Duke Lesley 1A-LR080218 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308783 Project No.: 0713408 Date of Service: 12/21/2007 Report Date: 02/18/2008 Project: Point West VI) f It Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT OAT A Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Batch time: Concrete: 550F Ticket No: NA Unit Weight (pcf): NA Measured Slump (inc les) 5.0 Mix Design 1.0.: 7753 Placement Date: 12/21/2007 Weather Conditions: Clear Time Sampled: 03:15am Temperature - Air: 400F Truck No: 142 Air Content: 4.5% Overall Placement Location: Paving - parking spaces and driveway on north side of building and northwest corner Sample Location: 160' north from grid line N17.3 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 1 1 12/28/2007 7 6.00 28.27 116,470 4,120 Type2 1 2 01/18/2008 28 6.00 28.27 154,560 5,470 Type2 1 3 01/18/2008 28 6.00 28.27 165,710 5,860 Type2 Average 5,660 1 4 02/15/2008 56 6.00 28.27 183,480 6,490 Type3 l~~EJ ~QJ 5IE bJ C][] D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 L1MITA TIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW/KW) Page 1 of 10 Rone Eni== Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308783 Project No.: 0713408 Date of Service: 12/21/2007 Report Date: 02/18/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in') (Ibs) (psi) 2 1 12/28/2007 7 6.00 28.27 105,570 3,730 2 2 01/18/2008 28 6.00 28.27 147,850 5,230 2 3 01/18/2008 28 6.00 28.27 146,070 5,170 Average 5,200 2 4 02/15/2008 56 6.00 28.27 170,880 6,040 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 ~~;~ r3 ~ [g tTIJ tSJ [~~][_J r~l Type 1 Type 2 Type 3 Type 4 Type 5 PROJECT DATA Batch time: Concrete: 52DF Ticket No: NA Unit Weight (pet): NA Measured Slump (inches) 5.75 Mix Design 1.0.: 7753 Placement Date: 12/21/2007 Weather Conditions: Clear Time Sampled: 05:15am Temperature - Air: 42DF Truck No: 137 Air Content: 4.7% Overall Placement Location: Paving - parking spaces and driveway on north side of building and northwest corner Sample Location: 120' north from grid line A/16.3 Fracture Type Type5 Type3 Type3 Type2 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar SUbject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW/KW) Page 2 of 10 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308783 Project No.: 0713408 Date of Service: 12/21/2007 Report Date: 02/18/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in2) (Ibs) (psi) 3 1 12/28/2007 7 6.00 28.27 95,890 3,390 3 2 01/18/2008 28 6.00 28.27 132,310 4,680 3 3 01/18/2008 28 6.00 28.27 135,680 4,800 Average 4,740 3 4 02/15/2008 56 6.00 28.27 143,060 5,060 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 ~Lj ~I~Q] ~ tsJ [=][] IJ Type 1 Type 2 Type 3 Type 4 Type 5 Measured Slump (inches) 5.25 Mix Design I.D.: 7753 Placement Date: 12/21/2007 Weather Conditions: Clear, windy Time Sampled: 07:00am Batch time: Temperature. Air: 550F Concrete: 580F Truck No: 136 Ticket No: NA Air Content: 5.7% Unit Weight (pet): NA Overall Placement Location: Paving - parking spaces and driveway on north side of building and northwest corner Sample Location: 100' north from grid line N6.3 Fracture Type Type5 Type2 Type5 Type2 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW/KW) Page 4 of 10 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308783 Project No.: 0713408 Date of Service: 12/21/2007 Report Date: 02/18/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete al the placement locations, perform required testing, cast compressive strength samples and bring samples back 10 the laboratory for curing and testing in accordance with applicable standards. REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in') (Ibs) (psi) 4 1 12/28/2007 7 6.00 28.27 95,130 3,360 4 2 01/18/2008 28 6.00 28.27 121,440 4,300 4 3 01/18/2008 28 6.00 28.27 116,560 4,120 Average 4,210 4 4 02/15/2008 56 6.00 28.27 150,060 5,310 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 t....j. E7] ~n.]r [gr' ,>< " ., ..~ ....l.... ......-.-.-- --- ~..- fI~~ \ !." Type 3 [~~~ C. j I..'" [-~'1 Type 1 Type 2 Type 4 Type 5 PROJECT DATA Measured Slump (inches) 5.5 Mix Design I.D.: 7753 Placement Date: 12/21/2007 Weather Conditions: Clear, windy Time Sampled: 08:34am Batch time: Temperature - Air: 450F Concrete: 550F Truck No: 137 Ticket No: NA Air Content: 5.5% Unit Weight (pcf): NA Overall Placement Location: Paving. parking spaces and driveway on north side of building and northwesl corner Sample Location: 160' north from grid line AJ4 7 Fracture Type Type5 Type6 Type2 Type2 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter proVided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd. (KW/KW) Page 6 of 10 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308783 Project No.: 0713408 Date of Service: 12/21/2007 Report Date: 02/18/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in') (Ibs) (psi) 5 1 12/28/2007 7 6.00 28.27 91,510 3,240 5 2 01/18/2008 28 6.00 28.27 126,890 4,490 5 3 01/18/2008 28 6.00 28.27 116,720 4,130 Average 4,310 5 4 02/15/2008 56 6.00 28.27 135,280 4,780 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 l?