Gateway BP(3.1)-LR071217 Rone Eni== Client: Transwestern Commercial Services 5001 Spring Valley Dallas, TX 75244 8908 Ambassador Row, Dallas, TX 75247 n01 W Little York, ste 600, Houston, TX 77040 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 307204 Project No.: 0712786 Date of Service: 12/04/2007 Report Date: 12/17/2007 Project: Gateway Business Center Cappell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Constructors & Associates Concrete Supplier: Redi-Mix Plant: 88 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 5" maximum Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Batch time: 12:35pm Concrete: 700F Ticket No: 88057384 Unit Weight (pet): NA Measured Slump (inches) 5.0 Mix Design 1.0.: 23601524 Placement Date: 12/04/2007 Weather Conditions: Sunny Time Sampled: 01 :30pm Temperature - Air: 730F Truck No: 1059 Air Content: 4.5% Overall Placement Location: Sidewalk, buildings 1 and 2, southeast and southwest side of building 2 and 1 light pole. Relocated to (cont. below) Sample Location: Building 2, southwest side of building REPORT OF TESTS Cylinder Marked Date Set No. Tested 1 1 12/11/2007 1 2 01/01/2008 1 3 01/01/2008 1 4 01/29/2008 Age (days) 7 Diameter (in) 6.00 28 28 56 Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 104,960 Compressive Strength (psi) 3,710 Fracture Type Cone/Split Area (in") 28.27 Remarks: Cont: 81' west from original site and steel installed prior to inspection LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/JB) Page 1 of 2