K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/18/2008
TECHNICIAN: J. Mayo REPORT NO: 127084 Page 1 of 7
CONCRETE FOR: Pavement SE side of Area A 60' S x 20' W
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA IN.2 TYPE LOAD, LBS STRENGTH, PSI
127084A 5 12/20/07 12/25/07 4.00 12.57 5 55,840 4,440
127084B 7 12/20/07 12/27/07 4.00 12.57 3 58,820 4,680
127084C 28 12/20/07 1/17/08 3.99 12.50 2 76,630 6,130
1270840 28 12/20/07 1/17/08 3.99 12.50 1 73,780 5,900
127084E HOLD 12/20/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 6.015
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL SPECIFIED)
TRUCK NO. : 1015 SLUMP: 4.25
TICKET NO. : 1163721 AIR TEMP. : 50
ACCUMULATED YDS ; 20 of 400 MIX TEMP. : 71
TIME CAST: 4:32 AM AIR CONTENT: 2.9
TIME IN TRUCK: 77 min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends. less than 1 in (25 mm) of cracking through caps.
2 Well-formed cone on one end. vertical cracks running through caps. no well-defined cone on other end.
3 Columnar vertical cracking through both ends. no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
f\ ,!i hllt..nrl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area. diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable. the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173 / C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Canst.; Alln: Andy Munoz (amunoz@starlingrichardson.com) /1-, ~~
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams Uames.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) ~
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com) ')-Lvo<::l Peters, P.E.
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
Indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/18/2008
TECHNICIAN: J. Mayo REPORT NO: 127084 Page 2 of 7
CONCRETE FOR: Pavement SE corner of Area A 60' E x 100' S
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD,LBS STRENGTH, PSI
127085A 5 12/20/07 12/25/07 4.00 12.57 5 44,910 3,570
127085B 7 12/20/07 12/27/07 4.00 12.57 5 42,490 3,380
127085C 28 12/20/07 1/17/08 3.99 12.50 2 65,190 5,210
1270850 28 12/20/07 1/17/08 3.99 12.50 4 65,210 5,220
127085E HOLD 12/20/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,215
MIX DESIGN: DOOOOOO07725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
I ACTUAL SPECIFIED
TRUCK NO. : 33 SLUMP: 9.5
TICKET NO. : 1163732 AIR TEMP.: 50
ACCUMULATED YDS: 70 of 41 0 MIX TEMP. : 70
TIME CAST: 5:18 AM AIR CONTENT: 4.1
TIME IN TRUCK: 68 min WATER ADDED (gal) : 10
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps. no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 .':imil"r tn Tvnl> 5 . nnintell
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area. diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173 / C231; Temperature ASTM C1 064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /L y:-
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Uames.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) -
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com) ~r Joel Peters, P.E.
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/22/2008
TECHNICIAN: J. Mayo REPORT NO: 127084 Page 3 of 7
CONCRETE FOR: Pavement SE corner of Area A 100' E x 70' S
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
127086A 5 12/20/07 12/25/07 4.00 12.57 5 48,900 3,890
127086B 7 12/20/07 12/27/07 4.00 12.57 5 48,410 3,850
127086C 28 12/20/07 1/17/08 3.99 12.50 4 66,680 5,330
1270860 28 12/20/07 1/17/08 3.99 12.50 5 67,560 5,400
127086E HOLD 12/20/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,365
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL T SPECIFIED
TRUCK NO. : 905 SLUMP: 8.0
TICKET NO. : 1163759 AIR TEMP. : 50
ACCUMULATED YDS: 150 of 400 MIX TEMP.: 71
TIME CAST: 6:11 AM AIR CONTENT: 3.9
TIME IN TRUCK: 61 min WATER ADDED (gal): 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
R 5 hilt An"
NOTES: . Compressive strengths determined in accordance with ASTM C39. ' Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /L r-Z-
DCCCD Bond Office; Altn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams uames.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) C t1.rJoel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Altn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Oist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/22/2008
TECHNICIAN: J. Mayo REPORT NO: 127084 Page 4 of 7
CONCRETE FOR: Pavement SE corner of Area A 90' E X 80' S
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
127087A 5 12/20/07 12/25/07 4.00 12.57 5 44,300 3,530
127087B 7 12/20/07 12/27/07 4.00 12.57 5 45,660 3,630
127087C 28 12/20/07 1/17/08 3.99 12.50 5 59,130 4,730
1270870 28 12/20/07 1/17/08 3.99 12.50 4 57,960 4,640
127087E HOLD 12/20/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 4,685
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED I
TRUCK NO. : 2 SLUMP: 8.75
TICKET NO. : 1163791 AIR TEMP. : 55
ACCUMULATED YDS : 200 of 400 MIX TEMP. : 73
TIME CAST: 6:49 AM AIR CONTENT: 4.0
TIME IN TRUCK: 64 min WATER ADDED (gal) : 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
R - - . : nointed
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143:
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) /LYt-
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Oames.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) C4'r:el Peters, P,E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E L D E R
2211 Century Center 8Ivd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/22/2008
TECHNICIAN: J. Mayo REPORT NO: 127084 Page 5 of 7
CONCRETE FOR: Pavement from Royal Ln. NE entrance 180' W x 15' S (firelane)
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
127088A 5 12/20/07 12/25/07 4.00 12.57 5 49,970 3,980
1270888 7 12/20/07 12/27/07 4.00 12.57 3 53,910 4,290
127088C 28 12/20/07 1/17/08 3.99 12.50 5 68,760 5,500
1270880 28 12/20/07 1/17/08 3.99 12.50 5 65,540 5,240
127088E HOLD 12/20/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,370
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL T SPECIFIED
TRUCK NO. : 1020 SLUMP: 6.25
TICKET NO. : 1163827 AIR TEMP.: 60
ACCUMULATED YDS : 250 of 400 MIX TEMP. : 72
TIME CAST: 7:39 AM AIR CONTENT: 4.4
TIME IN TRUCK: 79min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-fonmed cone on one end, vertical cracks running through caps. no weli-defined cone on other end.