~g [J ~ cg [[1 [~J [] 1:::..J r=] Type 1 Type 2 Type 3 Type 4 Type 5 Measured Slump (inches) 5.25 Mix Design 1.0.: 7753 Placement Date: 12/21/2007 Weather Conditions: Clear, windy Time Sampled: Batch time: Temperature - Air: 550F Concrete: 580F Truck No: 137 Ticket No: NA Air Content: 5.7% Unit Weight (pcf): NA Overall Placement Location: Paving - parking spaces and driveway on north side of building and northwest corner Sample Location: 120' north from grid line A/1. 7 Fracture Type Type2 Type2 Type6 Type6 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW/KW) Page 8 of 10 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308783 Project No.: 0713408 Date of Service: 12/21/2007 Report Date: 02/18/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Duke Construction, LP Concrpt.e Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Measured Slump (inches) 6.0 Mix Design I.D.: 7753 Placement Date: 12/21/2007 Weather Conditions: Sunny, windy Time Sampled: 11 :04am Batch time: Temperature - Air: 600F Concrete: 580F Truck No: 129 Ticket No: NA Air Content: 5.6% Unit Weight (pet): NA Overall Placement Location: Paving - parking spaces and driveway on north side of building and northwest corner Sample Location: 120' north, 70' west from grid line A/1 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 6 1 12/28/2007 7 6.00 28.27 103,130 3,650 Type6 6 2 01/18/2008 28 6.00 28.27 153,740 5,440 Type3 6 3 01/18/2008 28 6.00 28.27 150,060 5,310 Type3 Average 5,370 6 4 02/15/2008 56 6.00 28.27 161,740 5,720 Type6 F);~l I/ZJ fTITl r..-c} Rr~1 t<" I r'" ) I .J lr<;j l.j [~ t:j Lj UW __J._.._____ L_._I Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMIT A nONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of simiiar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW/KW) Page 9 of 10 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308966 Project No.: 0713408 Date of Service: 12/22/2007 Report Date: .02/18/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placementlocalions, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design 1.0.: 7753 Placement Date: 12/22/2007 Weather Conditions: Clear Time Sampled: 03:30am Temperature - Air: 550F Truck No: 109 Air Content: 5.8% Overall Placement Location: Paving, driveway, east side of project Batch time: Concrete: 580F Ticket No: NA Unit Weight (pcf): NA Measured Slump (inches) 5.0 Sample Location: 100' north, 30' east from grid lines A/42 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 1 1 12/29/2007 7 6.00 28.27 116,140 4,110 Type2 2 01/19/2008 28 6.00 28.27 159,790 5,650 Type2 3 01/19/2008 28 6.00 28.27 148,900 5,270 Type2 Average 5,460 4 02/16/2008 56 6.00 28.27 174,130 6,160 Type2 ~tj ~[g ill] t~~J [][-] [J Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar SUbject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in fuli without the written approval of Rone Engineering Services, Ltd. (KW/KW) Page 1 of 10 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308966 Project No.: 0713408 Date of Service: 12/22/2007 Report Date: 02/18/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in2) (Ibs) (psi) 2 1 12/29/2007 7 6.00 28.27 118,270 4,180 2 2 01/19/2008 28 6.00 28.27 163,960 5,800 2 3 01/19/2008 28 6.00 28.27 165,640 5,860 Average 5,830 2 4 02/16/2008 56 6.00 28.27 182,440 6,450 Contractor: Duke Construction, LP Con-:rete Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 F'~..'..'.'.:..~.'.:.l [><.,'(1 rrn,lrrl RTI'Y7'!! f~'j r.............ll....... ..1 [:""-':.~1 r:""'H.._J [v~j r~ llifj L.~~ l_ ..j _ Type 1 Type 2 Type 3 Type 4 Type 5 PROJECT DATA Mix Design 1.0.: 7753 Placement Date: 12/22/2007 Weather Conditions: Clear Time Sampled: 04:57am Temperature - Air: 570F Truck No: 136 Air Content: 5.7% Overall Placement Location: Paving, driveway, east side of project Batch time: Concrete: 580F Ticket No: NA Unit Weight (pcf): NA Measured Slump (inches) 5.75 Sample Location: 55' east from northeast corner of building, grid line A.5/42 Fracture Type Type2 Type6 Type6 Type2 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW/KW) Page 2 of 10 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308966 Project No.: 0713408 Date of Service: 12/22/2007 Report Date: 02/18/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in') (Ibs) (psi) 3 1 12/29/2007 7 6.00 28.27 118,490 4,190 3 2 01/19/2008 28 6.00 28.27 170,370 6,030 3 3 01/19/2008 28 6.00 28.27 171,860 6,080 Average 6,050 3 4 02/16/2008 56 6.00 28.27 182,090 6,440 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 F.' x;] IX] nT.rll~I:.J. RT'Q t"~~~1 I"._-j l ":,J [;r"'.'