15/07 12/13/07 4.00 12.57 3 65,270 5,190
1170940 HOLD 11/15/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,230
MIX DESIGN: DOOOOOO09355 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 26 SLUMP: 5.0
TICKET NO. : 1140724 AIR TEMP. : 70
ACCUMULATED YDS: 60 of 60 MIX TEMP. : 83
TIME CAST: 3:27 PM AIR CONTENT: N/A
TIME IN TRUCK: 32 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 ," ,",,,t.."n
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143:
Unit Weight ASTM C138; Air Content ASTM C173/ C231; TemperatureASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) ();p- 1:/~
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) j/
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P.E.
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclUSive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.