4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/30/2008
TECHNICIAN: J. Mayo REPORT NO: 127111 Page 1 of 4
CONCRETE FOR: Pavement from the SW corner of Area A 120' S x 30' W
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
127111A 7 12/31/08 1/7/09 4.00 12.57 5 61,080 4,860
127111 B 28 12/31/08 1/28/09 4.00 12.57 4 77,030 6,130
127111C 28 12/31/08 1/28/09 4.00 12.57 3 72,870 5,800
1271110 HOLD 12/31/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,965
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 1020 SLUMP: 5.75
TICKET NO. : 1168585 AIR TEMP. : 45
ACCUMULATED YDS : 50 of 400 MIX TEMP. : 73
TIME CAST: 7:53 AM AIR CONTENT: 2.8
TIME IN TRUCK: 39min WATER ADDED (gal) : 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
6 nut "nrt of . , Dointed.
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Canst.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Canst.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /2L~
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams fjames.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) V7 ~rJoel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/30/2008
TECHNICIAN: J. Mayo REPORT NO: 127111 Page 2 of 4
CONCRETE FOR: Pavement from the SW corner of Area A 25' S x 30' W
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
127112A 7 12/31/08 1/7/09 4.00 12.57 3 50,640 4,030
1271128 28 12/31/08 1/28/09 4.00 12.57 3 76,940 6,120
127112C 28 12/31/08 1/28/09 4.00 12.57 2 72,220 5,750
1271120 HOLD 12/31/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,935
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL I SPECIFIED I
TRUCK NO. : 1084 SLUMP: 6.5
TICKET NO. : 1168596 AIR TEMP. : 45
ACCUMULATED YDS : 70 of 400 MIX TEMP. : 71
TIME CAST: 8:19 AM AIR CONTENT: 2.1
TIME IN TRUCK: 59 min WATER ADDED (gal) : 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in (25 mm) of cracking through caps
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 !':;mi " linri..,
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit WeightASTM C138; Air ContentASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) /h~
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams (james.wi/liams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) c:;:;r ,t;"-Joel Peters, P.E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/30/2008
TECHNICIAN: J. Mayo REPORT NO: 127111 Page 3 of 4
CONCRETE FOR: Pavement from the SW corner of Area A 80' S X 70' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
127113A 7 12/31/08 1/7/09 4.00 12.57 3 53,900 4,290
127113B 28 12/31/08 1/28/09 4.00 12.57 4 66,630 5,300
127113C 28 12/31/08 1/28/09 4.00 12.57 3 67,790 5,390
1271130 HOLD 12/31/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,345
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL I SPECIFIED I
TRUCK NO. : 905 SLUMP: 5.5
TICKET NO. : 1168674 AIR TEMP.: 50
ACCUMULATED YDS : 150 of 400 MIX TEMP. : 77
TIME CAST: 9:14 AM AIR CONTENT: 2.9
TIME IN TRUCK: 46min WATER ADDED (gal) : 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 " ' r.vlinrt"r i~ nnint"rt
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM Cl72 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) /LL-
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams uames.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) ~Joel Peters, P.E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/30/2008
TECHNICIAN: J. Mayo REPORT NO: 127111 Page 4 of 4
CONCRETE FOR: Pavement from the SW corner of Area A 80' S x 110' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD,LBS STRENGTH, PSI
127114A 7 12/31/08 1/7/09 4.00 12.57 3 51,380 4,090
127114B 28 12/31/08 1/28/09 4.00 12.57 3 73,100 5,820
127114C 28 12/31/08 1/28/09 4.00 12.57 3 66,950 5,330
1271140 HOLD 12/31/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,575
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL I SPECIFIED
TRUCK NO. : 84 SLUMP: 7.25
TICKET NO. : 1168695 AIR TEMP. : 50
ACCUMULATED YDS : 200 of 400 MIX TEMP.: 72
TIME CAST: 9:47 AM AIR CONTENT: 2.3
TIME IN TRUCK: 62min WATER ADDED (gal) : 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with nO cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 ,<; hll' Ann nf ~
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173 / C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com) /h~
DCCCD Bond Office;Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcCcd.edu) arJoel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
KlEINFElDER
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community COllegrDiSt.
