Rone En~==
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client: Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
Report of Concrete Compressive Strength Test
Report No.: 301941
Project No.: 0711530
Date of Service: 10/12/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 9750 PW
Placement Date: 10/12/2007
Weather Conditions: Clear
Time Sampled: 04:30am
Temperature - Air: 670F
Truck No: 136
Air Content: NA
Overall Placement Location:
Panel walls from P27 to P40
Batch time: 04:06am
Concrete: 850F
Ticket No: 7911
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
From P.2B
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in") (Ibs) (psi) Type
1 1 10/16/2007 4 6.00 28.27 106,680 3,770 Cone/Split
1 2 10/16/2007 4 6.00 28.27 107,570 3,800 Cone/Split
Average 3,790
1 3 10/19/2007 7 6.00 28.27 113,190 4,000 Cone/Shear
1 4 11/09/2007 28 6.00 28.27 139,730 4,940 Cone/Split
1 5 11/09/2007 28 6.00 28.27 138,590 4,900 Shear
Average 4,920
1 6 12/07/2007 56 6.00 28.27 172,880 6,110 Cone/Split
Remarks: Water added at site: 5 gallons
Results to superintendent
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in Quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(DM/ED) Page 1 of 2
Rone En2==
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
Report of Concrete Compressive Strength Test
Report No.: 301941
Project No.: 0711530
Date of Service: 10/12/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 9750 PW
Placement Date: 10/12/2007
Weather Conditions: Clear
Time Sampled: 05:30am
Temperature - Air: 640F
Truck No: 134
Air Content: NA
Overall Placement Location:
Panel walls from P27 to P40
Batch time: 05:04am
Concrete: 780F
Ticket No: 7920
Unit Weight (pet): NA
Measu red
Slump
(inches)
5.75
Sample Location:
From P.35
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
2 1 10/16/2007 4 6.00 28.27 109,650 3,880 Cone/Split
2 2 10/16/2007 4 6.00 28.27 107,190 3,790 Cone/Split
Average 3,830
2 3 10/19/2007 7 6.00 28.27 118,860 4,200 Cone/Shear
2 4 11/09/2007 28 6.00 28.27 151,100 5,340 Cone/Split
2 5 11/09/2007 28 6.00 28.27 147,930 5,230 Shear
Average 5,290
2 6 12/07/2007 56 6.00 28.27 170,940 6,050 Cone/Split
Remarks: Water added at site: 5 gallons
Results to superintendent
Technician: Jose Villanueva Started: 04:00am
Report Distribution:
Ori9: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne
(1-ec copy)
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc Potter Concrete Attn: Mr Ryan Skelly
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Attn: Mr. Larry Davis
Finished: 07:45am R E. .
~;;ij
~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(OM/ED) Page 2 of 2
Rone En~~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, 8te 600, Houston, TX 77040
4421 Freidrich, 8te 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 303274
Project No.: 0711530
Date of Service: 10/27/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 5,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 9385
Placement Date: 10/27/2007
Weather Conditions: Sunny
Time Sampled: 08:45am
Temperature - Air: 530F
Truck No: 125
Air Content: 2.2%
Overall Placement Location:
Panel #68
Batch time: 08:12am
Concrete: 730F
Ticket No: 8319
Unit Weight (pcf): NA
MeasiJred
Slump
(inches)
6.5
Sample Location:
Same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/30/2007 3 6.00 28.27 106,310 3,760 Cone/Split
1 2 10/30/2007 3 6.00 28.27 102,560 3,630 Cone/Split
Average 3,690
3 11/03/2007 7 6.00 28.27 126,390 4,470 Shear
1 4 11/24/2007 28 6.00 28.27 176,440 6,240 Cone/Split
1 5 11/24/2007 28 6.00 28.27 177,530 6,280 Cone/Split
Average 6,260
1 6 12/22/2007 56
Technician: Alejandro Avendano Started: 08:00am
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne
(1-ec copy)
1-cc Potter Concrete Attn: Mr Ryan Skelly
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Attn: Mr. Larry Davis
Finished:
09:45am R E. .
