Northlake College-LR080102
TECHNICIAN: J. Mayo
KLEINFELDER
YLlNDER COMPRESSIVE STRENGTH REPORT
PROJECT: North Lake College, N Campus
W Sandy Lake Road @ SH 121
PROJECT NO: 87015
REPORT DATE: 1/2/2008
REPORT NO: 127029
Page 1 of 6
CONCRETE FOR: Firelane on the W side of S parking area from the NW corner 15' W x 10' S
CYLINDER AGE
MARK DAYS
127029A 7
1270298 28
127029C 28
1270290 HOLD
DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
12/5/07 12/12/07 4.00 12.57 5 57,700 4,590
12/5/07 1/2/08 4.00 12.57 1 70,410 5,600
12/5/07 1/2/08 4.00 12.57 1 72,340 5,760
12/5/07 HOLD
SUPPLIER: Southern Star
MIX DESIGN: 000000007725
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
TRUCK NO. :
TICKET NO. :
ACCUMULATED YDS:
TIME CAST:
TIME IN TRUCK:
WEATHER:
AVERAGE 28 DAY STRENGTH: 5,680
28 DAY STRENGTH REQUIREMENT: 4,000
84
1153744
40 of 300
5:01 AM
61 min
Clear
SPECIFIED
SLUMP:
AIR TEMP. :
MIX TEMP.:
AIR CONTENT:
WATER ADDED (gal) :
UNIT WEIGHT:
ACTUAL
6.0
40
74
2.6
o
N/A
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area. diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads.
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable. the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu)
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not Intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
KLEIN FELDER
Joel Peters, P.E.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/2/2008
TECHNICIAN: J. Mayo REPORT NO: 127029 Page 2 of 6
CONCRETE FOR: Firelane on the W side of S parking area from the NW corner 15' W x 130' S
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
127030A 7 12/5/07 12/12/07 4.00 12.57 5 50,960 4,060
127030B 28 12/5/07 1/2/08 4.00 12.57 2 67,260 5,350
127030C 28 12/5/07 1 /2/08 4.00 12.57 1 70,410 5,600
1270300 HOLD 12/5/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,475
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
r ACTUAL T SPECIFIED
TRUCK NO. : 1015 SLUMP: 7.0
TICKET NO. : 1153766 AIR TEMP.: 40
ACCUMULATED YDS: 70 of 300 MIX TEMP. : 74
TIME CAST: 5:36 AM AIR CONTENT: 1.6
TIME IN TRUCK: 81 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 . . ~ " nnint..d
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
o Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231: Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) (b "/&IU?
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) I
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P.E.
Jacobs; Altn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppel!; Attn: Larry Davis
1- City of Coppel!; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/2/2008
TECHNICIAN: J. Mayo REPORT NO: 127029 Page 3 of 6
CONCRETE FOR: Firelane on the W side of S parking area from the NW corner 15' W x 230' S
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD,LBS STRENGTH, PSI
127031A 7 12/5/07 12/12/07 4.00 12.57 3 55,880 4,450
127031B 28 12/5/07 1/2/08 4.00 12.57 1 72,920 5,800
127031C 28 12/5/07 1/2/08 4.00 12.57 1 68,950 5,490
1270310 HOLD 12/5/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,645
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 39 SLUMP: 4.5
TICKET NO. : 1153799 AIR TEMP.: 40
ACCUMULATED YDS: 130 of 300 MIX TEMP.: 75
TIME CAST: 7:06 AM AIR CONTENT: 1.8
TIME IN TRUCK: 66min WATER ADDED (gal): 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 . . " ~^i~'a'"
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) (jrd~
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) I
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P. E.
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/2/2008
TECHNICIAN: J. Mayo REPORT NO: 127029 Page 4 of 6
CONCRETE FOR: Pavement from the SE entrance at Royal, 340' W x 30' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
127032A 7 12/5/07 12/12/07 4.00 12.57 5 49,640 3,950
127032B 28 12/5/07 1/2/08 4.00 12.57 3 64,530 5,140
127032C 28 12/5/07 1/2/08 4.00 12.57 3 63,090 5,020
1270320 HOLD 12/5/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,080
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED I
TRUCK NO. : 905 SLUMP: 5.75
TICKET NO. : 1153884 AIR TEMP. : 45
ACCUMULATED YDS: 200 of 300 MIX TEMP. : 71
TIME CAST: 7:46 AM AIR CONTENT: 2.1
TIME IN TRUCK: 49min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends. no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
R . . " hllt..nd
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C 172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C 143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) r;;~~
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) 7 Joel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approvai. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/2/2008
TECHNICIAN: J. Mayo REPORT NO: 127029 Page 5 of 6
CONCRETE FOR: Pavement from the SE entrance at Royal, 240' W x 10' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD,LBS STRENGTH, PSI
127033A 7 12/5/07 12/12/07 4.00 12.57 5 45,980 3,660
127033B 28 12/5/07 1/2/08 4.00 12.57 1 62,250 4,950
127033C 28 12/5/07 1/2/08 4.00 12.57 3 62,880 5,000
1270330 HOLD 12/5/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 4,975
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 28 SLUMP: 5.5
TICKET NO. : 1154002 AIR TEMP. : 45
ACCUMULATED YDS : 240 of 300 MIX TEMP.: 74
TIME CAST: 8:43 AM AIR CONTENT: 2.0
TIME IN TRUCK: 62 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end. vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps),
6 ' , , ,oointed.
NOTES: . Compressive strengths determined in accordance with ASTM C39, . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others, . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted, . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable, . When applicable. the following test procedures were used: Slump ASTM C143;
Unit WeightASTM C138; Air ContentASTM C173/ C231: Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com) Ood~
DCCCD Bond Office; Alln: Brenda Spinelli (brenda,spinelli@dcccd,edu)
DCCCD Bond Office; Alln: James Williams (james,williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike,daniels@dcccd,edu) IJOel Peters, P.E. /
Jacobs; Alln: Andrea Stogner (Andrea,stogner@jacobs,com)
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs,com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained end apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/2/2008
TECHNICIAN: J. Mayo REPORT NO: 127029 Page 6 of 6
CONCRETE FOR: Pavement from the SE entrance at Royal, 130' W x 5' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA IN.2 TYPE LOAD,LBS STRENGTH, PSI
127034A 7 12/5/07 12/12/07 4.00 12.57 3 51,770 4,120
1270348 28 12/5/07 1/2/08 4.00 12.57 2 69,910 5,560
127034C 28 12/5/07 1/2/08 4.00 12.57 2 69,070 5,500
1270340 HOLD 12/5/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,530
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL I SPECIFIED
TRUCK NO. : 39 SLUMP: 5.0
TICKET NO. : 1154165 AIR TEMP. : 50
ACCUMULATED YDS: 290 of 300 MIX TEMP.: 77
TIME CAST: 9:25 AM AIR CONTENT: 2.2
TIME IN TRUCK: 38 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 . . ~ . . nnint..tl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit WeightASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) aJiiZ
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Games.williams@dcccd.edu)
DCCCD Bond Office; Attn; Mike Daniels (mike.daniels@dcccd.edu) {
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P. E.
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.