Loading...
RollingOaks-CS090602 TO: FROM: DATE: REF: 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. THE.CITY.OF corrELL Ii MEMORANDUM Rick O'Dell, Engineering Danny Hightower, Public Works June 2, 2009 Rolling Oaks Memorial Center Need pad around first irrigation valve in Park Need 4' extension valve on first irrigation valve from Park Need pad around first irrigation valve in Oak Memorial Mark IRR in blue on curb at first valve in Oak Memorial First FH missing valve; no marking (FHV) on curb Mark ML V on curb in blue for main line valves Need test paperwork on all Domestic DC's Mark FHV on curb at all Fire Hydrants Mark FL V on valve in red to fire vault Need 3" drainage around vault Need paperwork on DC in vault (6") and bypass Paint lid blue on vault Must be dry in vault to inspect for leak Need grate around pipe inside cap for sewer CO in road Need chimney seal in third manhole Call 972-462-5150 to schedule Danny Hightower to check punch list upon completion.