Duke Lesley 2A-LR080108
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 305138
Project No.: 0712932
Date of Service: 11/12/2007
Report Date: 01/08/2008
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7753 PW
Placement Date: 11/12/2007
Weather Conditions: Cloudy, light wind
Time Sampled: 03:05am Batch time: 02:50am
Temperature - Air: 620F Concrete: 750F
Truck No: 140 Ticket No: 925
Air Content: 4.4% Unit Weight (pct): NA
Overall Placement Location:
Paving - southwest section of south parking lot, south side of building 7
Measured
Slump
(inches)
5.0
Sample Location:
130' east, 75' south from southwest corner of building 7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
1 1 11/19/2007 7 6.00 28.27 111,590 3,950 Cone/Split
2 12/10/2007 28 6.00 28.27 148,750 5,260 Shear
3 12/10/2007 28 6.00 28.27 147,310 5,210 Shear
Average 5,240
4 01/07/2008 56 6.00 28.27 164,740 5,830 Cone/Split
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 1 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 305138
Project No.: 0712932
Date of Service: 11/12/2007
Report Date: 01/08/2008
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7753 PW
Placement Date: 11/12/2007
Weather Conditions: Cloudy, windy
Time Sampled: 04: 1 Oam Batch time: 03:53am
Temperature - Air: 620F Concrete: 740F
Truck No: 40 Ticket No: 9034
Air Content: 4.5% Unit Weight (pcf): NA
Overall Placement Location:
Paving - southwest section of south parking lot, south side of building 7
Measured
Slump
(inches)
5.0
Sample Location:
175' east, 80' south from southwest corner of building 7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
-
2 1 11/19/2007 7 6.00 28.27 112,230 3,970 Cone/Split
2 2 12/10/2007 28 6.00 28.27 144,950 5,130 Cone/Split
2 3 12/10/2007 28 6.00 28.27 150,840 5,330 Shear
Average 5,230
2 4 01/07/2008 56 6.00 28.27 164,150 5,810 Cone/Split
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 2 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 305138
Project No.: 0712932
Date of Service: 11/12/2007
Report Date: 01/08/2008
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7753 PW
Placement Date: 11/12/2007
Weather Conditions: Cloudy, windy
Time Sampled: 05:25am Batch time: 05:09am
Temperature - Air: 610F Concrete: 760F
Truck No: 109 Ticket No: 9045
Air Content: 4.4% Unit Weight (pcf): NA
Overall Placement Location:
Paving - southwest section of south parking lot, south side of building 7
Measured
Slump
(inches)
4.5
Sample Location:
230' east, 80' south from southwest corner of building 7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (inZ) (Ibs) (psi) Type
-
3 1 11/19/2007 7 6.00 28.27 109,240 3,860 Cone/Split
3 2 12/10/2007 28 6.00 28.27 141,360 5,000 Cone/Split
3 3 12/10/2007 28 6.00 28.27 147,250 5,210 Cone/Split
Average 5,100
3 4 01/07/2008 56 6.00 28.27 156,180 5,520 Cone/Split
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 3 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 305138
Project No.: 0712932
Date of Service: 11/12/2007
Report Date: 01/08/2008
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7753 PW
Placement Date: 11/12/2007
Weather Conditions: Cloudy, windy
Time Sampled: 06:40am Batch time: 06: 19am
Temperature - Air: 640F Concrete: 760F
Truck No: 138 Ticket No: 9055
Air Content: 4.6% Unit Weight (pet): NA
Overall Placement Location:
Paving - southwest section of south parking lot, south side of building 7
Measured
Slump
(inches)
5.0
Sample Location:
300' east, 70' south from southwest corner of building 7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
4 1 11/19/2007 7 6.00 28.27 105,090 3,720 Cone/Split
4 2 12/10/2007 28 6.00 28.27 146,340 5,180 Shear
4 3 12/10/2007 28 6.00 28.27 138,910 4,910 Cone/Split
Average 5,040
4 4 01/07/2008 56 6.00 28.27 165,800 5,860 Cone/Split
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KWIKW) Page 4 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 305138
Project No.: 0712932
Date of Service: 11/12/2007
Report Date: 01/08/2008
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7753 PW
Placement Date: 11/12/2007
Weather Conditions: Cloudy, windy
Time Sampled: 07:45am Batch time: 07:33am
Temperature - Air: 690F Concrete: 760F
Truck No: 110 Ticket No: 9065
Air Content: 4.4% Unit Weight (pcf): NA
Overall Placement Location:
Paving - southwest section of south parking lot, south side of building 7
Measured
Slump
(inches)
5.5
Sample Location:
380' east, 85' south from southwest corner of building 7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
5 1 11/19/2007 7 6.00 28.27 100,000 3,540 Cone/Shear
5 2 12/10/2007 28 6.00 28.27 135,320 4,790 Cone/Shear
5 3 12/10/2007 28 6.00 28.27 139,510 4,930 Shear
Average 4,860
5 4 01/07/2008 56 6.00 28.27 149,940 5,300 Shear
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 5 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 305138
Project No.: 0712932
Date of Service: 11/12/2007
Report Date: 01/08/2008
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing. cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7753 PW
