Chateaus-LR081017 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Piano, TX 75074 Report No.: 335337 Project No.: 0814523 Date of Service: 10/08/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Concrete Supplier: Redi-Mix Plant: 259 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 4" - 5" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design 1.0.: 536L 1524 Placement Date: 10/08/2008 Weather Conditions: Clear Time Sampled: 08:06am Temperature - Air: 580F Truck No: 1293 Air Content: 4.3% Overall Placement Location: Paving, Station 13+00 to 0+00 Batch time: 06:53am Concrete: 790F Ticket No: 59033970 Unit Weight (pet): NA Measured Slump (inches) 4.5 Sample Location: Station 12+16 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Marked Date Age Diameter Area Load Set No. Tested (days) (in) (in2) (Ibs) 1 1 10/15/2008 7 5.99 28.18 108,450 1 2 11/05/2008 28 1 3 11/05/2008 28 1 4 12/03/2008 56 Fracture 'Type Type2 ~~ ~~ 51] ~ DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CLl Page 1 of 9 Rone Engineering 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Report of Concrete Compressive Strength Test CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335337 Project No.: 0814523 Date of Service: 10/08/2008 Report Date: . 10/17/2008 Proje'ct: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Concrete Supplier: Redi-Mix Plant: 259 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 4" - 5" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10,1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design I.D.: 536L 1524 Placement Date: 10/08/2008 Weather Conditions: Clear Time Sampled: 08:56am Temperature - Air: 590F Truck No: 1216 Air Content: 5.3% Overall Placement Location: Paving, Station 13+00 to 0+00 Batch time: 08:23am Concrete: 750F Ticket No: 59033987 Unit Weight (pct): NA Measured Slump (inches) 4.0 Sample Location: Station 10+50 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 2 1 10/15/2008 7 5.99 28:18 108,740 3,860 Type2 2 2 11/05/2008 28 2 3 11/05/2008 28 2 4 12/03/2008 56 ~~ ~[g DJ] E;] DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 2 of 9 Rone Engineering 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, 5te 600, Houston, TX 77040 4421 Freidrich, 5te 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Report of Concrete Compressive Strength Test CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335337 Project No.: 0814523 Date of Service: 10/08/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Concrete Supplier: Redi-Mix Plant: 259 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 4" - 5" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design I.D.: 536L 1524 Placement Date: 10/08/2008 Weather Conditions: Clear Time Sampled: 10:04am Temperature - Air: 690F Truck No: 1388 Air Content: 4.7% Overall Placement Location: Paving, Station 13+00 to 0+00 Batch time: 09:23am Concrete: 800F Ticket No: 59034000 Unit Weight (pet): NA Measured Slump (inches) 3.5 Sample Location: Station 9+18 REPORT OF TESTS Cylinder Marked Date Set No. Tested 3 1 10/15/2008 3 2 11/05/2008 3 3 11/05/2008 3 4 12/03/2008 Age (days) 7 Diameter (in) 5.99 28 28 56 0t:J ~[2] 5J] ~ DO D Type 1 Type 2 Type 3 Type 4 Type 5 Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 106,110 Compressive Strength (psi) 3,770 Fracture Type Type2 Area (in') 28.18 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services. Ltd. (TM/CL) Page 3 of 9 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 . 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Report of Concrete Compressive Strength Test CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Piano, TX 75074 Report No.: 335337 Project No.: 0814523 Date of Service: 10/08/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Concrete Supplier: Redi-Mix Plant: 259 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 4" - 5" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design I.D.: 536L 1524 Placement Date: 10/08/2008 Weather Conditions: Clear Time Sampled: 11 :07am Temperature - Air: 750F Truck No: 1286 Air Content: 4.4% Overall Placement Location: Paving, Station 13+00 to 0+00 Batch time: 10:21am Concrete: 800F Ticket No: 59034014 Unit Weight (pet): NA Measured Slump (inches) 3.0 Sample Location: Station 7+00 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in2) (Ibs) (psi) Type 4 1 10/15/2008 7 5.99 28.18 104,940 3,720 Type2 4 2 11/05/2008 28 4 3 11/05/2008 28 4 4 12/03/2008 56 0E3 ~[g E;] DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responSibility for variation In quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 4 of 9 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335337 Project No.: 0814523 Date of Service: 10/08/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Remarks: Water added at site: 20 gallons LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 5 of 9 Rone Engineering 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Piano, TX 75074 Report No.: 335337 Project No.: 0814523 Date of Service: 10/08/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Concrete Supplier: Redi-Mix Plant: 259 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 4" - 5" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design I.D.: 536L 1524 Placement Date: 10/08/2008 Weather Conditions: Clear Time Sampled: 11 :45am Temperature - Air: 790F Truck No: 1321 Air Content: 4.9% Overall Placement Location: Paving, Station 13+00 to 0+00 Batch time: 10:50am Concrete: 810F Ticket No: 59034023 Unit Weight (pct): NA Measured Slump (inches) 4.0 Sample Location: Station 6+80 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (inZ) (Ibs) (psi) Type 5 1 10/15/2008 7 5.99 28.18 99,180 3,5 Type5 5 2 11/05/2008 28 5 3 11/05/2008 28 5 4 12/03/2008 56 r.8JE3 ~~ 5J] tJ DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/Cl) Page 6 of 9 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335337 Project No.: 0814523 Date of Service: 10/08/2008 Report Date:. 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Contractor: Concrete Supplier: Redi-Mix Plant: 259 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 4" - 5" Air (%): 4% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 PROJECT DATA Mix Design 1.0.: 536L 1524 Placement Date: 10/08/2008 Weather Conditions: Clear Time Sampled: 01 :23pm Temperature - Air: 820F Truck No: 1387 Air Content: 4.7% Overall Placement Location: Paving, Station 13+00 to 0+00 Batch time: 12:24pm Concrete: 840F Ticket No: 59034046 Unit Weight (pet): NA Measured Slump (inches) 4.5 Sample Location: Station 2+60 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (inZ) (Ibs) (psi) Type 6 1 10/15/2008 7 5.99 28.18 98,000 3,480 Type2 6 2 11/05/2008 28 6 3 11/05/2008 28 6 4 12/03/2008 56 ~r:3 ~~ ~ E;] DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMIT A nONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/el) Page 7 of 9 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Piano, TX 75074 Report No.: 335337 Project No.: 0814523 Date of Service: 10/08/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Remarks: Water added at site: 10 gallons LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 8 of 9 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test CTM-Coppell, LLC c/o Lenart Development Co., LLC Report No.: 335472 520 Central Parkway E Project No.: 0814523 Plana, TX 75074 Date of Service: 10/09/2008 Report Date: 10/17/2008 Client: Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Concrete Supplier: Redi-Mix Plant: 136 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 2" - 4" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design I.D.: 536L 1524 Placement Date: 10/09/2008 Weather Conditions: Clear Time Sampled: 07:35am Temperature - Air: 800F Truck No: 1395 Air Content: 4.1 % Overall Placement Location: Bourdeaux Court, Station 3+25 to 1 +45, Corsica Court, Station 2+96.22 to 1 +39 and (cont below) Batch time: 07:00am Concrete: 800F Ticket No: 13624039 Unit Weight (pet): NA Measured Slump (inches) 3.5 Sample Location: Bourdeaux Court, Station 3+25 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (inZ) (Ibs) (psi) ~ Type 1 1 10/16/2008 7 5.99 28.18 123,230 / Type2 2 11/06/2008 28 3 11/06/2008 28 1 4 12/04/2008 56 ~t:j ~~ 5I]b] DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 1 of 15 Rone Engineering " 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Piano, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10/09/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Remarks: Cont: Montebello Drive, Stations 3+50, 5+25, 7+25, 8+50, 10+50 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 2 of 15 Rone Engineering 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Report of Concrete Compressive Strength Test CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10/09/2008 Report Date: 10/17/2008 . Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Concrete Supplier: Redi-Mix Plant: 136 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 2" - 4" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design 1.0.: 536L 1524 Placement Date: 10/09/2008 Weather Conditions: Clear, sunny Time Sampled: 09:35am Batch time: 08:44am Temperature - Air: 800F Concrete: 790F Truck No: 1293 Ticket No: 59034146 Air Content: 3.9% Unit Weight (pct): NA Overall Placement Location: Bourdeaux Court, Station 3+25 to 1 +45, Corsica Court, Station 2+96.22 to 1 +39 and (cont below) Measured Slump (inches) 3.75 Sample Location: Bourdeaux Court, Station 1+45 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in2) (Ibs) (psi) Type 2 1 10/16/2008 7 5.99 28.18 94,810 3,360 Type2 2 2 11/06/2008 28 2 3 11/06/2008 28 2 4 12/04/2008 56 ~r::J [IE][2] 51] [SJ D D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 3 of 15 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Report of Concrete Compressive Strength Test CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Piano, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10/09/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Remarks: Cont: Montebello Drive, Stations 3+50, 5+25, 7+25, 8+50, 10+50 Water added at site: 5 gallons LIMIT A nONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 4 of 15 Rone Engineering .. 