1505 South Lamar, Suite 1015
Dallas, Texas 75215
PROJECT: North Lake College, N Campus
W Sandy Lake Road @ SH 121
PROJECT NO: 87015
TECHNICIAN: J. Mayo
CONCRETE FOR: Pavement from the NE entrance 90' W x 40' N
REPORT DATE: 1/30/2008
REPORT NO: 018168
Page 1 of 7
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018168A Os 1/21/08 1/28/08 4.00 12.57 2
018168B 1/21/08 2/18/08
018168C 28 1/21/08 2/1 8/08
0181680 HOLD 1/21/08 HOLD
SUPPLIER: Southern Star
MIX DESIGN: 000000007725
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
AVERAGE 28 DAY STRENGTH:
28 DAY STRENGTH REQUIREMENT: 4,000
TRUCK NO. : 97
TICKET NO.: 1183501
ACCUMULATED YDS: 50 of 350
TIME CAST: 9:11 AM
TIME IN TRUCK: 46 min
WEATHER: Cloudy with rain
SLUMP:
AIR TEMP. :
MIX TEMP. :
AIR CONTENT:
WATER ADDED (gal) :
UNIT WEIGHT:
ACTUAL
5.5
35
66
3.1
o
N/A
SPECIFIED
~)7)~!~
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM Cl72 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Canst.; Attn: Eric Stanaland (eps@starlingrichardson.com)
Starling Richardson Canst.; Attn: Andy Munoz (amunoz@starlingrichardson.com)
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Uames.williams@dcccd.edu)
DCCCD Bond Office; Attn; Mike Daniels (mike.daniels@dcccd.edu)
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn; Lee Stone
KLEINFELDER
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/30/2008
TECHNICIAN: J. Mayo REPORT NO: 018168 Page 2 of 7
CONCRETE FOR: Pavement from the NE entrance at Royal Lane 120' W x 50' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018169A 7 1/21/08 1/28/08 4.00 12.57 6 46,050 3,660
018169B 28 1/21/08 2/18/08
018169C 28 1/21/08 2/18/08
0181690 HOLD 1/21/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED I
TRUCK NO. : 5019 SLUMP: 6.25
TICKET NO. : 1183597 AIR TEMP.: 35
ACCUMULATED YDS: 100 of 350 MIX TEMP. : 69
TIME CAST: 9:54 AM AIR CONTENT: 2.8
TIME IN TRUCK: 52min WATER ADDED (gal) : 5
WEATHER: Cloudy with rain UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
6 I'i hilt Ann nf r:vlinriAr .
NOTES: 0 Compressive strengths determined in accordance with ASTM C39. 0 Cross-sectional area, diameter and length are standard unless otherwise noted.
o Portions of the information contained in this report have been furnished by others. 0 Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. 0 Un bonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken In accordance with ASTM C172 where practicable. 0 When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231: Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com) /2h-
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams Uames.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) ~ ~Joel Peters, P.E.
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/30/2008
TECHNICIAN: J. Mayo REPORT NO: 018168 Page 3 of 7
CONCRETE FOR: Pavement from the NE entrance at Royal Lane 120' W x 80' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
018170A 7 1/21/08 1/28/08 4.00 12.57 2 52,270 4,160
018170B 28 1/21/08 2/18/08
018170C 28 1/21/08 2/18/08
018170D HOLD 1/21/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED
TRUCK NO. : 3441 SLUMP: 8.0
TICKET NO. : 1183667 AIR TEMP.: 35
ACCUMULATED YDS: 150 of 350 MIX TEMP. : 63
TIME CAST: 10:28 AM AIR CONTENT: 2.6
TIME IN TRUCK: 58 min WATER ADDED (gal) : 10
WEATHER: Cloudy with rain UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps. no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 " nnintF>l'l
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /L~
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) p ~r-Joel Peters, P.E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/30/2008
TECHNICIAN: J. Mayo REPORT NO: 018168 Page 4 of 7
CONCRETE FOR: Pavement from the NE entrance at Royal Lane 120' W x 125' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018171A 7 1/21/08 1/28/08 4.00 12.57 4 51,110 4,070
018171B 28 1/21/08 2/18/08
018171C 28 1/21/08 2/18/08
0181710 HOLD 1/21/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: DOOOOOO07725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL SPECIFIED I
TRUCK NO. : 39 SLUMP: 8.5
TICKET NO. : 1183722 AIR TEMP. : 35
ACCUMULATED YDS : 190 of 350 MIX TEMP. : 68
TIME CAST: 11 : 11 AM AIR CONTENT: 3.4
TIME IN TRUCK: 56 min WATER ADDED (gal) : 10
WEATHER: Cloudy with rain UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
6 ,5 h,,+ <>nn
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138: Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Alln: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; Alln: Andy Munoz (amunoz@starlingrichardson.com) /L~
DCCCD Bond Office; Alln: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Alln: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Alln: Mike Daniels (mike.daniels@dcccd.edu) ~r' Joel Peters, P.E.
