August 20, 2008
City Of Coppell
255 Parkway Boulevard
Coppell, Texas 75019
Attention:
Ms. DiWanna Baskin, Graduate Engineer
Engineering Department
Subject:
ADDENDUM-Letter on Proposed Pavement Section
Proposed Four Residences & Pavement At
Lots 1-4 &':lX,:Block-A
1.96 Acre Site, Bellacere Addition
-300 West Sandy Lake 'Road
"Coppell , Da1Ias-" County ~ Texas
SE&T Soil No: 169GX4K8 Dated 5-14-2008
SE&T Current Project No: 334EX4K8
Madam:
SAM Engineering & Testing, L.P. (SE&T) is pleased to submit this addendum
letter on the proposed pavement section at the subject site.
1. Background
SE&T performed the seven soil test borings soil report for the subject
project (SE&T #169GX4K8 dated 5-14-2008) containing our recommendations on
selection, designs & construction of the proposed four residences &
pavement.
2. Paving plan #C30 by Hamilton-Duffy and e-mail by Mr. Tommy Cansler
showed the proposed pavement section Gomprising of the following minimum
thicknesses from the-surface down:
8 em. (3. 15 " )
0.75"-1"
5"
6"
thick pavestone pavers.
thick sand base.
thick 3600 psi concrete with #3 rebars @ 18" a/c.
thick subgrade compacted to 95% of ASTM D698A.
City Of Coppell
SE&T Project No. 334EX4K8
August 20, 2008
Page 2 of 2
Geotechnical
Materials ~ Failure
Testing Vlnvestigation
Environmental
3. Based on the above supplied section, our above subsurface data & our
experience with similar projects, SE&T recommends that the above
proposed pavement is considered SATISFACTORY with the following
modifications/adjustments:
The concrete to be a 4,000 psi/28 days (6 sack minimum).
The upper 12" of the sugrade under the pavement should be compacted &
tested to a minimum of 95 % of ASTM D-698A.
SE&T should perform all CMT testing & inspections.
4. All other listed recommendations in our above soil report should be
followed.
It has been a pleasure serving you on this project and we trust that this
report is satisfactory. Should you desire any additional services pursuant
to this report, either in additional consultations or construction testing,
please do not hesitate to contact us.
~~~
;,),~\\,
.\~
,
Very truly yours,
SAM Engineering & Testing, L.P.
Sadik (Sam) Al-musawe, M.Sc., Ph.D., P.E., F.ASCE,
Civil & Environmental Engineer
Texas Professional Registration No: 61893
2-10 Home Buyers Warranty (HBW) No. 8827
Home of Texas/Residential Warranty Corporation (RWC) No. 633
Bonded Builders Home Warranty No. TXG025
cc. Mr. Tom F. Whatley, President-Heritage Development
Mr. Micha P. Duffy, P.E.-Hamilton-Duffy
Mr. Tommy Cansler-Timberland Creek Companies