Chateaus-LR081002 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 4601 Old Shepard Place Plana, TX 75093 Report No.: 331915 Project No.: 0814523 Date of Service: 09/02/2008 Report Date: 10/02/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Concrete Supplier: LMC Plant: 7 Specification Requirements Strength: Slump (in.): Air (%): Test Method: NA NA ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design I.D.: 1701 Placement Date: 09/02/2008 Weather Conditions: Cloudy, windy Time Sampled: 02:05pm Batch time: 01:16pm Temperature - Air: 940F Concrete: 930F Truck No: 1045 Ticket No: 7197441 Air Content: 2.1 % Unit Weight (pet): NA Overall Placement Location: Inlet footings, Station 3+75 Measured Slump (inches) 4.25 Sample Location: East footing REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (In2) (Ibs) (psi) Type 1 1 09/09/2008 7 5.99 28.18 98,030 3,480 Type2 1 2 09/30/2008 28 6.00 28.27 119,990 4,240 Type3 1 3 09/30/2008 28 6.00 28.27 127,610 4,510 Type2 Average 4,380 4 10/28/2008 56 0L3 ~~ [ill] t;J DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 1 of 2 Rone EngineE!ring . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 4601 Old Shepard Place Plana, TX 75093 Report No.: 329633 Project No.: 0814523 Date of Service: 08/05/2008 Report Date: 10/02/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Concrete Supplier: LMC Plant: 7 Specification Requirements Strength: 4,200 psi @ 28 days Slump (in.): 2" - 3" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design I.D.: 1851 Placement Date: 08/05/2008 Weather Conditions: Partly cloudy Time Sampled: 01 :40pm Batch time: 12:24pm Temperature - Air: 980F Concrete: 960F Truck No: 1087 Ticket No: 7196411 Air Content: NA Unit Weight (pct): NA Overall Placement Location: Manhole, line A, Stations 3+08.83 and 5+84 Measured Slump (inches) 2.5 Sample Location: Manhole, Station 5+84 line A REPORT OF TESTS 5'1{' o 0 28.1 ftv;~age 28.~24,880 fl' R.mar~: ~.Revisoo on 9/1~OB to re;;;;jB ;jth ~rement... Cylinder Marked Set No. - - 1 1 Date Tested 08/12/2008 Age (days) 7 Diameter (In) 5.99 2 3 09/02/2008 09/02/2008 28 28 4 09/30/2008 56 ~t:j [g!]Q] mJ lSJ DO D Type 1 Type 2 Type 3 Type 4 Type 5 Concrete Compressive Cylinder 6" x 12" Maximum Load Compressive Strength (psi) 3,370 Area (In2) 28.18 Fracture Type Type2 5.99 5.99 Type4 Type2 4,260 4,310 4,280 4 20 6.00 Type2 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd. (GD/CL) Page 1 of 2 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC Report No.: 329757 4601 Old Shepard Place Project No.: 0814523 Piano, TX 75093 Date of Service: 08/06/2008 Report Date: 10/02/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Concrete Supplier: LMC Plant: 7 Specification Requirements Strength: 4,200 psi @ 28 days Slump (in.): 2" - 3" Air (%): NA Test Method: ASTM C-172 ASTM C-31 (except 10. ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design 1.0.: 1851 Placement Date: 08/06/2008 Weather Conditions: Cloudy Time Sampled: 01 :30pm Temperature - Air: 950F Truck No: 1087 Air Content: 4.5% Overall Placement Location: Manhole, Station 8+82 and Station 13+15 Batch time: 12:06pm Concrete: 900F Ticket No: 7196466 Unit Weight (pet): NA Measured Slump (inches) 3.5 .. Sample Location: Station 8+82 h/-L REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (InZ) (Ibs) (psi) Type 1 1 08/13/2008 7 5.99 28.18 124,800 4,430 Type5 1 2 09/03/2008 28 5.99 28.18 135,020 4,790 Type5 1 3 09/03/2008 28 5.99 28.18 133,950 4,750 Type2 Average 4,770 4 1 % 1/2008 56 5.99 28.18 147,190 5,220 Type2 ~~ ~[g [ill] bJ DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 o /~/6/Zf LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to .whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (GD/CL) Page 1 of 2 Rone Engineering II 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC Report No.: 332039 4601 Old Shepard Place Project No.: 0814523 Plana, TX 75093 Date of Service: 09/03/2008 Report Date: 10/02/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Concrete Supplier: Lattimore Plant: 6 Specification Requirements Strength: 4,000 psi @ 28 days Slump (in.): 3" - 5" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design 1.0.: 1701 Placement Date: 09/03/2008 Weather Conditions: Cloudy, windy Time Sampled: 02:50pm Batch time: 02:01 pm Temperature - Air: 760F Concrete: 800F Truck No: 5013 Ticket No: 6337170 Air Content: 4.1 % Unit Weight (pet): NA Overall Placement Location: Inlet bottoms, Montebello Drive and walls, Station 2+75 Measured Slump (inches) 3.5 Sample Location: Inlet bottom and walls, same as above REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (In) (In2) (Ibs) (psi) Type 1 1 09/10/2008 7 5.99 28.18 112,610 4,000 Type5 1 2 10/01/2008 28 5.99 28.18 156,160 5,540 Type2 1 3 10/01/2008 28 5.99 28.18 158,050 5,610 Type2 Average 5,580 4 10/29/2008 56 0~ ~Q] fJ] 5] DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/Cl) Page 1 of 2