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report ~f Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10/09/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Concrete Supplier: Redi-Mix Plant: 136 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 2" - 4" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design I.D.: 536L 1524 Placement Date: 10/09/2008 Weather Conditions: Clear, sunny Time Sampled: 10:55am Batch time: 10:14am Temperature - Air: 840F Concrete: 800F Truck No: 1336 Ticket No: 59034162 Air Content: 4.2% Unit Weight (pct): NA Overall Placement Location: Bourdeaux Court, Station 3+25 to 1 +45, Corsica Court, Station 2+96.22 to 1 +39 and (cont below) Measured Slump (inches) 3.75 Sample Location: Montebello Drive, Station 3+50 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi)~ Type 3 1 10/16/2008 7 5.99 28.18 85,880 /,050 Type5 3 2 11/06/2008 28 3 3 11/06/2008 28 3 4 12/04/2008 56 ~~ ~[2] ~ EJ DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/Cl) Page 5 of 15 Rone Engineering 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10/09/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. . Remarks: Cant: Montebello Drive, Stations 3+50, 5+25, 7+25, 8+50, 10+50 liMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 6 of 15 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Report of Concrete Compressive Strength Test CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Piano, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10/09/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Concrete Supplier: Redi-Mix Plant: 136 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 2" - 4" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design I.D.: 536L 1524 Placement Date: 10/09/2008 Weather Conditions: Clear, sunny Time Sampled: 12:15pm Batch time: 11:10am Temperature - Air: 850F Concrete: 820F Truck No: 1022 Ticket No: 59034174 Air Content: 4.0% Unit Weight (pet): NA Overall Placement Location: Bourdeaux Court, Station 3+25 to 1+45, Corsica Court, Station 2+96.22 to 1+39 and (cont below) Measured Slump (inches) 4.0 Sample Location: Montebello Drive, 5+25 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strerig~ Fracture Set No. Tested (days) (in) (in2) (Ibs) (psi) Type 4 1 10/16/2008 7 5.99 28.18 109,470 /,880 Type2 4 2 11/06/2008 28 4 3 11/06/2008 28 4 4 12/04/2008 56 ~~ ~~ Dm t;] DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 7 of 15 Rone Engineering 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report of Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10/09/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Remarks: Cant: Montebello Drive, Stations 3+50,5+25,7+25,8+50, 10+50 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, LId: (TM/CL) Page 8 of 15 Rene Engineering .. 8908 Ambassador Row. Dallas. TX 75247 7701 W Little York, Ste 600. Houston, TX 77040 4421 Freidrich, Ste 195. Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Report of Concrete Compressive Strength Test CTM-Coppell, LLC c/o Lenart Development Co.. LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10/09/2008 Report Date:. 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Concrete Supplier: Redi-Mix Plant: 136 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 2" - 4" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design I.D.: 536L 1524 Placement Date: 10/09/2008 Weather Conditions: Clear. sunny Time Sampled: 01 :35pm Batch time: 01 :04pm Temperature - Air: 880F Concrete: 810F Truck No: 1180 Ticket No: 59034195 Air Content: 4.8% Unit Weight (pet): NA Overall Placement Location: Bourdeaux Cou'rt, Station 3+25 to 1+45, Corsica Court, Station 2+96.22 to 1+39 and (cont below) Measured Slump (inches) 3.25 Sample Location: Montebello Drive, Station 7+25 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive , Marked Date Age Diameter Area Load Strength /Fracture Set No. Tested (days) (in) (inZ) (Ibs) (psi). Type 5 1 10/16/2008 7 5.99 28.18 114,000 4.050..... Type2 /' 5 2 11/06/2008 28 5 3 11/06/2008 28 5 4 12/04/2008 56 0r3 ~[g 5ru b] DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 9 of 15 Rone Engineering ., 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Report of Concrete Compressive Strength Test CTM-Coppell, LLC cIa Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335472 Project No.: 0814523 . Date of Service: 10109/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Remarks: Cant: Montebello Drive, Stations 3+50, 5+25, 7+25, 8+50, 10+50 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 10 of 15 Rone Engineering .. 