Northlake College-LR080123
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/23/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 1 of 6
CONCRETE FOR: Pavement; The corner of the NW quadrant in S parking area, 30' S x 50' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018116A 7 1/15/08 1/22/08 4.00 12.57 2 48,010 3,820
018116B 28 1/15/08 2/12/08
018116C 28 1/15/08 2/12/08
0181160 HOLD 1/15/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
I ACTUAL SPECIFIED l
TRUCK NO.: 6233 SLUMP: 6.25
TICKET NO. : 1179463 AIR TEMP.: 40
ACCUMULATED YDS: 50 of 300 MIX TEMP. : 69
TIME CAST: 8:09 AM AIR CONTENT: 3.6
TIME IN TRUCK: 69 min WATER ADDED (gal) : 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps. no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
" ," linder is nn;nt"rl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits COnical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air COntent ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) /L~
OCCCO Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
OCCCO Bond Office; AUn: James Williams Games.williams@dcccd.edu)
DCCCO Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) C/O,- Joel Peters, P.E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/23/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 2 of 6
CONCRETE FOR: Pavement; The corner of the NW quadrant in S parking area, 30' S x 85' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
018117A 7 1/15/08 1/22/08 4.00 12.57 2 52,140 4,150
018117B 28 1/15/08 2/12/08
018117C 28 1/15/08 2/12/08
0181170 HOLD 1/15/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: DOOOOOO07725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED I
TRUCK NO. : 945 SLUMP: 6.50
TICKET NO. : 1179585 AIR TEMP. : 40
ACCUMULATED YDS : 90 of 300 MIX TEMP. : 71
TIME CAST: 8:48 AM AIR CONTENT: 3.1
TIME IN TRUCK: 53 min WATER ADDED (gal) : 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 !':imil"r In Tv",," ~ r i'" nninl..rt
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Un bonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C13B; Air Content ASTM C173 I C231; Temperature ASTM C1 064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com) /1. \. /J
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu) j~~
DCCCD Bond Office; Alln: James Williams Games.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) (%-
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com) or.:foel Peters, P.E.
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/23/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 3 of 6
CONCRETE FOR: Pavement; The corner of the NW quadrant in S parking area, 30' S x 120' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018118A 7 1/15/08 1/22/08 4.00 12.57 3 50,530 4,020
018118B 28 1/15/08 2/12/08
018118C 28 1/15/08 2/12/08
0181180 HOLD 1/15/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 8 SLUMP: 8.25
TICKET NO. : 1179713 AIR TEMP. : 45
ACCUMULATED YDS : 150 of 300 MIX TEMP. : 68
TIME CAST: 9:49 AM AIR CONTENT: 2.8
TIME IN TRUCK: 64 min WATER ADDED (gal) : 10
WEATHER: Clear UNIT WEIGHT: N/A
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1
5 Side fractures at top or bottom (occur commonly with unbonded caps).
'" <:;"";1'" I... Tv..... <; ""t ..nl'j of '. --;~+_...
NOTES: .. Compressive strengths determined in accordance with ASTM C39. .. Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
othelWise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /2~
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) ~ii Joel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclUSive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently Identical products. The use of our name must receive prior writlen approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/23/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 4 of 6
CONCRETE FOR: Pavement; The corner of the NW quadrant in S parking area, 30' S x 180' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018119A 7 1/15/08 1/22/08 4.00 12.57 2 47,930 3,810
018119B 28 1/15/08 2/12/08
018119C 28 1/15/08 2/12/08
0181190 HOLD 1/15/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 1084 SLUMP: 8.75
TICKET NO. : 1179871 AIR TEMP.: 50
ACCUMULATED YDS: 200 of 300 MIX TEMP. : 69
TIME CAST: 10:26 AM AIR CONTENT: 3.4
TIME IN TRUCK: 31 min WATER ADDED (gal) : 10
WEATHER: Clear UNIT WEIGHT : N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
n ,1\ hilI pnrl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been fumished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted' Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable . When applicable, the following test procedures were used: Slump ASTM C143:
Unit Weight ASTM C138; Air Content ASTM C 173 I C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com) /L~
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) -~~oel Peters, P.E.
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclUSive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/23/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 5 of 6
CONCRETE FOR: Pavement; The corner of the NW quadrant in S parking area, 30' S x 210' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018120A 7 1/15/08 1/22/08 4.00 12.57 2 48,700 3,880
018120B 28 1/15/08 2/12/08
018120C 28 1/15/08 2/12/08
0181200 HOLD 1/15/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 26 SLUMP: 6.0
TICKET NO. : 117996 AIR TEMP. : 55
ACCUMULATED YDS : 250 of 300 MIX TEMP.: 73
TIME CAST: 11 :18 AM AIR CONTENT: 3.3
TIME IN TRUCK: 52 min WATER ADDED (gal): 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
n ," ""Ion" ie nn;nlon
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C13B; Air Content ASTM C173/ C231: Temperature ASTM C1064
Reports to:
Starling Richardson Canst.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Canst.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /1, ~J-
OCCCO Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCO Bond Office; Attn: James Williams Games.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) ~~JOel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs: Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/23/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 6 of6
CONCRETE FOR: Pavement from the NE entrance 50' W x 70' S
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD,LBS STRENGTH, PSI
018121A 7 1/15/08 1/22/08 4.00 12.57 2 48,970 3,900
018121B 28 1/15/08 2/12/08
018121C 28 1/15/08 2/12/08
0181210 HOLD 1/15/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED
TRUCK NO. : 1092 SLUMP: 5.75
TICKET NO. : 1180037 AIR TEMP. : 55
ACCUMULATED YDS : 290 of 300 MIX TEMP. : 74
TIME CAST: 11 :54 AM AIR CONTENT: 3.1
TIME IN TRUCK: 49 min WATER ADDED (gal): 0
WEATHER: Clear UNIT WEIGHT : N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends. no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 . ,nnint..rl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit WeightASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /1 y+-
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams uames.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) d ~Joel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.