~dii
~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CHfED) Page 1 of 1
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, 8te 600, Houston, TX 77040
4421 Freidrich, 8te 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 303109
Project No.: 0711530
Date of Service: 10/26/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: On site
Specification Req uirements
Strength: 4,000 psi @28 days
Slump (in.): 3" - 5"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 9385
Placement Date: 10/26/2007
Weather Conditions: Sunny
Time Sampled: 09:30am
Temperature - Air: 580F
Truck No: 118
Air Content: NA
Overall Placement Location:
Spandle panels SP41, SP42, SP90, SP91
Measured
Slump
(inches)
4.75
Batch time: 09: 13am
Concrete: 740F
Ticket No: 8221
Unit Weight (pcf): NA
Sample Location:
Panels SP41, SP42
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 10/27/2007 1 6.00 28.27 71,930 2,540 Cone/Split
1 2 10/28/2007 2 6.00 28.27 100,550 3,560 Cone/Split
1 3 11/02/2007 7 6.00 28.27 138,960 4,910 Cone/Split
1 4 11/23/2007 28 6.00 28.27 193,810 6,850 Shear
1 5 11/23/2007 28 6.00 28.27 193,590 6,850 Cone/Split
Average 6,850
1 6 12/21/2007 56
Technician: Bruce Eberts Started: 09:30am Finished:
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne
(1-ec copy)
1-cc Potter Concrete Attn: Mr Ryan Skelly
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Attn: Mr. Larry Davis
1 0:30am R E
~2
~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 1 of 1
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304806
Project No.: 0711530
Date of Service: 11/08/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: TXI
Plant: 141
Specification Requirements
Strength: 3,500 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 5%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 88274
Placement Date: 11/08/2007
Weather Conditions: Sunny
Time Sampled: 09:00am
Temperature - Air: 510F
Truck No: 1066
Air Content: 4.6%
Overall Placement Location:
Paving, sidewalk, building 1
Batch time: 08:31am
Concrete: 730F
Ticket No: 569396
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
120 yards west from building 1 intersection
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (inZ) (Ibs) (psi) Type
1 1 11/15/2007 7 6.00 28.27 128,720 4,550 Cone/Split
1 2 12/06/2007 28 6.00 28.27 138,430 4,900 Cone/Split
1 3 12/06/2007 28 6.00 28.27 139,800 4,940 Cone/Split
Average 4,920
1 4 01/03/2008 56
Started: 08:30am Finished: 11 :OOam
Technician: David Best
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byme
(1-ec copy)
1-cc City of Coppel! Attn: Mr. Lee Stone
1-cc Potter Concrete Attn: Mr Ryan Skelly
1-cc City of Coppel! Attn: Mr. Lee Stone
1-cc City of Coppel! Attn: Mr. Larry Davis
Rone Engineering
p~
~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/ED) Page 1 of 1
Rone En2==
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
Report of Concrete Compressive Strength Test
Report No.: 304333
Project No.: 0711530
Date of Service: 11/05/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: On site
Specification Req uirements
Strength: 5,000 psi @ 28 days
Slump (in.): 4" - 6"
Air (%): NA
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 9385 PW
Placement Date: 11/05/2007
Weather Conditions: Sunny, windy
Time Sampled: 12:30pm Batch time:
Temperature - Air: 760F Concrete: 780F
Truck No: 140 Ticket No:
Air Content: 1.4% Unit Weight (pcf): NA
Overall Placement Location:
Tilt walls - DP1, DP2, DP3, DP4, DP5, DP6, SP21A, SP21 B, SP21 C
Measured
Slump
(inches)
5.0
Sample Location:
DP3
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 11/08/2007 3 6.00 28.27 90,850 3,210 Cone/Split
1 2 11/12/2007 7 6.00 28.27 115,290 4,080 Cone/Split
1 3 12/03/2007 28 6.00 28.27 152,400 5,390 Shear
1 4 12/03/2007 28 6.00 28.27 162,140 5,730 Cone/Split
Average 5,560
1 5 12/31/2007 56
Technician: Javier Martinez
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne
(1-ec copy)
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc Potter Concrete Attn: Mr Ryan Skelly
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Attn: Mr. Larry Davis
Started: 11 :15am Finished: 01 :30pm
Rone Engineering
,~
~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/ED) Page 1 of 1
Rone En~=a
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
89D8 Ambassador Row, Dallas, TX 75247
77D1 W Little York, Ste 600, Houston, TX 77D4D
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 7752
Placement Date: 11/06/2007
Weather Conditions: Clear
Time Sampled: 04:45am
Temperature - Air: 500F
Truck No: 132
Air Content: 7.1 %
Overall Placement Location:
West parking
Measured
Slump
(inches)
6.0
Batch time: 04:39am
Concrete: 700F
Ticket No: 8865
Unit Weight (pet): NA
Sample Location:
20' east from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 11/13/2007 7 6.00 28.27 94,460 3,340 Shear
1 2 12/04/2007 28 6.00 28.27 123,500 4,370 Cone/Split
1 3 12/04/2007 28 6.00 28.27 112,760 3,990 Shear
Average 4,180
1 4 01/01/2008 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CHlKW) Page 1 of 9
Rone Eni~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7752
Placement Date: 11/06/2007
Weather Conditions: Clear
Time Sampled: 05:35am
Temperature - Air: 510F
Truck No: 107
Air Content: 7.0%
Overall Placement Location:
West parking
Batch time: 05: 19am
Concrete: 680F
Ticket No: 8873
Unit Weight (pcf): NA
Measured
Slump
(inches)
5.0
Sample Location:
75' east from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
2 1 11/13/2007 7 6.00 28.27 119,710 4,230 Cone/Split
2 2 12/04/2007 28 6.00 28.27 149,530 5,290 Cone/Split
2 3 12/04/2007 28 6.00 28.27 147,130 5,200 Cone/Split
Average 5,250
2 4 01/01/2008 56
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing, We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd,
(CH/KW) Page 2 on
Rone Engineering
.