Placement Date: 11/12/2007
Weather Conditions: Cloudy. light rain
Time Sampled: 09:20am Batch time: 08:58am
Temperature - Air: 700F Concrete: 790F
Truck No: 138 Ticket No: 9075
Air Content: 4.5% Unit Weight (pet): NA
Overall Placement Location:
Paving - southwest section of south parking lot, south side of building 7
Measured
Slump
(inches)
5.0
Sample Location:
425' east. 85' south from southwest corner of building 7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in') (Ibs) (psi) Type
6 1 11/19/2007 7 6.00 28.27 95,550 3,380 Cone/Split
6 2 12/10/2007 28 6.00 28.27 131,930 4,670 Cone/Split
6 3 12/10/2007 28 6.00 28.27 131,560 4,650 Shear
Average 4,660
6 4 01/07/2008 56 6.00 28.27 146,670 5,190 Cone/Split
Remarks: Water added at site: 10 gallons
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition. appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 6 019
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W little York, Ste 600, Houston, TX 77040
4421 Freidrlch, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 305138
Project No.: 0712932
Date of Service: 11/12/2007
Report Date: 01/08/2008
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7753 PW
Placement Date: 11/12/2007
Weather Conditions: Cloudy, windy
Time Sampled: 10:25am Batch time: 10:10am
Temperature - Air: 750F Concrete: 790F
Truck No: 138 Ticket No: 9085
Air Content: 4.6% Unit Weight (pet): NA
Overall Placement Location:
Paving - southwest section of south parking lot, south side of building 7
Measured
Slump
(inches)
5.0
Sample Location:
480' east, 85' south from southwest corner of building 7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
7 1 11/19/2007 7 6.00 28.27 89,640 3,170 Cone/Shear
7 2 12/10/2007 28 6.00 28.27 129,900 4,590 Cone/Split
7 3 12/10/2007 28 6.00 28.27 129,510 4,580 Shear
Average 4,590
7 4 01/07/2008 56 6.00 28.27 134,400 4,750 Cone/Split
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 7 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 305138
Project No.: 0712932
Date of Service: 11/12/2007
Report Date: 01/08/2008
Project: Hemisphere's at Point West
Coppell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design I.D.: 7753 PW
Placement Date: 11/12/2007
Weather Conditions: Cloudy, windy
Time Sampled: 11 :20am Batch time:
Temperature - Air: 780F Concrete: 810F
Truck No: 130 Ticket No: 9095
Air Content: 4.6% Unit Weight (pet): NA
Overall Placement Location:
Paving - southwest section of south parking lot, south side of building 7
Measured
Slump
(inches)
5.0
Sample Location:
530' east, 80' south from southwest corner of building 7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
8 1 11/19/2007 7 6.00 28.27 95,410 3,370 Cone/Split
8 2 12/10/2007 28 6.00 28.27 137,640 4,870 Cone/Split
8 3 12/10/2007 28 6.00 28.27 136,360 4,820 Cone/Split
Average 4,850
8 4 01/07/2008 56 6.00 28.27 152,020 5,380 Cone/Split
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd.
(KW/KW) Page 8 of 9
Rone Engineering
.
Client:
Duke Construction, LP
14241 Dallas Pkwy, Ste 1000
Dallas, TX 75254-2936
8908 Ambassador Row, Dallas, TX 75247
7701 W Little York, Ste 600, Houston, TX 77040
4421 Freidrich, Ste 195, Austin, TX 78744
Corporate Phone: (214) 630-9745
Report of Concrete Compressive Strength Test
Report No.: 305138
Project No.: 0712932
Date of Service: 11/12/2007
Report Date: 01/08/2008
Project: Hemisphere's at Point West
Cappell, Texas
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
Contractor: Duke Construction, LP
Concrete Supplier: Potter Concrete
Plant: 10
Specification Requirements
Strength: 4,000 psi @ 28 days
Slump (in.): 5" maximum
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
PROJECT DATA
Mix Design 1.0.: 7753 PW
Placement Date: 11/12/2007
Weather Conditions: Partly cloudy, windy
Time Sampled: 12:15pm Batch time: 11:58am
Temperature - Air: 800F Concrete: 810F
Truck No: 130 Ticket No: 9103
Air Content: 4.5% Unit Weight (pet): NA
Overall Placement Location:
Paving - southwest section of south parking lot, south side of building 7
Measured
Slump
(inches)
5.0
Sample Location:
560' east, 75' south from southwest corner of building 7
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength Fracture
Set No. Tested (days) (in) (in2) (Ibs) (psi) Type
9 1 11/19/2007 7 6.00 28.27 98,310 3,480 Shear
9 2 12/10/2007 28 6.00 28.27 150,270 5,310 Cone/Split
9 3 12/10/2007 28 6.00 28.27 132,900 4,700 Cone/Split
Average 5,010
9 4 01/07/2008 56 6.00 28.27 157,090 5,560 Cone/Split
Started: 02:30am Finished: 01 :30pm
Technician: Pat Parks
Report Distribution:
Orig: Duke Construction, LP (Dallas, TX) Attn: Mr. Paul Byrne
(1-ec copy)
1-cc Potter Concrete Attn: Mr Ryan Skelly
1-cc City of Coppell Attn: Mr. Lee Stone
1-cc City of Coppell Attn: Mr. Larry Davis
Rone Engineering
p~~
K. Scott Watson, AET
Project Manager
LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality
(composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are
for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd.
(KW/KW) Page 9 of 9