Loading...
Gateway BP(3.1)-LR080109 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 305356 ~"' Project No.: 0712786 " Date of Service: 11/13/2007 V ;. A~eport Date: 01/09/2008 Project: Gateway Business Center / J~J~VI Coppell, Texas II ~ Services: Obtain samples of fresh concrete at the placement locations, perform reqUlrelf'ting, cast compressive strength samples and bring Client: Transwestern Commercial Services 5001 Spring Valley Dallas, TX 75244 samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Constructors & Associates Concrete Supplier: Redi-Mix Plant: 259 Specification Requirements Strength: 3,000 psi @ 28 days Slump (in.): 3" - 5" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design 1.0.: 330J1504 Placement Date: 11/13/2007 Weather Conditions: Partly cloudy Time Sampled: 02:00pm Batch time: 12:07pm Temperature - Air: 800F Concrete: 800F Truck No: 1345 Ticket No: 59017164 Air Content: 2.0% Unit Weight (pet): NA Overall Placement Location: Sidewalk Measured Slump (inches) 7.25 Sample Location: Sidewalks, south side of buildings 1 and 2 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 1 1 11/20/2007 7 6.00 28.27 66,100 2,340 Cone/Shear 1 2 12/11/2007 28 6.00 28.27 95,530 3,380 Cone/Split 1 3 12/11/2007 28 6.00 28.27 91,370 3,230 Cone/Shear Average 3,310 4 01/08/2008 56 6.00 28.27 113,040 4,000 Cone/Split Remarks: Water added at site: 15 gallons flt~ LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/KW) Page 1 of 2