Northlake College-LR080205
KLEINFELDER
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. ~
1505 South Lamar, Suite 1015
Dallas, Texas 75215
10/ -e..
TECHNICIAN: J. Mayo
CONCRETE FOR: Pavement 90' W x 40' N fro
PROJECT: North Lake College, N Campus
W Sandy Lake Road @ SH 121
ROJECT NO: 87015
REPORT DATE: 2/5/2008
REPORT NO: 018029
the SE quadrant parking
Page 1 of 3
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
018029A 7 1/7/08 1/14/08 4.00 12.57 5 44,150 3,510
0180298 28 1/7/08 2/4/08 4.00 12.57 5 59,920 4,770
018029C 28 1/7/08 2/4/08 4.00 12.57 3 60,750 4,830
0180290 HOLD 1/7/08 HOLD
SUPPLIER: Southern Star
MIX DESIGN: 000000007725
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
TRUCK NO. :
TICKET NO. :
ACCUMULATED YDS:
TIME CAST:
TIME IN TRUCK:
WEATHER:
1020
1172707
40 of 150
9:29 AM
59 min
Clear
SLUMP:
AIR TEMP. :
MIX TEMP. :
AIR CONTENT:
WATER ADDED (gal) :
UNIT WEIGHT:
AVERAGE 28 DAY STRENGTH: 4,800
28 DAY STRENGTH REQUIREMENT: 4,000
SPECIFIED
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Sieje fractures at top or bottom (occur commoniy with un bonded caps).
6
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been fumished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231: Temperature ASTM C1064
Reports to:
Starling Richardson Cons\.; AUn: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Cons\.; AUn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu)
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
Indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
KLEINFELDER
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 2/5/2008
TECHNICIAN: J. Mayo REPORT NO: 018029 Page 2 of 3
CONCRETE FOR: Pavement 90' W x 80' N from the SE corner of the SE quadrant parking
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
018030A 7 1/7/08 1/14/08 4.00 12.57 3 45,060 3,590
018030B 28 1/7/08 2/4/08 4.00 12.57 3 64,700 5,150
018030C 28 1/7/08 2/4/08 4.00 12.57 3 60,440 4,810
0180300 HOLD 1 /7/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 4,980
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL SPECIFIED
TRUCK NO. : 1011 SLUMP: 6.25
TICKET NO. : 1172789 AIR TEMP. : 65
ACCUMULATED YDS : 90 of 150 MIX TEMP. : 92
TIME CAST: 10:10 AM AIR CONTENT: 3.4
TIME IN TRUCK: 55 min WATER ADDED (gal) : 10
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 ," k"t~nn i" nn;nt~n
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231, Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Altn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; Altn: Andy Munoz (amunoz@starlingrichardson.com) /Z~
DCCCD Bond Office; Altn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Altn: James Williams Oames.williams@dcccd.edu)
DCCCD Bond Office; Altn: Mike Daniels (mike.daniels@dcccd.edu) t:7 t;,-
Jacobs; Altn; Andrea Stogner (Andrea.stogner@jacobs.com) Joel Peters, P.E.
Jacobs; Altn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Altn: Larry Davis
1- City of Coppell; Altn: Lee Stone
The results shown on this report are for the exclusiVe use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparen11y identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 2/5/2008
TECHNICIAN: J. Mayo REPORT NO: 018029 Page 3 of 3
CONCRETE FOR: Pavement 85' W x 130' N from the SE corner of the SE quadrant parking
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD,LBS STRENGTH, PSI
018031A 7 1/7/08 1/14/08 4.00 12.57 5 48,390 3,850
018031B 28 1/7/08 2/4/08 4.00 12.57 3 63,900 5,090
018031C 28 1/7/08 2/4/08 4.00 12.57 3 65,510 5,210
0180310 HOLD 1/7/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,150
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 5013 SLUMP: 6.5
TICKET NO. : 1172874 AIR TEMP.: 65
ACCUMULATED YDS : 150 of 150 MIX TEMP.: 91
TIME CAST: 11:02 AM AIR CONTENT: 3.7
TIME IN TRUCK: 67min WATER ADDED (gal) : 10
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
~ . nnint..rt
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173! C231, Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /L ,;7:-
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Uames.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) ~,..- Joel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Artn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only \0 the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.