CONCRETE, GROUT, AND MORTAR TESTS
LETTER OF TRANSMITTAL
TI!XAS
TO: City of Coppell
P.O. Box 9478
DATE: 03/07/2008
RE: Bethel Road - Coppell
Coppell, TX 75019
ATTN: Mr. Rick O'Dell
PERMIT #:
JOB NO.: 005061
LOCATION:
Bethel Road, Coppell, TX
Weare enclosing:
X Attached
Materials Engineering Division Concrete Reports:
122, 123, 124
X
X
For Your Use
X
As Requested
CC: TISEO Paving - Robert Caudill
City of Coppell - Rick O'Dell
tJJi? L
Davicf A. Lewis, P.E.
Principal Engineer
~(l~
Eric L. Branch, C.E.T.
Project Manager
By:
Project:
Location:
Bethel Road - Coppell
Bethel Road, Coppell, TX
Concrete Cylinders Strength Report
Project: 5061 Set Designation: A
Cast Date: 02/29/2008
Design Strength: 4000 psi
Report No.: 122
~ ECS Texas, LLP
~ 4950 Keller Springs Road, Suite 480
Addison, TX 7500]
(972) 392-3222
(FAX) 392-0 I 02
_TIIXAS
Owner: City of Coppell - Rick O'Dell Client: City of Coppell - Kenneth M. Griffin,
Arch.: Gen. Contr.:
Struc. Eng.: Cone. Contr.:
Placement Location: Stamped concrete for Entech, 1000 ft East of Royal Lane on Bethel Rd
Concrete Supplier: Southern Star
Mix Designation: 9363
Added Water:
Truck No: 931
Mix Strength: 4000 pSI
Time Added:
Ticket No:
Batch Time:
Unit Wt.:
1214324
09:45AM
FIELD TEST DATA: Tested by: Jonathan E. Steiner
Temperature - Air: 700 F
Time Sampled: 1 0:20AM
Concrete: 740 F
Slump:4.00 in.
Air Content:3.20 % (P)
Sample Test Test Type Diameter Area Breaking Compr. Brk Break Review
No Date Age Cure In. In.2 Load,lbs Str.,psi Typ by by
39365 03/07/2008 7 Lab 4.00 12.56 51936 4130 ELBl
39366 03/28/2008 28 Lab 4.00 12.56
39367 03/28/2008 28 Lab 4.00 12.56
39368 04/25/2008 56 Lab 4.00 12.56
. . . .
Sampling in accordance With (iaw) ASTM C172, except that samples may have been taken from the beginning of the load after a minimum discharge of approximately one cubic yard.
Cylinder molding and laboratory curing iaw ASTM C31, compressive strength test and break type iaw ASTM C39. slump iaw C143, air content iaw ASTM C173 (V) or C231 (P),
temperature iaw ASTM Cl064, and unit weight iaw ASTM C138. Cylinders are tested using unbonded caps iaw ASTM C1231 or are capped using sulphur
mortar jaw C617. Break Types are classified as: Type 1,2,3,4,5, or 6 iaw C39-04a
FIELD CURING CONDITIONS:
Curing Box
X No Curing Box
Remarks:
Insulated
Heated
Cooled
X Caps
Ice
Other
Final Review By:
ELBl
Print Date:
03/0712008
Concrete Cylinders Strength Report
N ECS Texas, LLP
~ 4950 Keller Springs Road, Suite 480
Addison, TX 7500]
(972) 392-3222
(FAX) 392-0 I 02
11!XAS
Project:
Location:
Bethel Road - Coppell
Bethel Road, Coppell, TX
Project: 5061
Cast Date:
Design Strength:
Report No.:
Set Designation: B
02/29/2008
3600 psi
123
Owner: City of Coppell - Rick O'Dell Client: City of Coppell - Kenneth M. Griffin,
Arch.: Gen. Contr.:
Struc. Eng.: Conc. Contr.:
Placement Location: Box culvert walls, sampled at Sta. 44+50
Concrete Supplier: LMC
Mix Designation: 170 I
Added Water: 5 Gals.
Truck No: 7060
Mix Strength: 3600 pSi
Time Added: --:-
Ticket No: 7189201
Batch Time: 01:36PM
Unit Wt.:
FIELD TEST DATA: Tested by: Jonathan E. Steiner
Temperature - Air: 760 F
Time Sampled:02: 15PM
Concrete: 790 F
Slump: 5.00 in.
Air Content:6.00 % (P)
Sample Test Test Type Diameter Area Breaking Compr. Brk Break Review
No Date Age Cure In. In.2 Load,lbs Str.,psi Typ by by
39377 03/07/2008 7 Lab 4.00 12.56 49408 3930 ELBl
39378 03/28/2008 28 Lab 4.00 12.56
39379 03/28/2008 28 Lab 4.00 12.56
39380 04/25/2008 56 Lab 4.00 12.56
. . . .
Sampfing In accordance With (law) ASTM Cl72, except that samples may have been taken from the beginning of the load after a minimum discharge of approximately one cubiC yard.
