Duke Lesley 3C-LR071115
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299178
Project No.: 0711530
Date of Service: 09/19/2007
Report Date: 11/15/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 7752 PW
Placement Date: 09/19/2007
Weather Conditions: Cloudy
Time Sampled: 03:10am
Temperature - Air: 760F
Truck No: 110
Air Content: NA
Overall Placement Location:
Beltline Road I Highway 635
Measured
Slump
(inches)
5.0
Batch time: 03:03am
Concrete: 800F
Ticket No: 7420
Unit Weight (pet): NA
Sample Location:
South section-southeast corner, section 1
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 09/26/2007 7 6.00 28.27 74,520 2,640 Cone/Split
1 2 10/17/2007 28 6.00 28.27 102,440 3,620 Cone/Split
1 3 10/17/2007 28 6.00 28.27 101,490 3,590 Cone/Split
Average 3,610 *
1 4 11/14/2007 56 6.00 28.27 106,280 3,760 Shear
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject mailer provided by persons or conditions over which we have no control. Our lellers and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the wrillen approval of Rone Engineering Services, Ltd.
(JC/JC) Page 1 of B
Rone Engineering
.
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
Report of Concrete Compressive Strength Test
Report No.: 299178
Project No.: 0711530
Date of Service: 09/19/2007
Report Date: 11/15/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 7752 PW
Placement Date: 09/19/2007
Weather Conditions: Cloudy
Time Sampled: 04:00am
Temperature - Air: 760F
Truck No: 138
Air Content: NA
Overall Placement Location:
Beltline Road I Highway 635
Batch time: 03:42am
Concrete: 800F
Ticket No: 7425
Unit Weight (pct): NA
Measured
Slump
(inches)
5.0
Sample Location:
South section-center, section 1
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in") (Ibs) (psi) Type
2 1 09/26/2007 7 6.00 28.27 73,690 2,610 Cone/Split
2 2 10/17/2007 28 6.00 28.27 98,240 3,470 Shear
2 3 10/17/2007 28 6.00 28.27 103,900 3,670 Cone/Split
Average 3,570 "
2 4 11/14/2007 56 6.00 28.27 110,330 3,900 Shear
" Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(JC/JC) Page 2 of 8
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, 518 600, Houston, TX 77040
4421 Freidrlch, 5te 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299178
Project No.: 0711530
Date of Service: 09/19/2007
Report Date: 11/15/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7752 PW
Placement Date: 09/19/2007
Weather Conditions: Cloudy
Time Sampled: 05:00am
Tern peratu re - Ai r: 760F
Truck No: 109
Air Content: NA
Overall Placement Location:
Beltline Road I Highway 635
Batch time: 04:51am
Concrete: 800F
Ticket No: 7437
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
South section-southwest corner, section 2
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
3 1 09/26/2007 7 6.00 28.27 76,190 2,690 Cone/Split
3 2 10/17/2007 28 6.00 28.27 125,210 4,430 Cone/Split
3 3 10/17/2007 28 6.00 28.27 122,390 4,330 Cone/Split
Average 4,380
3 4 11/14/2007 56 6.00 28.27 136,140 4,810 Cone/Shear
L1MITA TION5: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(JC/JC) Page 3 of8
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, 8te 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299178
Project No.: 0711530
Date of Service: 09/19/2007
Report Date: 11/15/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 7752 PW
Placement Date: 09/19/2007
Weather Conditions: Cloudy
Time Sampled: 06:15am
Temperature - Air: 780F
Truck No: 109
Air Content: NA
Overall Placement Location:
Beltline Road I Highway 635
Measured
Slump
(inches)
5.0
Batch time: 06:05am
Concrete: 820F
Ticket No: 7447
Unit Weight (pet): NA
Sample Location:
South section-southeast corner, section 2
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
4 1 09/26/2007 7 6.00 28.27 95,000 3,360 Cone/Split
4 2 10/17/2007 28 6.00 28.27 125,220 4,430 Cone/Split
4 3 10/17/2007 28 6.00 28.27 119,570 4,230 Cone/Split
Average 4,330
4 4 11/14/2007 56 6.00 28.27 133,060 4,710 Cone/Shear
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar SUbject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(JC/JC) Page 4 of 8
