Northlake College-LR080124
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/24/2008
TECHNICIAN: J. Mayo REPORT NO: 127092 Page 1 of 6
CONCRETE FOR: Slab on grade, SE corner of Area A 130' W x 40' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
127092A 7 12/26/07 1/2/08 4.00 12.57 1 67,700 5,390
127092B 28 12/26/07 1/23/08 4.00 12.57 3 87,060 6,930
127092C 28 12/26/07 1/23/08 4.00 12.57 3 88,630 7,050
1270920 HOLD 12/26/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 6,990
MIX DESIGN: DOOOOOO07772 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
I ACTUAL SPECIFIED 1
TRUCK NO. : 39 SLUMP: 6.0
TICKET NO. : 1166747 AIR TEMP. : 43
ACCUMULATED YDS : 50 of 450 MIX TEMP. : 71
TIME CAST: 8:12 AM AIR CONTENT: N/A
TIME IN TRUCK: 57 min WATER ADDED (gal) : 0
WEATHER: Rain UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
I'. -. . - - . nn;n'".-i
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C13B; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) /1-~
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) C~JOel Peters, P. E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City ofCoppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/24/2008
TECHNICIAN: J. Mayo REPORT NO: 127092 Page 2 of 6
CONCRETE FOR: Slab on grade, SE corner of Area A 110' W x 30' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD,LBS STRENGTH, PSI
127093A 7 12/26/07 1/2/08 4.00 12.57 3 67,460 5,370
127093B 28 12/26/07 1/23/08 4.00 12.57 5 88,100 7,010
127093C 28 12/26/07 1/23/08 4.00 12.57 3 87,720 6,980
1270930 HOLD 12/26/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 6,995
MIX DESIGN: DOOOOOOO7772 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
I ACTUAL SPECIFIED
TRUCK NO. : 103 SLUMP: 6.25
TICKET NO. : 1166751 AIR TEMP.: 43
ACCUMULATED YDS : 90 of 450 MIX TEMP.: 69
TIME CAST: 8:33 AM AIR CONTENT: N/A
TIME IN TRUCK: 58min WATER ADDED (gal) : 0
WEATHER: Rain UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no craCking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
6 . nn;nt.,rl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Un bonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C 172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C 143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Altn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Altn: Andy Munoz (amunoz@starlingrichardson.com) /LXk
DCCCD Bond Office; Altn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Altn: James Williams Games.williams@dcccd.edu)
DCCCD Bond Office; Altn: Mike Daniels (mike.daniels@dcccd.edu) C~rJOel Peters, P.E.
Jacobs; Altn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Altn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Altn: Larry Davis
1- City of Coppell; Altn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 CenturyCenter8Ivd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/24/2008
TECHNICIAN: J. Mayo REPORT NO: 127092 Page 3 of 6
CONCRETE FOR: Slab on grade, SE corner of Area A 90' W x 60' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA.IN.2 TYPE LOAD, LBS STRENGTH, PSI
127094A 7 12/26/07 1/2/08 4.00 12.57 1 62,900 5,010
1270948 28 12/26/07 1/23/08 4.00 12.57 2 82,070 6,530
127094C 28 12/26/07 1/23/08 4.00 12.57 3 83,160 6,620
127094D HOLD 12/26/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 6,575
MIX DESIGN: 000000007772 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED
TRUCK NO. : 905 SLUMP: 3.0
TICKET NO. : 1166757 AIR TEMP.: 43
ACCUMULATED YDS : 150 of 450 MIX TEMP.: 69
TIME CAST: 8:51 AM AIR CONTENT: N/A
TIME IN TRUCK: 33min WATER ADDED (gal): 5
WEATHER: Cloudy with rain UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 . nnint..ri
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173 / C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /L ~*-
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) c:;r-~JOel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identicai products. The use of our name must receiva prior written approval. Raports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/24/2008
TECHNICIAN: J. Mayo REPORT NO: 127092 Page 4 of 6
CONCRETE FOR: Slab on grade, SE corner of Area A 60' W X 80' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA.IN.2 TYPE LOAD, LBS STRENGTH, PSI
127095A 7 12/26/07 1/2/08 4.00 12.57 1 58,960 4,690
127095B 28 12/26/07 1/23/08 4.00 12.57 3 76,950 6,120
127095C 28 12/26/07 1/23/08 4.00 12.57 3 76,480 6,090
1270950 HOLD 12/26/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 6,105
MIX DESIGN: 000000007772 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED I
TRUCK NO. : 1097 SLUMP: 5.5
TICKET NO. : 1166764 AIR TEMP. : 45
ACCUMULATED YDS : 200 of 450 MIX TEMP. : 74
TIME CAST: 9:37 AM AIR CONTENT: N/A
TIME IN TRUCK: 33min WATER ADDED (gal) : 0
WEATHER: Cloudy with rain UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends. less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
F; . . 5 hlll..nd . cainled
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) ~~
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) c::;/ 4..- Joel Peters, P.E.
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Alln; Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samplas tested and/or inspected. They are not intended to be
Indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/24/2008
TECHNICIAN: J. Mayo REPORT NO: 127092 Page 5 of 6
CONCRETE FOR: Slab on grade, SE corner of Area A 20' W x 35' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA IN.2 TYPE LOAD, LBS STRENGTH, PSI
127096A 7 12/26/07 1/2/08 4.00 12.57 1 62,810 5,000
127096B 28 12/26/07 1/23/08 4.00 12.57 2 78,250 6,230
127096C 28 12/26/07 1/23/08 4.00 12.57 4 78,890 6,280
1270960 HOLD 12/26/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 6,255
MIX DESIGN: DOOOOOOO7772 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED I
TRUCK NO. : 39 SLUMP: 5.75
TICKET NO. : 1166771 AIR TEMP. : 45
ACCUMULATED YDS : 250 of 450 MIX TEMP. : 72
TIME CAST: 10:12 AM AIR CONTENT: N/A
TIME IN TRUCK: 27min WATER ADDED (gal) : 5
WEATHER: Rain UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end. vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 . .
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
, Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C13B; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com) /2~
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams Oames.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) ~ -h,....Joel Peters, P.E.
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/24/2008
TECHNICIAN: J. Mayo REPORT NO: 127092 Page 6 of 6
CONCRETE FOR: Slab on grade, SE corner of Area A 80' W X 50' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD,LBS STRENGTH, PSI
127097A 7 12/26/07 1/2/08 4.00 12.57 1 63,280 5,040
127097B 28 12/26/07 1/23/08 4.00 12.57 3 84,860 6,750
127097C 28 12/26/07 1/23/08 4.00 12.57 2 83,800 6,670
1270970 HOLD 12/26/07 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 6,710
MIX DESIGN: 000000007772 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL SPECIFIED I
TRUCK NO. : 1020 SLUMP: 5.5
TICKET NO. : 1166779 AIR TEMP. : 40
ACCUMULATED YDS: 290 of 450 MIX TEMP. : 70
TIME CAST: 10:59 AM AIR CONTENT: N/A
TIME IN TRUCK: 33min WATER ADDED (gal) : 0
WEATHER: Rain UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
R 5 hilt ..nrl
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit WeightASTM C138; Air ContentASTM C173/ C231; TemperatureASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) X
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu) /2
DCCCD Bond Office; AUn: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) ~~JOel Peters, P.E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; AUn: Lee Stone