Loading...
Gateway BP(3.1)-LR071218 Rone Eni== Client: Transwestern Commercial Services 5001 Spring Valley Dallas, TX 75244 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 307715 Project No.: 0712786 Date of Service: 12/08/2007 Report Date: 12/18/2007 Project: Gateway Business Center Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Constructors & Associates Concrete Supplier: Osburn Ready Mix Plant: 2 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 5" maximum Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1 064 ASTM C-138 ASTM C-39 Mix Design 1.0.: 40A55 Placement Date: 12/08/2007 Weather Conditions: Cloudy Time Sampled: 08:15am Temperature - Air: 680F Truck No: 2305 Air Content: 4.4% Overall Placement Location: Paving: North driveway from southbound Freeport Parkway Measured Slump (inches) 5.0 Batch time: 07:30am Concrete: 740F Ticket No: 15159 Unit Weight (pct): NA Sample Location: 85' west from west curb on southbound Freeport Parkway in center of driveway REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type - 1 1 12/15/2007 7 6.00 28.27 107,660 3,810 Type5 2 3 01/05/2008 01/05/2008 28 28 1 02/02/2008 56 4 F.......1:...71 ~?~:;] [:~~::.] Type 1 TI'Tj,....r....] p.Jt ~...J".. :...,. ... .'. .~...'...-.... Type 2 '''J'['''.'' : 'I" v.:, ).1 L\~.\J Type 3 f<::~ r.........I'.......] I:.:r-'<~I I........... .....'...... .......~'... ............ Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, LId. (CH/JB) Page 1 of 2 Rone Eni=:= Client: Transwestem Commercial Services 5001 Spring Valley Dallas, TX 75244 8908 Ambassador Row, Dallas, TX 75247 n01 W Little York, Ste 600, Houston, TX n040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 305356 Project No.: 0712786 Date of Service: 11/13/2007 Report Date: 12/18/2007 Project: Gateway Business Center Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Constructors & Associates Concrete Supplier: Redi-Mix Plant: 259 Specification Requirements Strength: 3,000 psi @ 28 days Slump (in.): 3" - 5" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C~143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design I.D.: 330J1504 Placement Date: 11/13/2007 Weather Conditions: Partly cloudy Time Sampled: 02:00pm Batch time: 12:07pm Temperature - Air: 800F Concrete: 800F Truck No: 1345 Ticket No: 59017164 Air Content: 2.0% Unit Weight (pet): NA Overall Placement Location: Sidewalk Measured Slump (inches) 7.25 Sample Location: Sidewalks, south side of buildings 1 and 2 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (irr) (Ibs) (psi) Type 1 1 11/20/2007 7 6.00 28.27 66,1 00 2,340 Cone/Shear 1 2 12/11/2007 28 6.00 28.27 95,530 3,380 Cone/Split 1 3 12/11/2007 28 6.00 28.27 91,370 3,230 Cone/Shear Average 3,310 1 4 01/08/2008 56 Remarks: Water added at site: 15 gallons LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject mailer provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TMIKW) Page 1 of 2 Rone Eni=a Client: Transwestern Commercial Services 5001 Spring Valley Dallas, TX 75244 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 305552 Project No.: 0712786 Date of Service: 11/15/2007 Report Date: 12/18/2007 Project: Gateway Business Center Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Constructors & Associates Concrete Supplier: Redi-Mix Plant: 88 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 3" - 5" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Batch time: 06:14am Concrete: 60DF Ticket No: 88056763 Unit Weight (pet): NA Measured Slump (inches) 5.0 Mix Design I.D.: 23601524 Placement Date: 11/15/2007 Weather Conditions: Sunny Time Sampled: 06:30am Temperature - Air: 40DF Truck No: 1218 Air Content: 2.5% Overall Placement Location: Paving, 110' southwest of north approach off Freeport Parkway, center of drivelfirelane Sample Location: Same as above REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type - - 1 1 11/22/2007 7 6.00 28.27 78,990 2,790 Cone/Split 1 2 12/13/2007 28 6.00 28.27 108,220 3,830 Cone/Split 1 3 12/13/2007 28 6.00 28.27 1 09,1 50 3,860 Shear Average 3,840 1 4 01/10/2008 56 1 5 01/10/2008 56 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KWI'r<Y'i) Page 1 of 2