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299178
Project No.: 0711530
Date of Service: 09/19/2007
Report Date: 11/15/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7752 PW
Placement Date: 09/19/2007
Weather Conditions: Cloudy
Time Sampled: 08:00am
Temperature - Air: 780F
Truck No: 110
Air Content: NA
Overall Placement Location:
Beltline Road I Highway 635
Batch time: 07:51am
Concrete: 830F
Ticket No: 7457
Unit Weight (pcf): NA
Measured
Slump
(inches)
5.0
Sample Location:
Center section-center, 3rd section
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (inZ) (Ibs) (psi) Type
5 1 09/26/2007 7 6.00 28.27 103,560 3,660 Cone/Split
5 2 10/17/2007 28 6.00 28.27 143,120 5,060 Cone/Split
5 3 10/17/2007 28 6.00 28.27 140,080 4,950 Cone/Split
Average 5,010
5 4 11/14/2007 56 6.00 28.27 156,470 5,530 Cone/Shear
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(JCIJC) Page 5 of 8
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
n01 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299178
Project No.: 0711530
Date of Service: 09/19/2007
Report Date: 11/15/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7752 PW
Placement Date: 09/19/2007
Weather Conditions: Cloudy
Time Sampled: 09:05am
Temperature - Air: 820F
Truck No: 140
Air Content: NA
Overall Placement Location:
Beltline Road I Highway 635
Batch time: 08:58am
Concrete: 850F
Ticket No: 7468
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
Center section-north, northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
6 1 09/26/2007 7 6.00 28.27 106,800 3,780 Cone/Split
6 2 10/17/2007 28 6.00 28.27 139,770 4,940 Cone/Split
6 3 10/17/2007 28 6.00 28.27 143,450 5,070 Cone/Split
Average 5,010
6 4 11/14/2007 56 6.00 28.27 152,780 5,400 Cone/Shear
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(JC/JC) Page 6 of B
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299178
Project No.: 0711530
Date of Service: 09/19/2007
Report Date: 11/15/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placementlocalions, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 7752 PW
Placement Date: 09/19/2007
Weather Conditions: Cloudy
Time Sampled: 10:27am
Temperature - Air: 860F
Truck No: NA
Air Content: NA
Overall Placement Location:
Beltline Road I Highway 635
Measured
Slump
(inches)
5.0
Batch time: 09:51 am
Concrete: 910F
Ticket No: 59014101
Unit Weight (pet): NA
Sample Location:
North section-northeast corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
7 1 09/26/2007 7 6.00 28.27 73,980 2,620 Cone/Split
7 2 10/17/2007 28 6.00 28.27 100,090 3,540 Cone/Split
7 3 10/17/2007 28 6.00 28.27 97,510 3,450 Cone/Split
Average 3,490 *
7 4 11/14/2007 56 6.00 28.27 107,710 3,810 Cone/Split
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variaUon in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or condiUons over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(JCIJC) Page 7 of 8
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freldrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 299178
Project No.: 0711530
Date of Service: 09/19/2007
Report Date: 11/15/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7752 PW
Placement Date: 09/19/2007
Weather Conditions: Cloudy
Time Sampled: 11:21am
Temperature - Air: 900F
Truck No: 140
Air Content: NA
Overall Placement Location:
Beltline Road I Highway 635
Batch time: 11: 14am
Concrete: 950F
Ticket No: 7473
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
North section-northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
8 1 09/26/2007 7 6.00 28.27 73,320 2,590 Cone/Split
8 2 10/17/2007 28 6.00 28.27 98,120 3,470 Cone/Split
8 3 10/17/2007 28 6.00 28.27 99,970 3,540 Cone/Split
Average 3,500 '"
8 4 11/14/2007 56 6.00 28.27 1 08,440 3,840 Shear
'" Does not comply with specified strength
Technician: Jason Shipe Started: 02:30am
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne
(1-ec copy)
1-cc Potter Concrete Attn: Mr. Ryan Skelly
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Altn: Mr. Larry Davis
Finished: 01:00pm Rone Engineering
,~~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(JC/JC) Page 8 of 8