Northlake College-LR080213
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 2/13/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 1 of 6
CONCRETE FOR: Pavement; The corner of the NW quadrant in S parking area, 30'S x 50' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
018116A 7 1/15/08 1/22/08 4.00 12.57 2 48,010 3,820
018116B 28 1/15/08 2/12/08 4.00 12.57 3 63,060 5,020
018116C 28 1/15/08 2/12/08 4.00 12.57 3 63,070 5,020
0181160 HOLD 1/15/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,020
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL SPECIFIED 1
TRUCK NO. : 6233 SLUMP: 6.25
TICKET NO. : 1179463 AIR TEMP. : 40
ACCUMULATED YDS: 50 of 300 MIX TEMP. : 69
TIME CAST: 8:09 AM AIR CONTENT: 3.6
TIME IN TRUCK: 69 min WATER ADDED (gal): 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends. less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps. no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
~ ~,. ,Tv"",/:;
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area. diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted.' Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads.
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) /h~
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) ~JOel Peters, P.E.
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; AUn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently idenllcal products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 2/13/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 2 of 6
CONCRETE FOR: Pavement; The corner of the NW quadrant in S parking area, 30' S x 85' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA,IN.2 TYPE LOAD, LBS STRENGTH, PSI
018117A 7 1/15/08 1/22/08 4.00 12.57 2 52,140 4,150
0181178 28 1/15/08 2/12/08 4.00 12.57 5 68,130 5,420
018117C 28 1/15/08 2/12/08 4.00 12.57 3 67,860 5,400
018117D HOLD 1/15/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,410
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
ACTUAL I SPECIFIED 1
TRUCK NO. : 945 SLUMP: 6.50
TICKET NO. : 1179585 AIR TEMP. : 40
ACCUMULATED YDS : 90 of 300 MIX TEMP. : 71
TIME CAST: 8:48 AM AIR CONTENT: 3.1
TIME IN TRUCK: 53 min WATER ADDED (gal): 5
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends. less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with un bonded caps).
R ~i",il'lIrtnTv"",!i . , nnintAll
NOTEs: . Compressive strengths detenmined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Un bonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /:L~
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams Games.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) c;::::' fOr- Joel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclUSive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirely.
K L E I N F E L D E R
2211 Century Center 8Ivd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 2/13/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 3 of 6
CONCRETE FOR: Pavement; The corner of the NW quadrant in S parking area, 30' S x 120' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018118A 7 1/15/08 1/22/08 4.00 12.57 3 50,530 4,020
0181188 28 1/15/08 2/12/08 4.00 12.57 3 64,730 5,150
018118C 28 1/15/08 2/12/08 4.00 12.57 3 63,060 5,020
0181180 HOLD 1/15/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,085
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED
TRUCK NO. : 8 SLUMP: 8.25
TICKET NO. : 1179713 AIR TEMP. : 45
ACCUMULATED YDS: 150 of 300 MIX TEMP. : 68
TIME CAST: 9:49 AM AIR CONTENT: 2.8
TIME IN TRUCK: 64 min WATER ADDED (gal) : 10
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end. vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends. no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
R . . 1; hllt..nri . --,-~.
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air Content ASTM C173 / C231: Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) /2~
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) tar-JOel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualrties of apperently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K l E I N F E l D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 2/13/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 4 of 6
CONCRETE FOR: Pavement; The corner of the NW quadrant in S parking area, 30' S x 180' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018119A 7 1/15/08 1/22/08 4.00 12.57 2 47,930 3,810
0181198 28 1/15/08 2/12/08 4.00 12.57 3 62,440 4,970
018119C 28 1/15/08 2/12/08 4.00 12.57 3 63,310 5,040
0181190 HOLD 1/15/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,005
MIX DESIGN: 000000007725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED 1
TRUCK NO. : 1084 SLUMP: 8.75
TICKET NO. : 1179871 AIR TEMP. : 50
ACCUMULATED YDS : 200 of 300 MIX TEMP. : 69
TIME CAST: 10:26AM AIR CONTENT: 3.4
TIME IN TRUCK: 31 min WATER ADDED (gal): 10
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 . . - ,!;
NOTES: . Compressive strengths determined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
Unit Weight ASTM C138; Air ContentASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AlIn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; AlIn: Andy Munoz (amunoz@starlingrichardson.com) /L Lk-
OCCCO Bond Office; AlIn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCO Bond Office; AUn: James Williams Oames.williams@dcccd.edu)
DCCCO Bond Office; AUn: Mike Daniels (mike.daniels@dcccd.edu) ~oel Peters, P. E.
Jacobs; AlIn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Altn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; AUn: Larry Davis
1- City of Coppell; AUn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor Inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy Lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 2/13/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 5 of 6
CONCRETE FOR: Pavement; The corner of the NW quadrant in S parking area, 30' S x 210' E
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018120A 7 1/15/08 1/22/08 4.00 12.57 2 48,700 3,880
0181208 28 1/15/08 2/12/08 4.00 12.57 3 66,240 5,270
018120C 28 1/15/08 2/12/08 4.00 12.57 5 65,340 5,200
0181200 HOLD 1/15/08 HOLD
I SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,235
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEINFELDER:
I ACTUAL SPECIFIED I
TRUCK NO. : 26 SLUMP: 6.0
TICKET NO. : 117996 AIR TEMP.: 55
ACCUMULATED YDS: 250 of 300 MIX TEMP.: 73
TIME CAST: 11: 18 AM AIR CONTENT: 3.3
TIME IN TRUCK: 52 min WATER ADDED (gal): 5
WEATHER: Clear UNIT WEIGHT: N/A
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical craCking through both ends, no well-formed cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
S Side fractures at top or bottom (occur commonly with unbonded caps).
fI . . ~ . , nointed
NOTES: . Compressive strengths detenmined in accordance with ASTM C39. .c-ross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the infonmation contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143;
UnitWeightASTM C13B; Air Content ASTM C1731 C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; Attn: Eric Stanaland (eps@starlingrichardson.com) KLEIN FELDER
Starling Richardson Const.; Attn: Andy Munoz (amunoz@starlingrichardson.com) /L ~.