3 Columnar vertical cracking through both ends. no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
6 c; h"t ..nrl
NOTES: . Compressive strengths detenmined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the infonmation contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /L ;:;I! +=-
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) V'~el Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently Identical products The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/18/2008
TECHNICIAN: J. Mayo REPORT NO: 127084 Page 6 of 7
CONCRETE FOR: Pavement from Royal Ln. NE entrance 150' W (firelane)
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD,LBS STRENGTH, PSI
127089A 5 12/20/07 12/25/07 4.00 12.57 5 41,800 3,330
127089B 7 12/20/07 12/27/07 4.00 12.57 3 45,560 3,630
127089C 28 12/20/07 1/17/08 3.99 12.50 3 62,450 4,990
1270890 28 12/20/07 1/17/08 3.99 12.50 3 59,440 4,750
127089E HOLD 12/20/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 4,870
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL SPECIFIED
TRUCK NO. : 33 SLUMP: 8.0
TICKET NO. : 1163988 AIR TEMP. : 60
ACCUMULATED YDS: 300 of 400 MIX TEMP. : 68
TIME CAST: 8:17 AM AIR CONTENT: 4.7
TIME IN TRUCK: 57 min WATER ADDED (gal) : 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
6 . 5 bllt end
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /L~
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) c7 fOr-Joel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/18/2008
TECHNICIAN: J. Mayo REPORT NO: 127084 Page 7 of 7
CONCRETE FOR: Pavement from Royal Ln. firelane entrance 45' W
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD,LBS STRENGTH, PSI
127090A 5 12/20/07 12/25/07 4.00 12.57 5 48,290 3,840
127090B 7 12/20/07 12/27/07 4.00 12.57 3 52,100 4,150
127090C 28 12/20/07 1/17/08 3.99 12.50 4 63,720 5,100
1270900 28 12/20/07 1/17/08 3.99 12.50 3 63,130 5,050
127090E HOLD 12/20/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,075
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
I ACTUAL SPECIFIED I
TRUCK NO. : 5019 SLUMP: 6.0
TICKET NO. : 1164094 AIR TEMP. : 60
ACCUMULATED YDS : 350 of 400 MIX TEMP. : 70
TIME CAST: 9:14 AM AIR CONTENT: 4.8
TIME IN TRUCK: 64 min WATER ADDED (gal) : 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 . . hilt ..nrl nf . nnint..rl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been fumished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Un bonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Cons\.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Cons\.; AUn: Andy Munoz (amunoz@starlingrichardson.com) /1... ~r-
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCO Bond Office; AUn: James Williams Oames.williams@dcccd.edu)
DCCCO Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) 7
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com) -A,- Joel Peters, P.E.
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
KLEINFELDER
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPR.ESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist.
1505 South Lamar, Suite 1015
Dallas, Texas 75215
PROJECT: North Lake College, N Campus
W Sandy Lake Road @ SH 121
PROJECT NO: 87015
TECHNICIAN: J. Mayo
REPORT DATE: 1/18/2008
REPORT NO: 018098
CONCRETE FOR: Pavement left turn lane on Royal Ln., 80' E from SE entrance ramp
CYLINDER AGE
MARK DAYS
018098A 7
018098B 28
018098C 28
0180980 HOLD
DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
1/11/08 1/18/08 3.99 12.50 3 58,220 4,660
1/11/08 2/8/08
1/11/08 2/8/08
1/11/08 HOLD
1011
1177333
1 0 of 40
10:02 AM
42 min
Clear
SPECIFIED
SUPPLIER: Southern Star
MIX DESIGN: D00000007725
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ERAGE 28 DAY STRENGTH:
TRENGTH REQUIREMENT: 4,000
TRUCK NO. :
TICKET NO. :
ACCUMULATED YDS :
TIME CAST:
TIME IN TRUCK:
WEATHER:
SLUMP:
AIR TEMP. :
MIX TEMP. :
AIR CONTENT:
WATER ADDED (gal) :
UNIT WEIGHT:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends. less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
o Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples laken in accordance with ASTM C172 where practicable. When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C13B; Air Content ASTM C173/ C231; Temperature ASTM C1D64
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu)
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
,ndicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entiraty.
KLEINFELDER
KLEINFELDER
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
DAILY REPORT SUMMARY
TO: Dallas County Community College Dist.
1505 South Lamar, Suite 1015
Dallas, Texas 75215
PROJECT: North Lake College, N Campus
W Sandy Lake Road @ SH 121
PROJECT NO: 87015
TECHNICIAN:
WEATHER:
TIME ARRIVED:
TIME DEPARTED:
eyer
REPORT DATE:
REPORT NO.: 018471
TEST DATE: 1/24/2008
PROGRESS REPORT:
- Column 15/B Lejuens not broken.
- Column 17G - NG bridging missing due to interference with kickers during installation.
- 10 screws per lap of decking and welded 100%.
- Other areas viewed were acceptable.
- Welder certifications appear to be current and acceptable.
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu)
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
KLEINFELDER
The results shown on lhis report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.