. Report of Concrete Compressive Strength Test
Client:
CTM-Coppell, LLC c/o Lenart Development Co., LLC
520 Central Parkway E
Plana, TX 75074
Report No.: 332920
Project No.: 0814523
Date of Service: 09/12/2008
Report Date: 11/10/2008
Project: Chateaus of Coppell
Services: Obtain samples of fresh concrete at the placement locations, perform required testing, cast compressive strength samples and bring
samples back to the laboratory for curing and testing in accordance with applicable standards.
PROJECT DATA
Contractor:
Concrete Supplier: Lattimore
Plant: 14
Specification Requirements
Strength: 4,200 psi @ 28 days
Slump (in.): 3" - 5"
Air (%): 3% - 6%
Test Method: ASTM C-172
ASTM C-31 (except 10.1.2)
ASTM C-143
ASTM C-231
ASTM C-1064
ASTM C-138
ASTM C-39
Mix Design 1.0.: 1701
Placement Date: 09/12/2008
Weather Conditions: Cloudy
Time Sampled: 03:15pm
Temperature - Air: 920F
Truck No: 3033
Air Content: 4.1 %
Overall Placement Location:
Storm sewer and manhole walls, Montebello Drive, Station 10+09
Batch time: 02:17pm
Concrete: 900F
Ticket No: 14329964
Unit Weight (pet): NA
Measured
Slump
(inches)
4.5
Sample Location:
Manhole, same as above
REPORT OF TESTS
Concrete Compressive Cylinder 6" x 12"
Cylinder Maximum Compressive
Marked Date Age Diameter Area Load Strength
Set No. Tested (days) (in) (In2) (Ibs) (psi)
1 1 09/19/2008 7 5.99 28.18 101,470 3,600
1 2 10/10/2008 28 5.99 28.18 124,300 4,410
1 3 10/10/2008 28 5.99 28.18 129,580 4,600
Average 4,500
4 11/07/2008 56 5.99 28.18 145,990 5,180
Fracture
Type
Type2
Type2
Type2
Type5
~~ ~llJ Em rSl DO D
Type 1
Type 2 Type 3 Type 4
Type 5
Type 6
Remarks: Water added at site: 10 gallons