Vista Ridge Retail-LR080227
FIELD DENSITY TESTING
Report Number: 94071386.0027
Service Date: February 11, 2008
lrerracon
8901 Carpenter Frwy, Ste #1 00
Dallas, Texas 75247
(214) 630-1010
Client:
United Commercial Devel
Attn: Robert Dorazil
7001 Preston Rd Ste 500
Dallas TX 75205
Report Date:
Project:
February 27, 2008
Vista Ridge Retail Lots 6 & 7
NEC of 121 & Denton Tap Rd.
Coppell, TX
Material
No.
Description and Classification
Dark brown and light brown clayey sand mix
Dark brown and light brown clayey sand mix
Project No.: 94071386
Lab Test Data
Optimum Max. Lab
Water Dry Unit
Content Weight
(% ) (pcf)
19.1 104.4
19.1 104.4
Proiect Requirements
Material Information
Laboratory
Test Method
Water
Content
(%)
-1/+3
>/= +4
Minimum Dry
Unit Weight
(% compaction)
1 713860003 ASTM D 698
2 713860003 ASTM D 698
Field Test Data
Test
No.
95
92
Test Location
Probe Water Dry Unit Dry Unit
Li ft/ Mat. Depth Content Weight Weight
Elev. No. (inches) (%) (pcf) (% compaction)
7' BFG 1 6 19.5 103.2 99
6' BFG 1 6 19.1 99.8 96
5' BFG 1 6 19.9 104.4 100
3' BFG 2 6 23.7 98.4 94
3' BFG 2 6 24.0 97.2 93
3' BFG 2 6 25.8 96.6 93
2' BFG 2 6 24.2 97.1 93
2' BFG 2 6 25.0 96.9 93
2' BFG 2 6 24.2 98.5 94
Storm Sewer Line 1
155 Sta. 3+35
156 Sta. 3+35
157 Sta. 3+35
Building 1 Pad
158 175' s & 240' W of NE corner bldg
159 180' S & 140' W of NE corner bldg
160 190' S & 30' W of NE corner bldg
161 170' S & 250' W of NE corner bldg
162 180' S & 150' W of NE corner bldg
163 190' S & 35' W of NE corner bldg
Datum: BFG = below final grade
Comments:
Test results on this report meet project specification.
Services _ Perform in-place density and moisture content tests to determine degree of compaction and material moisture
condition.
Field Test Method: ASTM D-2922, ASTM D-3017
Terracon Rep: Bradley W.Hatch
Field Results Reported To: Jay, Lee Lewis
Report Distribution:
(1) United Commercial Oevel (1) O'Brien & Assoc
(1) Winkelmann & Assoc Inc Reviewed by:
(1) City of Coppell TX . . Bu nt Ethem P.G.
(1) Lee LewIs Construction Inc I '
I Project Manager
The tests were performed in general accordance with applicable ASTM, AASHTO, or DOT test methods. This report is ~USiVeIY for the use of the client
indicated above and shall not be reproduced except in full without the written consent of our company. Test results transmitted herein are only applicable
to the actual samples tested at the location(s) referenced and are not necessarily indicative of the properties of other apparently similar or identical
materials.
Page 1 of 1