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Report of Concrete Compressive Strength Test CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10/09/2008 Report Date: . 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Concrete Supplier: Redi-Mix Plant: 136 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 2" - 4" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design I.D.: 536L 1524 Placement Date: 10/09/2008 Weather Conditions: Clear Time Sampled: 03:10pm Temperature - Air: 900F Truck No: 1375 Air Content: 4.4% Overall Placement Location: Bourdeaux Court, Station 3+25 to 1+45, Corsica Court, Station 2+96.22 to 1+39 and (cont below) Batch time: 02:08pm Concrete: 810F Ticket No: 59034206 Unit Weight (pet): NA Measured Slump (inches) 3.75 Sample Location: Montebello Drive, Station 8+50 REPORT OF TESTS Cylinder Marked Date Set No. Tested 6 1 10/16/2008 6 2 11/06/2008 6 3 11/06/2008 6 4 12/04/2008 Age (days) 7 Diameter (in) 5.99 28 28 56 ~E:J ~[g 5ru E;] DO D Type 1 Type 2 Type 3 Type 4 Type 5 Concrete Compressive Cylinder 6" x 12" Maximum Load (Ibs) 101,730 Compressive Strength (psi) 3,610 Fracture Type Type2 Area (in2) 28.18 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance. etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/el) Page 11 of 15 Rone Engineering 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freidrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Report o~ Concrete Compressive Strength Test Client: CTM-Coppell, LLC c/o Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10/09/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Remarks: Cant: MontebeJlo Drive, Stations 3+50,5+25,7+25,8+50, 10+50 L1MITA nONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 12 of 15 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrich, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Report of Concrete Compressive Strength Test CTM-Coppell, LLC cia Lenart Development Co., LLC 520 Central Parkway E Plana, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10109/2008 Report Date: 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. PROJECT DATA Contractor: Concrete Supplier: Redi-Mix Plant: 136 Specification Requirements Strength: 3,600 psi @ 28 days Slump (in.): 2" - 4" Air (%): 3% - 6% Test Method: ASTM C-172 ASTM C-31 (except 10.1.2) ASTM C-143 ASTM C-231 ASTM C-1064 ASTM C-138 ASTM C-39 Mix Design 1.0.: 536L 1524 Placement Date: 10109/2008 Weather Conditions: Clear, sunny Time Sampled: 03:55pm Batch time: 02:40pm Temperature - Air: 930F Concrete: 820F Truck No: 1339 Ticket No: 59034214 Air Content: 4.0% Unit Weight (pet): NA Overall Placement Location: Bourdeaux Court, Station 3+25 to 1+45, Corsica Court. Station 2+96.22 to 1+39 and (cont below) Measured Slump (inches) 4.0 Sample Location: Montebello Drive, Station 10+50 REPORT OF TESTS Concrete Compressive Cylinder 6" x 12" Cylinder Maximum Compressive Marked Date Age Diameter Area Load Strength Fracture Set No. Tested (days) (in) (in') (Ibs) (psi) Type 7 1 10/16/2008 7 5.99 28.18 102,830 3,650 Type5 7 2 11/06/2008 28 7 3 11/06/2008 28 7 4 12/04/2008 56 [8]~ ~~ 5IE t] DO D Type 1 Type 2 Type 3 Type 4 Type 5 Type 6 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition, appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 13 of 15 Rone Engineering . 8908 Ambassador Row, Dallas, TX 75247 7701 W Little York, Ste 600, Houston, TX 77040 4421 Freldrlch, Ste 195, Austin, TX 78744 Corporate Phone: (214) 630-9745 Client: Report of Concrete Compressive Strength Test CTM-Coppell, LLC clo Lenart Development Co., LLC 520 Central Parkway E Piano, TX 75074 Report No.: 335472 Project No.: 0814523 Date of Service: 10109/2008 Report Date: . 10/17/2008 Project: Chateaus of Coppell Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring samples back to the laboratory for curing and testing in accordance with applicable standards. Remarks: Cont: Montebello Drive, Stations 3+50, 5+25, 7+25, 8+50, 10+50 LIMITATIONS: The test results presented herein were prepared based upon the specific samples provided for testing. We assume no responsibility for variation in quality (composition. appearance, etc.) or any other feature of similar subject matter provided by persons or conditions over which we have no control. Our letters and reports are for the exclusive use of the clients to whom they are addressed and shall not be reproduced except in full without the written approval of Rone Engineering Services, Ltd. (TM/CL) Page 14 of 15