REPORT OF FIELD
COMPACTION TESTS
PROJECT:
DATE: 05/09/08
TESTED FOR:
Alexander Court
Coppell, Texas
OUR REPORT NO.: 070021-52
TEST DATA:
TEST ~. SOIL ID OPTIMUM MAXIMUM LAB IN PLACE IN PLACE PERCENT
NO. DATE DEPTH NUMBER MOISTURE DRY DENSITY MOISTURE DRY DENSITY COMPACTION COMMENT*
% PCF % PCF
r
194 05/09/08 FG 3 13.0 115.4 12.1 111 96 1-A
195 05/09/08 FG-1.0 3 13.0 115.4 11.8 105 91 1-BC
196 05/09/08 FG 3 13.0 115.4 12.7 104 90 1-B
197 05/09/08 FG 3 13.0 115.4 12.3 113 98 1-A
198 05/09/08 FG 3 13.0 115.4 10.1 104 90 1-BC
~
198 FUTURE SCREEN WALL AT STATION 1+00
TEST LOCATION:
194 FUTURE SCREEN WALL AT STATION 4+90
195 FUTURE SCREEN WALL AT STATION 3+00
196 FUTURE SCREEN WALL AT STATION 3+05
197 FUTURE SCREEN WALL AT STATION 2+40
1. FILL
2. NATURALSUBGRADE
3. LIME STABILIZED
4. CEMENT TREATED
. A. IN PLACE PERCENT MOISTURE AND PERCENT COMPACTION COMPLY WITH SPECIFICATIONS
B. PERCENT COMPACTION DOES NOT COMPLY WITH SPECIFICATIONS
C. PERCENT IN PLACE MOISTURE DOES NOT COMPLY WITH SPECIFICATIONS
D. RETEST
Respectfully Submitted,
-/~
Tom Ellis
ALPHA TESTING, INC.