Report of Concrete Compressive Strength Test
Report No.: 307204
Project No.: 0712786
Date of Service: 12/04/2007
Report Date: 12/17/2007
Project: Gateway Business Center
Cappell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples
back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor: Constructors & Associates
Concrete Supplier: Redi-Mix
Plant: 88
Specification Requirements
Strength: 3,600 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Batch time: 12:35pm
Concrete: 700F
Ticket No: 88057384
Unit Weight (pet): NA
Measured
Slump
(inches)
5.0
Mix Design 1.0.: 23601524
Placement Date: 12/04/2007
Weather Conditions: Sunny
Time Sampled: 01 :30pm
Temperature - Air: 730F
Truck No: 1059
Air Content: 4.5%
Overall Placement Location:
Sidewalk, buildings 1 and 2, southeast and southwest side of building 2 and 1 light pole.
Relocated to (cont. below)
Sample Location:
Building 2, southwest side of building
REPORT OF TESTS
Cylinder
Marked Date
Set No. Tested
1 1 12/11/2007
1 2 01/01/2008
1 3 01/01/2008
1 4 01/29/2008
Age
(days)
7
Diameter
(in)
6.00
28
28
56
Concrete Compressive Cylinder 6" x 12"
Maximum
Load
(Ibs)
104,960
Compressive
Strength
(psi)
3,710
Fracture
Type
Cone/Split
Area
(in")
28.27
Remarks: Cont: 81' west from original site and steel installed prior to inspection
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(TM/JB) Page 1 of 2