Duke Lesley 3C-LR080104
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 01/04/2008
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%):, 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7752
Placement Date: 11/06/2007
Weather Conditions: Clear
Time Sampled: 04:45am
Temperature - Air: 500F
Truck No: 132
Air Content: 7.1%
Overall Placement Location:
West parking
Batch time: 04:39am
Concrete: 700F
Ticket No: 8865
Unit Weight (pcf): NA
Measured
Slump
(inches)
6.0
Sam pie Location:
20' east from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 11/13/2007 7 6.00 28.27 94,460 3,340 Shear
1 2 12/04/2007 28 6.00 28.27 123,500 4,370 Cone/Split
1 3 12/04/2007 28 6.00 28.27 112,760 3,990 Shear
Average 4,180
1 4 01/01/2008 56 6.00 28.27 156,120 5,520 Cone/Split
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 1 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 01/04/2008
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive stFength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7752
Placement Date: 11/06/2007
Weather Conditions: Clear
Time Sampled: 05:35am
Temperature - Air: 510F
Truck No: 107
Air Content: 7.0%
Overall Placement Location:
West parking
Batch time: 05:19am
Concrete: 680F
Ticket No: 8873
Unit Weight (pcf): NA
Measured
Slump
(inches)
5.0
Sample Location:
75' east from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
2 1 11/13/2007 7 6.00 28.27 119,710 4,230 Cone/Split
2 2 12/04/2007 28 6.00 28.27 149,530 5,290 Cone/Split
2 3 12/04/2007 28 6.00 28.27 147,130 5,200 Cone/Split
Average 5,250
2 4 01101/2008 56 6.00 28.27 192,200 6,800 Cone/Split
Remarks: Water added at site: 5 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 2 of9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 01/04/2008
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 07:30am
Temperature - Air: 510F
Truck No: 132
Air Content: 6.2%
Overall Placement Location:
West parking
Batch time: 06:47am
Concrete: 680F
Ticket No: 8885
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
15' east, 100' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
3 1 11/13/2007 7 6.00 28.27 104,160 3,680 Cone/Split
3 2 12/04/2007 28 6.00 28.27 125,740 4,450 Shear
3 3 12/04/2007 28 6.00 28.27 120,340 4,260 Cone/Split
Average 4,350
3 4 01/01/2008 56 6.00 28.27 138,260 4,890 Cone/Split
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 3 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 01/04/2008
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 07:55am
Temperature - Air: 510F
Truck No: 106
Air Content: 6.3%
Overall Placement Location:
West parking
Measured
Slump
(inches)
5.5
Batch time: 07:47am
Concrete: 680F
Ticket No: 8892
Unit Weight (pcf): NA
Sample Location:
10' east, 125' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
4 1 11/13/2007 7 6.00 28.27 96,400 3,410 Cone/Split
4 2 12/04/2007 28 6.00 28.27 127,440 4,510 Cone/Split
4 3 12/04/2007 28 6.00 28.27 123,330 4,360 Shear
Average 4,430
4 4 01/01/2008 56 6.00 28.27 144,210 5,100 Cone/Split
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 4 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 01/04/2008
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 09:13am
Temperature - Air: 540F
Truck No: 107
Air Content: 6.0%
Overall Placement Location:
West parking
Measured
Slump
(inches)
5.0
Batch time: 09:07am
Concrete: 710F
Ticket No: 8905
Unit Weight (pet): NA
Sample Location:
30' east, 125' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
5 1 11/13/2007 7 6.00 28.27 101,440 3,590 Shear
5 2 12/04/2007 28 6.00 28.27 130,600 4,620 Shear
5 3 12/04/2007 28 6.00 28.27 123,960 4,380 Shear
Average 4,500
5 4 01/01/2008 56 6.00 28.27 173,810 6,150 Shear
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 5 of9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 01/04/2008
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 11 :OOam
Temperature - Air: 590F
Truck No: 141
Air Content: 4.7%
Overall Placement Location:
West parking
Measured
Slump
(inches)
5.0
Batch time: 10:41 am
Concrete: 710F
Ticket No: 8917
Unit Weight (pet): NA
Sample Location:
20' east, 150' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
6 1 11/13/2007 7 6.00 28.27 108,720 3,850 Cone/Split
6 2 12/04/2007 28 6.00 28.27 146,440 5,180 Cone/Split
6 3 12/04/2007 28 6.00 28.27 134,230 4,750 Shear
Average 4,960
6 4 01/01/2008 56 6.00 28.27 174,160 6,160 Shear
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, ltd.
(CH/KW) Page 6 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
770.1 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 01/04/2008
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placementlocalions, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 12:03pm
Temperature - Air: 590F
Truck No: 144
Air Content: 6.2%
Overall Placement Location:
West parking
Batch time: 11 :59am
Concrete: 690F
Ticket No: 8930
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Sample Location:
35' east, 120' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
7 1 11/13/2007 7 6.00 28.27 125,760 4,450 Cone/Split
7 2 12/04/2007 28 6.00 28.27 131,530 4,650 Cone/Split
7 3 12/04/2007 28 6.00 28.27 148,340 5,250 Shear
Average 4,950
7 4 01/01/2008 56 6.00 28.27 173,500 6,140 Shear
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 7 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 01/04/2008
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 12:40pm
Temperature - Air: 590F
Truck No: 106
Air Content: 6.0%
Overall Placement Location:
West parking
Measured
Slump
(inches)
5.5
Batch time: 12:31pm
Concrete: 680F
Ticket No: 8936
Unit Weight (pcf): NA
Sample Location:
25' east, 130' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (inZ) (Ibs) (psi) Type
8 1 11/13/2007 7 6.00 28.27 86,590 3,060 Cone/Split
8 2 12/04/2007 28 6.00 28.27 105,280 3,720 Shear
8 3 12/04/2007 28 6.00 28.27 116,010 4,100 Shear
Average 3,910 *
8 4 01/01/2008 56 6.00 28.27 135,550 4,790 Shear
* Does not comply with specified strength
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(CH/KW) Page 8 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 304448
Project No.: 0711530
Date of Service: 11/06/2007
Report Date: 01/04/2008
Project: Point West Office I
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design I.D.: 7752
Placement Date: 11/06/2007
Weather Conditions: Sunny
Time Sampled: 01 :45pm
Temperature - Air: 590F
Truck No: 132
Air Content: 6.1 %
Overall Placement Location:
West parking
Measured
Slump
(inches)
5.0
Batch time: 01 :28pm
Concrete: 700F
Ticket No: 8945
Unit Weight (pet): NA
Sample Location:
25' east, 120' from northwest corner
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
9 1 11/13/2007 7 6.00 28.27 93,050 3,290 Shear
9 2 12/04/2007 28 6.00 28.27 117,980 4,170 Cone/Split
9 3 12/04/2007 28 6.00 28.27 101,590 3,590 Shear
Average 3,880 *
9 4 01/01/2008 56 6.00 28.27 129,910 4,590 Shear
* Does not comply with specified strength
Technician: David Best Started: 03:30am
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne
(1-ec copy)
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc Potter Concrete Attn: Mr Ryan Skelly
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Attn: Mr. Larry Davis
Remarks: Water added at site: 10 gallons
Finished: 05:15pm Rone Engineering
~~
J
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd.
(CH/KW) Page 9 of 9