Jacobs; Alln: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Alln: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Alln: Larry Davis
1- City of Coppell; Alln: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/30/2008
TECHNICIAN: J. Mayo REPORT NO: 018168 Page 5 of 7
CONCRETE FOR: Driveway from the NE entrance at Royal Lane 125' W x 50' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA IN.2 TYPE LOAD, LBS STRENGTH, PSI
018172A 7 1/21/08 1/28/08 4.00 12.57 2 61,110 4,860
018172B 28 1/21/08 2/18/08
018172C 28 1/21/08 2/18/08
0181720 HOLD 1/21/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
I ACTUAL SPECIFIED
TRUCK NO. : 5019 SLUMP: 8.25
TICKET NO. : 1183811 AIR TEMP.: 40
ACCUMULATED YDS : 240 of 350 MIX TEMP.: 71
TIME CAST: 11 :32 AM AIR CONTENT: 3.7
TIME IN TRUCK: 37 min WATER ADDED (gal) : 10
WEATHER: Cloudy with rain UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
R Simil"r " nnintF!r1
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted,
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted, . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173 / C231; Temperature ASTM C1064
Reports to:
Starling Richardson Canst.; Altn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; Altn: Andy Munoz (amunoz@starlingrichardson.com) /Z~
DCCCD Bond Office;Altn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Altn: James Williams Uames.williams@dcccd.edu)
DCCCD Bond Office; Altn: Mike Daniels (mike.daniels@dcccd.edu) ~ Joel Peters, P.E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Altn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppe"; Altn: Larry Davis
1- City of Coppe"; Altn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior writlen approval. Reports must be reproduced in their entirety.
K l E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/30/2008
TECHNICIAN: J. Mayo REPORT NO: 018168 Page 6 of 7
CONCRETE FOR: Driveway from the NE entrance at Royal Lane 125' W x 80' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018173A 7 1/21/08 1/28/08 4.00 12.57 3 56,580 4,500
018173B 28 1/21/08 2/18/08
018173C 28 1/21/08 2/18/08
0181730 HOLD 1/21/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL I SPECIFIED I
TRUCK NO. : 1099 SLUMP: 7.75
TICKET NO. : 1183876 AIR TEMP. : 40
ACCUMULATED YDS : 300 of 350 MIX TEMP. : 69
TIME CAST: 12:19 PM AIR CONTENT: 3.2
TIME IN TRUCK: 49min WATER ADDED (gal): 5
WEATHER: Cloudy with rain UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends. less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end. vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends. no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 Similar to ~ cVlinaer is oointed.
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable. the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; Altn: Andy Munoz (amunoz@starlingrichardson.com) /Z.~
DCCCD Bond Office; Altn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Oames.williams@dcccd.edu)
DCCCD Bond Office; Altn: Mike Daniels (mike.daniels@dcccd.edu) ~r-JOel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Altn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 1/30/2008
TECHNICIAN: J. Mayo REPORT NO: 018168 Page 7 of 7
CONCRETE FOR: Driveway from the NE entrance at Royal Lane 70' W x 60' N
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA IN.2 TYPE LOAD,LBS STRENGTH, PSI
018174A 7 1/21/08 1/28/08 4.00 12.57 3 52,070 4,140
0181748 28 1/21/08 2/18/08
018174C 28 1/21/08 2/18/08
0181740 HOLD 1/21/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH:
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
r ACTUAL T SPECIFIED
TRUCK NO. : 5019 SLUMP: 9.5
TICKET NO. : 1183945 AIR TEMP. : 40
ACCUMULATED YDS : 350 of 350 MIX TEMP.: 68
TIME CAST: 1 :22 PM AIR CONTENT: 3.4
TIME IN TRUCK: 57min WATER ADDED (gal): 10
WEATHER: Cloudy with rain UNIT WEIGHT: N/A
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
fi " n,.,ln'.."
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been fumished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C 1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) /Z~
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) C7 f;,... Joel Peters, P.E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.