Duke Lesley 1A-LR080313 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 310881 Project No.: 0713408 Date of Service: 01/16/2008 Report Date: 03/13/2008 Project: Point West VillA. Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in2) (Ibs) (psi) 1 1 01/23/2008 7 6.00 28.27 124,730 4,410 1 2 02/13/2008 28 6.00 28.27 183,550 6,490 1 3 02/13/2008 28 6.00 28.27 176,520 6,240 Average 6,370 4 03/12/2008 56 6.00 28.27 193,590 6,850 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: 1 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 ~~ ~[g &ill Type 3 [SJ DO D Type 1 Type 2 Type 4 Type 5 Measured Slump (inches) Mix Design I.D.: 7753 PW6 Placement Date: 01/16/2008 Weather Conditions: Clear Time Sampled: 06:20am Temperature - Air: Truck No: 103 Air Content: NA Overall Placement Location: Paving for west side of building 6 - start location is 1000' south from northwest corner, 100' west, 100' (continue) Batch time: 06:05am Concrete: Ticket No: 18612 Unit Weight (pcf): NA Sample Location: 50' south, 40' west from start location Fracture Type Type2 Type3 Type5 Type2 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exdusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/KW) Page 1 of 13 Rone Engineering ., Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 310881 Project No.: 0713408 Date of Service: 01/16/2008 Report Date: 03/13/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in') (Ibs) (psi) 2 1 01/23/2008 7 6.00 28.27 115,390 4,080 2 2 02/13/2008 28 6.00 28.27 162,990 5,760 2 3 02/13/2008 28 5.98 28.09 173,060 6,160 Average 5,960 2 4 03/12/2008 56 6.00 28.27 181,910 6,430 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: 1 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1 064 ASTM C-138 ASTM C-39 ~~ ~m 5IE ~ DO D Type 1 Type 2 Type 3 Type 4 Type 5 Batch time: 07:05am Concrete: 600F Ticket No: 18619 Unit Weight (pcf): NA Measured Slump (inches) 6.5 Mix Design 1.0.: 7753 PW6 Placement Date: 01/16/2008 Weather Conditions: Clear Time Sampled: 07:15am Temperature - Air: 480F Truck No: 135 Air Content: 6.5% Overall Placement Location: Paving for west side of building 6 - start location is 1000' south from northwest corner, 100' west, 100' (continue) Sample Location: North from 9th set of ballards from north ramp, 90' west from building Fracture Type Type3 Type5 Type2 Type2 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition. appearance, etc.) or any other feature of similar sUbject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CHIKW) Page 3 of 13 Rone Engineering . Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 310881 Project No.: 0713408 Date of Service: 01/16/2008 Report Date: 03/13/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA . REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in2) (Ibs) (psi) 3 1 01/23/2008 7 6.00 28.27 104,880 3,710 3 2 02/13/2008 28 6.00 28.27 164,210 5,810 3 3 02/13/2008 28 6.00 28.27 153,530 5,430 Average 5,620 3 4 03/12/2008 56 6.00 28.27 176,240 6,230 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: 1 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1 064 ASTM C-138 ASTM C-39 ~EJ ~cg [U [SJ DO D Type 1 Type 2 Type 3 Type 4 Type 5 Batch time: 07:49am Concrete: 600F Ticket No: 18629 Unit Weight (pcf): NA Measured Slump (inches) 6.5 Mix Design I.D.: 7753 PW6 Placement Date: 01/16/2008 Weather Conditions: Clear Time Sampled: 08:00am Temperature - Air: 490F Truck No: 139 Air Content: 6.5% Overall Placement Location: Paving for west side of building 6 - start location is 1000' south from northwest corner, 100' west, 100' (continue) Sample Location: South of 9th set of ballards from north ramp, 90' west from building Fracture Type Type2 Type2 Type2 Type3 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar sUbject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/KW) Page 5 of 13 Rone Engineering .. Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 310881 Project No.: 0713408 Date of Service: 01/16/2008 Report Date: 03/13/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Set No. Tested (days) (in) (in2) (Ibs) (psi) 4 1 01/23/2008 7 6.00 28.27 129,410 4,580 4 2 02/13/2008 28 6.00 28.27 175,220 6,200 4 3 02/13/2008 28 6.00 28.27 179,750 6,360 Average 6,280 4 4 03/12/2008 56 6.00 28.27 189,710 6,710 Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: 1 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1 064 ASTM C-138 ASTM C-39 0E:3 ~lQ [}IE t] DO D Type 1 Type 2 Type 3 Type 4 Type 5 Batch time: 08:48am Concrete: 640F Ticket No: 18641 Unit Weight (pet): NA Measured Slump (inches) 6.5 Mix Design I.D.: 7753 PW6 Placement Date: 01/16/2008 Weather Conditions: Cloudy Time Sampled: 09:00am Temperature - Air: 450F Truck No: 139 Air Content: 5.4% Overall Placement Location: Paving for west side of building 6 - start location is 1000' south from northwest corner, 100' west, 100' (continue) Sample Location: 660' south, 10' west from start location Fracture Type Type2 Type5 Type2 Type3 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/KW) Page 7 of 13 Rone Engineering .. Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 310881 Project No.: 0713408 Date of Service: 01/16/2008 Report Date: 03/13/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: 1 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Batch time: 09:53am Concrete: 630F Ticket No: 18651 Unit Weight (pcf): NA Measured Slump (inches) 6.75 Mix Design I.D.: 7753 PW6 Placement Date: 01/16/2008 Weather Conditions: Cloudy Time Sampled: 10:30am Temperature - Air: 470F Truck No: 133 Air Content: 4.2% Overall Placement Location: Paving for west side of building 6 - start location is 1000' south from northwest corner, 100' west, 100' (continue) Sample Location: 800' south, 40' west from start location REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in2) (Ibs) (psi) Type 5 1 01/23/2008 7 6.00 28.27 116,410 4,120 Type2 5 2 02/13/2008 28 6.00 28.27 142,750 5,050 Type5 5 3 02/13/2008 28 6.00 28.27 145,050 5,130 Type2 Average 5,090 5 4 03/12/2008 56 5.99 28.18 161,220 5,720 Type5 [JE:J ~(..~;' d\ r ......Jl~ __woA, Type 2 mE lJ DO D Type 1 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (CH/KW) Page 9 of 13 Client: Duke Construction, LP 14241 Dallas Pkwy, Ste 1000 Dallas, TX 75254-2936 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Report No.: 310881 Project No.: 0713408 Date of Service: 01/16/2008 Report Date: 03/13/2008 Project: Point West VI Coppell, Texas Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards, PROJECT DATA Contractor: Duke Construction, LP Concrete Supplier: Potter Concrete Plant: 1 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 4" - 6" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1,2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Batch time: 11:04am Concrete: 680F Ticket No: 18661 Unit Weight (pet): NA Measured Slump (inches) 5.75 Mix Design 1.0.: 7753 PW6 Placement Date: 01/16/2008 Weather Conditions: Cloudy Time Sampled: 11 :35am Temperature - Air: 480F Truck No: 135 Air Content: 3,3% Overall Placement Location: Paving for west side of building 6 - start location is 1000' south from northwest corner, 100' west, 100' (continue) Sample Location: 900' south, 35' west from start location REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in2) (Ibs) (psi) Type 6 1 01/23/2008 7 6.00 28.27 120,680 4,270 Type2 6 2 02/13/2008 28 6.00 28.27 153,880 5,440 Type6 6 3 02/13/2008 28 6.00 28.27 159,060 5,630 Type2 Average 5,530 6 4 03/12/2008 56 6.00 28.27 171,520 6,070 Type2 ~Ej ~.u~ ~J~ Type 2 5I] ~ DO D Type 1 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd, (CH/KW) Page 11 of 13