Client: Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 07:30am
Temperature - Air: 510F
Truck No: 132
Air Content: 6.2%
Overall Placement Location:
West parking
Measured
Slump
(inches)
5.0
Batch time: 06:47am
Concrete: 680F
Ticket No: 8885
Unit Weight (pet): NA
Sample Location:
15' east, 100' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
3 1 11/13/2007 7 6.00 28.27 104,160 3,680 Cone/Split
3 2 12/04/2007 28 6.00 28.27 125,740 4,450 Shear
3 3 12/04/2007 28 6.00 28.27 120,340 4,260 Cone/Split
Average 4,350
3 4 01/01/2008 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 3 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 07:55am
Temperature - Air: 510F
Truck No: 106
Air Content: 6.3%
Overall Placement Location:
West parking
Measured
Slump
(inches)
5.5
Batch time: 07:47am
Concrete: 680F
Ticket No: 8892
Unit Weight (pct): NA
Sample Location:
10' east, 125' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
4 1 11/13/2007 7 6.00 28.27 96,400 3,410 Cone/Split
4 2 12/04/2007 28 6.00 28.27 127,440 4,510 Cone/Split
4 3 12/04/2007 28 6.00 28.27 123,330 4,360 Shear
Average 4,430
4 4 01/01/2008 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 4 of 9
Rone En2==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 09:13am
Temperature - Air: 540F
Truck No: 107
Air Content: 6.0%
Overall Placement Location:
West parking
Batch time: 09:07am
Concrete: 710F
Ticket No: 8905
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
30' east, 125' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
5 1 11/13/2007 7 6.00 28.27 101,440 3,590 Shear
5 2 12/04/2007 28 6.00 28.27 130,600 4,620 Shear
5 3 12/04/2007 28 6.00 28.27 123,960 4,380 Shear
Average 4,500
5 4 01/01/2008 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CHlKW) Page 5 of 9
Rone En2==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 11 :OOam
Temperature - Air: 590F
Truck No: 141
Air Content: 4.7%
Overall Placement Location:
West parking
Batch time: 10:41am
Concrete: 710F
Ticket No: 8917
Unit Weight (pcf): NA
Measured
Slump
(inches)
5.0
Sample Location:
20' east, 150' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
6 1 11/13/2007 7 6.00 28.27 108,720 3,850 Cone/Split
6 2 12/04/2007 28 6.00 28.27 146,440 5,180 Cone/Split
6 3 12/04/2007 28 6.00 28.27 134,230 4,750 Shear
Average 4,960
6 4 01/01/2008 56
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 6 of 9
Rone En~==
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, 8te 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 12:03pm
Temperature - Air: 590F
Truck No: 144
Air Content: 6.2%
Overall Placement Location:
West parking
Measured
Slump
(inches)
5.0
Batch time: 11 :59am
Concrete: 690F
Ticket No: 8930
Unit Weight (pct): NA
Sample Location:
35' east, 120' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
7 1 11/13/2007 7 6.00 28.27 125,760 4,450 Cone/Split
7 2 12/04/2007 28 6.00 28.27 131,530 4,650 Cone/Split
7 3 12/04/2007 28 6.00 28.27 148,340 5,250 Shear
Average 4,950
7 4 01/01/2008 56
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 7 of 9
Rone En~~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 12:40pm
Temperature - Air: 590F
Truck No: 106
Air Content: 6.0%
Overall Placement Location:
West parking
Measured
Slump
(inches)
5.5
Batch time: 12:31 pm
Concrete: 680F
Ticket No: 8936
Unit Weight (pet): NA
Sample Location:
25' east, 130' from northwest corner
REPORT OF TESTS
Concrete Cqmpressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in") (Ibs) (psi) Type
8 1 11/13/2007 7 6.00 28.27 86,590 3,060 Cone/Split
8 2 12/04/2007 28 6.00 28.27 105,280 3,720 Shear
8 3 12/04/2007 28 6.00 28.27 116,010 4,100 Shear
Average 3,910 *
8 4 01/01/2008 56
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 8 of 9
Rone En2~
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 12/11/2007
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength
Set No. Tested (days) (in) (in2) (Ibs) (psi)
9 1 11/13/2007 7 6.00 28.27 93,050 3,290
9 2 12/04/2007 28 6.00 28.27 117,980 4,170
9 3 12/04/2007 28 6.00 28.27 101,590 3,590
Average 3,880 ..
9 4 01/01/2008 56
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 01 :45pm
Temperature - Air: 590F
Truck No: 132
Air Content: 6.1%
Overall Placement Location:
West parking
Batch time: 01 :28pm
Concrete: 700F
Ticket No: 8945
Unit Weight (pet): NA
Measu red
Slump
(inches)
5.0
Sample Location:
25' east, 120' from northwest corner
Fracture
Type
Shear
Cone/Split
Shear
.. Does not comply with specified strength
Remarks: Water added at site: 10 gallons
Started: 03:30am Finished: 05:15pm
Technician: David Best
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byme
(1-ec copy)
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc Potter Concrete Attn: Mr Ryan Skelly
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Attn: Mr. Larry Davis
Rone Engineering
p~~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specifIC samples provided for testing. We assume no responsibility for variation in quality