Cylinder molding and laboratory curing iaw ASTM C3l, compressive strength test and break type law ASTM C39, slump iaw C143, air content iaw ASTM C173 M or C23l (P),
temperature iaw ASTM Cl064, and unit weight iaw ASTM C138. Cylinders are tested using unbonded caps iaw ASTM C123l or are capped using sulphur
mortar iaw C6l7. Break Types are classified as: Type 1,2,3,4,5, or 6 iaw C39-04a
FIELD CURING CONDITIONS:
Curing Box
X No Curing Box
Remarks:
Insulated
Heated
Cooled
X Caps
Ice
Other
Final Review By:
ELBl
Print Date:
03/07/2008
Concrete Cylinders Strength Report
'" ECS Texas, LLP
~ 4950 Keller Springs Road, Suite 480
Addison, TX 75001
(972) 392-3222
(FAX) 392-0102
_1"I!XA8
Project:
Location:
Bethel Road - Coppell
Bethel Road, Coppell, TX
City of Coppell - Rick O'Dell
Project: 5061
Cast Date:
Design Strength:
Report No.:
Set Designation: C
02/29/2008
4000 psi
124
Owner:
Arch.:
Struc. Eng.:
Placement Location: Inlet top at East entrance to Cici's.
Client: City of Coppell - Kenneth M. Griffin,
Gen. Contr.:
Conc. Contr.:
Concrete Supplier: Southern Star
Mix Designation: 9363
Added Water:
Truck No: 1020
Mix Strength: 4000 psi
Time Added:
Ticket No: 1214859
Batch Time: 01 :52PM
Unit Wt.:
FIELD TEST DATA: Tested by:Jonathan E. Steiner
Temperature - Air: 780 F
Time Sampled:03 :OOPM
Concrete: 800 F
Slump: 3.50 in.
Air Content:} .30 % (P)
Sample Test Test Type Diameter Area Breaking Compr. Brk Break Review
No Date Age Cure In. In.2 Load,lbs Str.,psi Typ by by
39381 03/07/2008 7 Lab 4.00 12.56 44288 3520 ELB1
39382 03/28/2008 28 Lab 4.00 12.56
39383 03/28/2008 28 Lab 4.00 12.56
39384 04/25/2008 56 Lab 4.00 12.56
. .
Samp6ng In accordance With (law) ASTM C172, except that samples may have been taken from the beginning of the load after a minimum discharge of approximately one cubic yard.
Cylinder molding and laboratory curing iaw ASTM C31, compressive strength test and break type iaw ASTM C39, slump iaw C143, air content iaw ASTM C173 (V) or C231 (P),
temperature iaw ASTM C1064, and unit weight iaw ASTM C138. Cylinders are tested using un bonded caps iaw ASTM C1231 or are capped using sulphur
mortar iaw C617. Break Types are classified as: Type 1,2,3,4,5, or 6 iaw C39-04a
FIELD CURING CONDITIONS:
Curing Box
X No Curing Box
Remarks:
Insulated
Heated
Cooled
X Caps
Ice
Other
Final Review By:
ELB1
Print Date:
03/07/2008
ECS Texas. LLP
4950 Keller Springs Road, Suite 480
Addison, TX 75001
(972) 392-3222
(FAX) 392-0102
LETTER OF TRANSMITTAL
gs:
TEXAS
March 7, 2008
RE: Bethel Road - CoppeIl
City of Coppell
P.O. Box 9478
Coppell, TX 75019
ECS Job # 19:5061
Pennits:
A TTN: Mr. Rick O'Dell
Location: Bethel Road
CoppeIl, TX
We are enclosing:
--L Materials Engineering Division Reports
--L For your use
--L As requested
CC: TISEO Paving - Robert Caudill
ENCL:
Field Report # 156
03/05/2008
f~~d~'J
~ C(3~
Eric L. Branch, C.E.T.
Project Manager
Principal Engineer
'" ECS Texas. LLP
E 4950 Keller Springs Road, Suite 480
Addison, TX 75001
(972) 392-3222
(FAX) 392-0102
FIELD REPORT
Project No.
Report No.
Day & Date
Weather
On-Site Time
Lab Time
Travel Time*
Total
Re Obs.Time
TI!XA8
Project Bethel Road - Coppell
Location Coppell, TX
Client City of Coppell - Rick O'Dell
Remarks
Trip Charges*
Chargeable Items
19:5061
156
Wednesday 03/05/2008
620/ Sunny
2.00
0.00
1.00
3.00
0.00
18.00
Tolls/Parking* $0.40
Mileage*
Time of Arrival Departure
01:30P 03:30P
* Travel time and mileage will be billed in accordance with the contract.
Summary of Services Performed (field test data, locations, elevations & depths are estimates) & Individuals Contacted.
The undersigned arrived on site, as requested, to observe:
1. The placement of 60 cubic yards of 4000 psi concrete for box culvert deck at Bethel Rd.
The required test limits were determined to be a slump of 3-6 inches, batch to placement time of
<90 minutes, and concrete temperature range of <90 degrees Fahrenheit.
Concrete observed on this date appeared to be placed in compliance with project specifications
with regard to temperature, slump, and batch to placement time. The air content was slightly
below the project requirements.
The following samples were obtained for compressive strength testing in our laboratory:
SetA:
6 cylinders of 4000 psi concrete for compressive strength testing.
By David L. Hunt, - Field Technician