.'.'.'.J r.",j [__, r__l L_ LlLJ,_.j ..... .....,._.. r,. Type 1 Type 2 Type 3 Type 4 Type 5 PROJECT DATA Mix Design I.D.: 7753 Placement Date: 12/22/2007 Weather Conditions: Clear Time Sampled: 06:00am Temperature - Air: 530F Truck No: 142 Air Content: 5.0% Overall Placement Location: Paving, driveway, easl side of project Batch time: Concrete: 570F Ticket No: NA Unit Weight (pcf): NA Measured Slump (inches) 5.25 Sample Location: 30' easl from grid lines D.7/42 Fracture Type Type6 Type5 Type2 Type2 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for lesting. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW/KW) Page 4 of 10 Rone En~~ Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308966 Project No.: 0713408 Date of Service: 12/22/2007 Report Date: 02/18/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placemenllocations. perform required testing. cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in2) (Ibs) (psi) 4 1 12/29/2007 7 6.00 28.27 154,150 5,450 4 2 01/19/2008 28 6.00 28.27 207,600 7,340 4 3 01/19/2008 28 6.00 28.27 211,540 7,480 Average 7,410 4 4 02/16/2008 56 6.00 28.27 210,520 7,450 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 ~~:::>1 tXj' ~'2]~TT' Q]T' "'. "" ~ ..t .... -.... "'---"~' - - fI~ Type 3 r-~ ...1 t". ...1[' ... ........J. l.,..~J- l~.__ _...~.__..' Type 1 Type 2 Type 4 Type 5 PROJECT DATA Mix Design 1.0.: 7753 PI;:Icement Date: 12/22/2007 W~ather Conditions: Clear Time Sampled: 08:45am Temperature - Air: 550F Truck No: 137 Air Content: 4.5% Overall Placement Location: Paving, driveway, east side of project Batch time: Concrete: 640F Ticket No: NA Unit Weight (pcf): NA Measured Slump (inches) 4.5 Sample Location: 60' east from grid line E1/42 Fracture Type Type2 Type3 Type2 Type2 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing, We assume no responsibility for variation in quality (composition, appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd. (KW/KW) Page 5 of 10 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308966 Project No.: 0713408 Date of Service: 12/22/2007 Report Date: 02/18/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in') (Ibs) (psi) 5 1 12/29/2007 7 6.00 28.27 139,210 4,920 5 2 01/19/2008 28 6.00 28.27 183,740 6,500 5 3 01/19/2008 28 6.00 28.27 188,590 6,670 Average 6,580 5 4 02/16/2008 56 6.00 28.27 187,320 6,630 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 ~~] t:j ~:~TI [;] DIE [~~,J [~1 ['_J r;~J Type 1 Type 2 Type 3 Type 4 Type 5 PROJECT OAT A Mix Design 1.0.: 7753 Placement Date: 12/22/2007 Weather Conditions: Clear Time Sampled: 10:32am Temperature - Air: 480F Truck No: 137 Air Content: 4.9% Overall Placement Location: Paving, driveway, east side of project Batch time: Concrete: 550F Ticket No: NA Unit Weight (pcf): NA Measured Slump (inches) 4.75 Sample Location: 50' east from grid lines K.1/42 Fracture Type Type2 Type6 Type3 Type5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KWIKW) Page 7 of 10 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 308966 Project No.: 0713408 Date of Service: 12/22/2007 Report Date: 02/18/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in2) (Ibs) (psi) 6 1 12/29/2007 7 6.00 28.27 116,570 4,120 6 2 01/19/2008 28 6.00 28.27 152,200 5,380 6 3 01/19/2008 28 6.00 28.27 154,720 5,470 Average 5,430 6 4 02/16/2008 56 6.00 28.27 170,060 6,010 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: On site Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 ~'~~:J' [Xl ~nrJ [--1] /'-, . '" "-"~. /-.... -....... -.-. --- Krn .,.... , , , ' 'I ~ \ . Type 3 [. '1 r'" '1 r .......J I..~~..l """j.... L__.'__~ Type 1 Type 2 Type 4 Type 5 PROJECT DATA Mix Design I.D.: 7753 Placement Date: 12/22/2007 Weather Conditions: Mostly cloudy, windy Time Sampled: 12:45pm Batch time: Temperature - Air: 450F Concrete: 600F Truck No: 131 Ticket No: NA Air Content: 5.7% Unit Weight (pcf): NA Overall Placement Location: Paving, driveway, east side of project Measured Slump (inches) 5.0 Sample Location: 95' south. 50' east from grid lines U42 Fracture Type Type2 Type6 Type2 Type3 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (KW/KW) Page 8 of 10