DCCCD Bond Office; Attn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; Attn: James Williams (james.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu) a"Joel Peters, P.E.
Jacobs; Attn: Andrea Stogner (Andrea.stogner@jacobs.com)
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested and/or inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.
K L E I N F E L D E R
2211 Century Center Blvd., Suite 101, Irving, Texas 75062
972-870-0808 Metro 972-953-0398 Fax 972-870-0802
4x8 CONCRETE CYLINDER COMPRESSIVE STRENGTH REPORT
TO: Dallas County Community College Dist. PROJECT: North Lake College, N Campus
1505 South Lamar, Suite 1015 W Sandy lake Road @ SH 121
Dallas, Texas 75215 PROJECT NO: 87015
REPORT DATE: 2/13/2008
TECHNICIAN: J. Mayo REPORT NO: 018116 Page 6 of 6
CONCRETE FOR: Pavement from the NE entrance 50' W x 70' S
CYLINDER AGE DATE DATE AVG. CYLINDER CYLINDER FRACTURE TOTAL COMPRESSIVE
MARK DAYS CAST TESTED DIAMETER, IN. AREA, IN.2 TYPE LOAD, LBS STRENGTH, PSI
018121A 7 1/15/08 1/22/08 4.00 12.57 2 48,970 3,900
0181218 28 1/15/08 2/12/08 4.00 12.57 3 65,120 5,180
018121C 28 1/15/08 2/12/08 4.00 12.57 3 64,520 5,130
0181210 HOLD 1/15/08 HOLD
SUPPLIER: Southern Star AVERAGE 28 DAY STRENGTH: 5,155
MIX DESIGN: DOOOOOOO7725 28 DAY STRENGTH REQUIREMENT: 4,000
ADDITIONAL INFORMATION IF MADE BY KLEIN FELDER:
ACTUAL I SPECIFIED I
TRUCK NO. : 1092 SLUMP: 5.75
TICKET NO. : 1180037 AIR TEMP. : 55
ACCUMULATED YDS : 290 of 300 MIX TEMP. : 74
TIME CAST: 11 :54 AM AIR CONTENT: 3.1
TIME IN TRUCK: 49min WATER ADDED (gal) : 0
WEATHER: Clear UNIT WEIGHT: N/A
:
FRACTURE TYPES:
1 Reasonably well-formed cones on both ends, less than 1 in. (25 mm) of cracking through caps.
2 Well-formed cone on one end, vertical cracks running through caps, no well-defined cone on other end.
3 Columnar vertical cracking through both ends, no well-fomned cones.
4 Diagonal fracture with no cracking through ends; tap with hammer to distinguish from Type 1.
5 Side fractures at top or bottom (occur commonly with unbonded caps).
6 . . ,!i hlltAnrl
NOTES: . (;ompressive strengths detemnined in accordance with ASTM C39. . Cross-sectional area, diameter and length are standard unless otherwise noted.
. Portions of the information contained in this report have been furnished by others. . Cylinders cured in laboratory in accordance with ASTM C31 unless
otherwise noted. . Unbonded caps utilized in accordance with ASTM C1231 unless otherwise noted. Because of the violent release of energy stored in pads,
the broken cylinder rarely exhibits conical fracture typical of capped cylinders and the sketches of types of fracture in Test Method C39 are not descriptive.
. Samples taken in accordance with ASTM C172 where practicable. . When applicable, the following test procedures were used: Slump ASTM C143:
Unit Weight ASTM C138; Air Content ASTM C173/ C231; Temperature ASTM C1064
Reports to:
Starling Richardson Const.; AUn: Eric Stanaland (eps@starlingrichardson.com) KLEINFELDER
Starling Richardson Const.; AUn: Andy Munoz (amunoz@starlingrichardson.com) /L ;Zl-
DCCCD Bond Office; AUn: Brenda Spinelli (brenda.spinelli@dcccd.edu)
DCCCD Bond Office; AUn: James Williams Qames.williams@dcccd.edu)
DCCCD Bond Office; Attn: Mike Daniels (mike.daniels@dcccd.edu)
Jacobs; AUn: Andrea Stogner (Andrea.stogner@jacobs.com) r Joel Peters, P. E.
Jacobs; Attn: Jennifer Blount (Jennifer.blount@jacobs.com)
1- City of Coppell; Attn: Larry Davis
1- City of Coppell; Attn: Lee Stone
The results shown on this report are for the exclusive use of the client for whom they were obtained and apply only to the samples tested andlor inspected. They are not intended to be
indicative of the qualities of apparently identical products. The use of our name must receive prior written approval. Reports must be reproduced in their entirety.