Chicken Express-LR080521
l rio~ ., Information
~..,. .To Build On
Engine""'" . Consulting . JHtfng
REPORT OF CONCRETE COMPRESSION TEST
TESTED FOR:
RANDY HYNES
RANDY HYNES GENERAL CONTRACTOR
101 TRINITY VIEW RD
WEATHERFORD, TX 76087
DATE:
May 21, 2008
PSI REPORT NO.: 341-80040-4
FIELD DATA:
LOCATION OF PLACEMENT
PROJECT: CHICKEN EXPRESS RESTAURANT
COPPELL, TX
Paving
Beltline Westbound Right Turn Lane
DATE PLACED
TIME
SLUMP, IN.
AIR CONTENT, %
AIR TEMPERATURE, OF
CONCRETE TEMPERATURE OF
DATE RECEIVED IN LAB
FIELD DATA SUBMITTED BY
MIX DATA SUBMITTED BY
May 21, 2008
01 : 45 pm
5 1/2
5.2
77
82
May 22, 2008
PSI\Ronnie Yeoman
Southern Star
SUPPLIER
DELIVERY TICKET NO/TRUCK NO.
MIX NUMBER AND PROPORTIONS
CEMENT
WATER
FINE AGGREGATE
COARSE AGGREGATE
ADMIXTURE
Southern Star
1271448
9375
NOTE' APPLICABLE ASTM STANDARDS UNLESS on.IERWISE INDICATED' SLUMP' C143' AIR CONTENT' C231 (EXCLUDING see 6)' TEMPERATURE- C1084' CYLINDERS' C31 (EXCLUDING SEe 1012\' SAMPLING' C172
COMPRESSION TEST RESULTS
ASTM C39; C1231
SPECIMEN TEST TOTAL CYLINDER CYLINDER COMPRESSIVE TYPE OF BREAK,
LABORATORY IDENTIFICATION AGE DATE OF LOAD DIAMETER AREA STRENGTH AS SHOWN IN
NUMBER OR SET NO. (DAYS) TEST (LBS.) (IN.) (sa. IN.) (PSI) ASTM C39
935 A 7 OS/28/08 95420 6.00 28.27 3380 Type 3
935 B 28 06/18/08
935 C 28 06/18/08
935 D H HOLD
SPECIFICATIONS
28 4500
REMARKS: ~ Cylinders made by PSI representative.
Cylinders picked up by PSI
~ representative.
Cylinders made by Architect's or
Contractor's representative.
Test results comply with applicable
specifications.
Cylinders delivered to PSI laboratory.
Test results do not compiy with
applicable specifications.
TECHNICIAN:
William Miller
cc: Hynes
Respectfully submitted,
Professional Service Industries, Inc.
THESE TEST RESULTS APPl Y ONLY TO THE SPECIFIC SAMPLES TESTED AND MAY NOT BE INDICATIVE OF THE ENTIRE CONCRETE PLACEMENT.
REPORTS MAY NOT BE REPRODUCED. EXCEPT IN FUll. WITHOUT WRITTEN PERMISSION BY PROFESSIONAL SERVICE INDUSTRIES. INC.
PSI A-200-4N F
Professional Service Industries, Inc.. 4087 Shilling Way. Dallas, TX 75237. Phone 214/330-9211 . Fax 214/467-0031
l-,,~.'InfomwJion
~~. .To Build On
EngIneerfng . Consulllng . TestIng
REPORT OF FIELD TESTING OF CONCRETE
TESTED FOR:
RANDY HYNES
RANDY HYNES GENERAL CONTRACTOR
101 TRINITY VIEW RD
WEATHERFORD, TX 76087
PROJECT: CHICKEN EXPRESS RESTAURANT
COPPELL, TX
DATE:
May 21, 2008
PSI REPORT NO.: 341-80040-3
FIELD DATA:
Concrete was a 4500 psi mix delivered by Southern Star,
mix number 9375.
NO. OF CONCRETE CUBIC TEMPERATURE, OF
SPECIMENS SUPPLIER TIME TRUCK TIME TRUCK YARDS OF AIR
SET NO. MADE TICKET NUMBER DISPATCHED UNLOADED CONCRETE SLUMP, in. CONTENT, % AIR CONCRETE
935 4 1271448 01:12 pm 02:00 pm 9.0 5 1/2 5.2 77 82
lOCATION:
Paving
935
Beltline Westbound Right Turn Lane
NOTE: APPLICABLE ASTM STANDARDS. UNLESS OTHERWISE INDICATED: MAKING SPECIMENS: C31 (EXC. SEC. 10 1.2): SLUMP: C143; AIR CONTENT C231 (EXC. SEC. 6); TEMPERATURE: C1064; SAMPLING: C172
REMARKS:
TECHNICIAN:
Ronnie Yeoman
Respectfully submitted,
Professional Service Industries, Inc.
cc: Hynes
THESE TEST RESULTS APPLY ONLY TO THE SPECIFIC SAMPLES TESTED AND MAY NOT BE INOlCA TIVE OF THE ENTIRE CONCRETE PLACEMENT
REPORTS MAY NOT BE REPROOUCED. EXCEPT IN FULL. WITHOUT WRITTEN PERMISSION BY PROFESSIONAL SERVICE INDUSTRIES, INC.
PSI A-200-1 (6)F
Professional Service Industries, Inc.. 4087 Shilling Way. Dallas, TX 75237. Phone 214/330-9211 . Fax 214/467-0031